LT AC THREE PHASE, FOUR WIRE PANEL MOUNTED STATIC KWH METER WITH COUNTER DISPLAY INSTALLATION & OPERATION MANUAL FRONT VIEW 1. kWh Counter Display 2. Phase Indication LED’s 3. Calibration LED : 15000 imp/kWh for -/5A CUTOUT DETAILS WIRING DIAGRAM The Panel Meter is installed on the cabinet’s front panel and shall be secured firmly with cabinet using 4 transparent Clips. The meter shall be wired as per the following wiring Diagram : 2 Use 0.5 to 2.5mm Cable for Voltage 2 2 terminals & 3mm to 6mm cable for Current terminals. +0.8 92 -0.0mm 3Phase, 4Wire Electronic kWh Meter CT-2E k wh 18 +0.8 92 -0.0mm 90mm P1 S1 P3 S3 FUSE 0 .5A REAR VIEW L1 I1 L2 kWh L3 96mm N CAL P2 S2 G S I2 S1 S2 S1 S2 I3 S1 S2 1 PULSE = 1 kWh HPL-SOCOMEC 96mm Fig. 2 S, G = PULSE OUTPUT Fig. 3 MULTIPLIFACTION FACTOR Actual Reading = Meter Reading x M.F. M.F. = CT Primary / CT Secondary (5A) Example: If the reading on the meter is 37.5 kWh. CT’s connected are of the rating 100/5A. M.F = 100 / 5 = 20 Actual reading = 37.5 x 20 = 75 kWh Ref: HPL / CT - 2M / 1007 N L1 L2 L3 LT AC THREE PHASE, FOUR WIRE PANEL MOUNTED STATIC KWH METER WITH COUNTER DISPLAY TECHNICAL PARAMETER ENCLOSURE Compact Weight : : 96mm x 96mm x 90 mm 300 gms. : : : COUNTER with 6 digits 8mm x 4.8mm IP 54 : : : : -/5A < 0.5VA 10ma (for 5A Secondary) 7A : : 120V AC to 300V AC Phase to Neutral <1 W per phase : Self Powered, No Auxiliary Supply required : Class 1.0 : : : 100 msec minimum 1 Pulse = 1 kWh interrogated with an external DC Voltage of 5V to 24V : : -100C to +550C 95% FRONT PANEL Display Digit Height Protection Index INPUTS A. CURRENT : Insulated secondary Current circuit burden Starting current Overload B. VOLTAGE : Measurement range Voltage circuit burden AUXILIARY SUPPLY ACCURACY Active Energy PULSE OUTPUT Pulse duration Pulse weight Potential free contact (Open collector type) OPERATING CONDITION Operating temperature Relative humidity SPECIAL FEATURES 1. Records energy accurately under the following Tamper conditions : a) One or Two phases are removed OR b) Neutral is Removed OR c) One Phase and neutral are removed OR d) Reverse current condition 2. Phase available indication LED’s 3. Finger touch-proof terminals for CT & Voltage connections. Ref: HPL / CT - 2M / 1007
© Copyright 2024 ExpyDoc