Variable Refrigerant Flow Presented by: Benoit Chayer, ing. VRF Systems VRF : VARIABLE REFRIGERANT FLOW • Technology introduced in Asia 25 years ago • To minimize • The losses found in conventional HVAC systems • The footprint of the HVAC system • Asia, Europe and South America are mature markets • North American market is in full growth • You can think of this as a big ductless split with multiple indoor heads. • A VRF system can have up to 60 indoor units connected to a single outdoor unit VRF Market Share VAV system 4 Water source heat pump 5 VRF system • Outdoor unit connected to multiple indoor units with refrigerant piping • Outdoor unit installed on the roof or inside next to an outside wall (ducted air outlet) • Electronic expansion valves open and close in every indoor unit to match the capacity • Refrigerant flow is modulating depending on the load 6 VRF system VIDEO 7 Why refrigerant? • Efficient way of moving energy in a building • 10x more energy per pound than water • 175x more energy per pound than air VRF what makes it different • Variable speed fans for the outdoor units (INVERTER DC) • Variable speed fan for the indoor units (BLDC) • Electronic Expansion Valves (EEV) • Variable speed compressors (INVERTER DC) • Heat recovery between zones. Heat rejected from one zone can be used in another part of the building rather than being rejected to the outside. • Minimal losses from ducts since most or all of the ductwork is eliminated. • Eliminating ducts may also allow buildings to be designed with lower floor-to-floor heights, reducing construction costs. • Comes in 2 formats • Heat Pumps • Heat recovery Heat Pump 2 pipe system : heating OR cooling mode just like a standard HP • Indoor units connected to a Cooling Cooling Cooling Cooling ‘’main pipe’’ with a Y-branch • Every zones in the same mode • Each zone controls it’s own temperature set point Heat Recovery 3 pipe system : heating AND cooling at the same time • 3 pipes connected to a Cooling Heating Cooling Heating distribution box that controls the flow of suction gas and hot gas through the evaporator • Each zone has the control over the mode AND temperature set point • Energy transferred between zones / <*HR Unit> Energy source • Both heat recovery and heat pump systems can use air or water as energy source (geothermal or water source) • Modular design • 3-30 ton per system for air source • 6-48 ton per system for water source • Air source units can be installed on the roof or inside ducted to the outside. • Water source units are installed in mechanical rooms 12 Indoor units • Wall mounted • 1-Way cassette • 2-Way cassette • 4-Way cassette • Low static ducted • High static ducted • Floor standing • Ceiling suspended • Vertical air handler • Medium or high temp water heater • Things to consider when choosing an indoor unit • Air distribution • Noise • Ceiling space 13 • Budget Hydro Kit Uses the energy in the cooling season to heat the water Can be used for the radiant floor heating HR Unit Refrigerant Cooling/heating Air Source Hot water Hot water heating High temp heat Water Source Cold water cooling HR Unit 14 Hot water floor heating Heat/Cool Controls • Controls are ‘’built in’’ the system = no need to add sensors • Thermostat is connected with a quick connect to the indoor unit • Daisy chain between all the indoor units and the outdoor unit • Adding a central controller of your choice to the outdoor unit gives full access to the system • Integration to the building management system – BACnet – LonWorks • Touch Screen • Individual billing • Auxiliary heating module 15 Selection software • Pipe sizing for the installer • Capacity correction • Piping length limitation • Pdf report • AutoCAD schematics for engineers • Refrigerant amount calculation Service software • Temperature sensors reading • Refrigerant pressures • Compressor speed • Fan speed • Auto Diagnostic • Electronic expansion valves opening • Other valves open/close status • Voltage and amp draw Things to watch out for… • Choosing the right system for the right application • Heat Recovery • Heat Pump • Making sure the refrigerant amount is within the CSA-B52 code for occupant safety • Qualified contractors must be selected for quoting and installation • Unqualified contractors put huge margins of safety in their quotes which makes the project over budget • Unqualified contractors can make mistakes in the installation that are difficult to diagnose • Certified contractor to do the service • 30 minute job can turn into a week of troubleshooting for an unqualified technician • Sequence of controls must be clearly understood by everyone, everything is possible, but needs to be designed properly in the first place • Fresh air is a separate dedicated system • Work with a well established VRF brand to get proper technical support, training, spare parts and inventory Benefits for the building owner • Comfort at all time, load matching capacity (20-100%) • Lowest operating cost • AHRI-certified products • Selection software, easy to modify the design as the project scope changes • Long pipe length capability gives flexibility to the designer • LEED points • Integrated system • Indoor units • Outdoor units • Controls • ERV • Lowest maintenance cost • Clean air filters • Clean outdoor coil • No square footage needed for the HVAC system (Air source) • • • • Easy installation Easy troubleshooting with the service software Only 1 contractor to call if there is a problem with the system Best solution for retrofit projects Commercial application District Griffin • Cooling and heating in commercial and office spaces (first 6 floors) • • • 340 tons 110 ducted units from 1 to 8 tons Air source heat recovery systems for offices and stores • Air source heat pump systems for restaurants • BacNet gateway Bombardier office building • • • • • • Retrofit project on existing building LEED project 220 tons More than 100 ducted units from 1 to 4 tons Air source Heat Recovery Sync systems Removed all existing rooftops and ductwork to install VRF • • Enhance comfort and energy saving were the main reasons BACnet gateway Apartment building Aquasole • • • • • • • Luxury apartments with view on the StLawrence River 110 tons 75 ducted units from 1 to 4 tons 9 story building Air source heat recovery systems (SYNC) Electrical baseboards as back up heat source Touch screen central controller Geothermal 1160 chemin du Golf • • • • • • • Rental apartments 90 tons 104 ducted units from 1 to 3 tons Water cooled heat pumps Water loop designed at 32F in heating Gas fired boiler as back up heat for the water loop Touch screen central controller Hospitality Forestel Hotel • Addition of 46 rooms to existing hotel, phase 1 of 3 • 40 tons • 46 wall mounted units (1 ton) • Air source heat pumps • Electric baseboard as backup heat • BACnet Gateway School Laval College • • • • • • Cooling and heating of class rooms, phase 1 85 tons 35x 4-way cassette units (0.5 to 3 ton) Air source heat recovery system Hot water baseboard as backup heat BACnet Gateway 26 Thank you
© Copyright 2024 ExpyDoc