Operating Manual

LT AC THREE PHASE, FOUR WIRE PANEL MOUNTED
STATIC KWH METER WITH COUNTER DISPLAY
INSTALLATION & OPERATION MANUAL
FRONT VIEW
1.
kWh Counter Display
2.
Phase Indication LED’s
3.
Calibration LED : 15000 imp/kWh for -/5A
CUTOUT DETAILS
WIRING DIAGRAM
The Panel Meter is installed on the cabinet’s
front panel and shall be secured firmly with
cabinet using 4 transparent Clips.
The meter shall be wired as per the following wiring
Diagram :
2
Use 0.5 to 2.5mm Cable for Voltage
2
2
terminals & 3mm to 6mm cable for Current
terminals.
+0.8
92 -0.0mm
3Phase, 4Wire Electronic kWh Meter
CT-2E
k wh
18
+0.8
92 -0.0mm
90mm
P1
S1
P3
S3
FUSE
0 .5A
REAR VIEW
L1
I1
L2
kWh
L3
96mm
N
CAL
P2
S2
G
S
I2
S1
S2
S1
S2
I3
S1
S2
1 PULSE = 1 kWh
HPL-SOCOMEC
96mm
Fig. 2
S, G = PULSE OUTPUT
Fig. 3
MULTIPLIFACTION FACTOR
Actual Reading = Meter Reading x M.F.
M.F. = CT Primary / CT Secondary (5A)
Example: If the reading on the meter is 37.5 kWh. CT’s connected are of the rating 100/5A.
M.F = 100 / 5 = 20
Actual reading = 37.5 x 20 = 75 kWh
Ref: HPL / CT - 2M / 1007
N
L1
L2
L3
LT AC THREE PHASE, FOUR WIRE PANEL MOUNTED
STATIC KWH METER WITH COUNTER DISPLAY
TECHNICAL PARAMETER
ENCLOSURE
Compact
Weight
:
:
96mm x 96mm x 90 mm
300 gms.
:
:
:
COUNTER with 6 digits
8mm x 4.8mm
IP 54
:
:
:
:
-/5A
< 0.5VA
10ma (for 5A Secondary)
7A
:
:
120V AC to 300V AC Phase to Neutral
<1 W per phase
:
Self Powered, No Auxiliary Supply required
:
Class 1.0
:
:
:
100 msec minimum
1 Pulse = 1 kWh
interrogated with an external
DC Voltage of 5V to 24V
:
:
-100C to +550C
95%
FRONT PANEL
Display
Digit Height
Protection Index
INPUTS
A. CURRENT :
Insulated secondary
Current circuit burden
Starting current
Overload
B. VOLTAGE :
Measurement range
Voltage circuit burden
AUXILIARY SUPPLY
ACCURACY
Active Energy
PULSE OUTPUT
Pulse duration
Pulse weight
Potential free contact
(Open collector type)
OPERATING CONDITION
Operating temperature
Relative humidity
SPECIAL FEATURES
1. Records energy accurately under the following Tamper conditions :
a) One or Two phases are removed
OR
b) Neutral is Removed
OR
c) One Phase and neutral are removed
OR
d) Reverse current condition
2. Phase available indication LED’s
3. Finger touch-proof terminals for CT & Voltage connections.
Ref: HPL / CT - 2M / 1007