+View Presentation Material

Variable Refrigerant Flow
Presented by: Benoit Chayer, ing.
VRF Systems
VRF : VARIABLE REFRIGERANT FLOW
•  Technology introduced in Asia 25 years ago
•  To minimize
•  The losses found in conventional HVAC systems
•  The footprint of the HVAC system
•  Asia, Europe and South America are mature markets
•  North American market is in full growth
•  You can think of this as a big ductless split with multiple indoor heads.
•  A VRF system can have up to 60 indoor units connected to a single
outdoor unit
VRF Market Share
VAV system
4
Water source heat pump
5
VRF system
•  Outdoor unit connected to multiple indoor units with refrigerant piping
•  Outdoor unit installed on the roof or inside next to an outside wall (ducted air outlet)
•  Electronic expansion valves open and close in every indoor unit to match the capacity
•  Refrigerant flow is modulating depending on the load
6
VRF system
VIDEO
7
Why refrigerant?
•  Efficient way of moving energy in a building
•  10x more energy per pound than water
•  175x more energy per pound than air
VRF what makes it different
•  Variable speed fans for the outdoor units (INVERTER DC)
•  Variable speed fan for the indoor units (BLDC)
•  Electronic Expansion Valves (EEV)
•  Variable speed compressors (INVERTER DC)
•  Heat recovery between zones. Heat rejected from one zone can be used in another part
of the building rather than being rejected to the outside.
•  Minimal losses from ducts since most or all of the ductwork is eliminated.
•  Eliminating ducts may also allow buildings to be designed with lower floor-to-floor
heights, reducing construction costs.
•  Comes in 2 formats
•  Heat Pumps
•  Heat recovery
Heat Pump
2 pipe system : heating OR cooling mode just like a standard HP
•  Indoor units connected to a
Cooling
Cooling
Cooling
Cooling
‘’main pipe’’ with a Y-branch
•  Every zones in the
same mode
•  Each zone controls it’s own
temperature set point
Heat Recovery
3 pipe system : heating AND cooling at the same time
•  3 pipes connected to a
Cooling
Heating
Cooling
Heating
distribution box that controls
the flow of suction gas and hot
gas through the evaporator
•  Each zone has the control
over the mode AND
temperature set point
•  Energy transferred between
zones
/
<*HR Unit>
Energy source
•  Both heat recovery and heat pump systems
can use air or water as energy source
(geothermal or water source)
•  Modular design
•  3-30 ton per system for air source
•  6-48 ton per system for water source
•  Air source units can be installed on the roof or
inside ducted to the outside.
•  Water source units are installed in mechanical
rooms
12
Indoor units
•  Wall mounted
•  1-Way cassette
•  2-Way cassette
•  4-Way cassette
•  Low static ducted
•  High static ducted
•  Floor standing
•  Ceiling suspended
•  Vertical air handler
•  Medium or high temp water
heater
•  Things to consider when choosing an indoor unit
•  Air distribution
•  Noise
•  Ceiling space
13
•  Budget
Hydro Kit
Uses the energy in the cooling season to heat the water
Can be used for the radiant floor heating
HR Unit
Refrigerant
Cooling/heating
Air Source
Hot water
Hot water
heating
High temp heat
Water
Source
Cold water
cooling
HR Unit
14
Hot water floor
heating
Heat/Cool
Controls
• 
Controls are ‘’built in’’ the system = no need to add sensors
• 
Thermostat is connected with a quick connect to the indoor unit
• 
Daisy chain between all the indoor units and the outdoor unit
• 
Adding a central controller of your choice to the outdoor unit gives full access to the system
• 
Integration to the building management system
– 
BACnet
– 
LonWorks
• 
Touch Screen
• 
Individual billing
• 
Auxiliary heating module
15
Selection software
•  Pipe sizing for the
installer
•  Capacity correction
•  Piping length limitation
•  Pdf report
•  AutoCAD schematics
for engineers
•  Refrigerant amount
calculation
Service software
•  Temperature sensors
reading
•  Refrigerant pressures
•  Compressor speed
•  Fan speed
•  Auto Diagnostic
•  Electronic expansion
valves opening
•  Other valves open/close
status
•  Voltage and amp draw
Things to watch out for…
•  Choosing the right system for the right application
•  Heat Recovery
•  Heat Pump
•  Making sure the refrigerant amount is within the CSA-B52 code for occupant safety
•  Qualified contractors must be selected for quoting and installation
•  Unqualified contractors put huge margins of safety in their quotes which makes the project
over budget
•  Unqualified contractors can make mistakes in the installation that are difficult to diagnose
•  Certified contractor to do the service
•  30 minute job can turn into a week of troubleshooting for an unqualified technician
•  Sequence of controls must be clearly understood by everyone, everything is possible, but needs
to be designed properly in the first place
•  Fresh air is a separate dedicated system
•  Work with a well established VRF brand to get proper technical support, training, spare parts and
inventory
Benefits for the building owner
•  Comfort at all time, load matching capacity (20-100%)
•  Lowest operating cost
•  AHRI-certified products
•  Selection software, easy to modify the design as the project scope changes
•  Long pipe length capability gives flexibility to the designer
•  LEED points
•  Integrated system
•  Indoor units
•  Outdoor units
•  Controls
•  ERV
•  Lowest maintenance cost
•  Clean air filters
•  Clean outdoor coil
•  No square footage needed for the HVAC system (Air source)
• 
• 
• 
• 
Easy installation
Easy troubleshooting with the service software
Only 1 contractor to call if there is a problem with the system
Best solution for retrofit projects
Commercial application
District Griffin
• 
Cooling and heating in commercial and
office spaces (first 6 floors)
• 
• 
• 
340 tons
110 ducted units from 1 to 8 tons
Air source heat recovery systems for
offices and stores
• 
Air source heat pump systems for
restaurants
• 
BacNet gateway
Bombardier office building
• 
• 
• 
• 
• 
• 
Retrofit project on existing building
LEED project
220 tons
More than 100 ducted units from 1 to 4 tons
Air source Heat Recovery Sync systems
Removed all existing rooftops and ductwork to install VRF
• 
• 
Enhance comfort and energy saving were the main reasons
BACnet gateway
Apartment building
Aquasole
• 
• 
• 
• 
• 
• 
• 
Luxury apartments with view on the StLawrence River
110 tons
75 ducted units from 1 to 4 tons
9 story building
Air source heat recovery systems
(SYNC)
Electrical baseboards as back up heat
source
Touch screen central controller
Geothermal
1160 chemin du Golf
• 
• 
• 
• 
• 
• 
• 
Rental apartments
90 tons
104 ducted units from 1 to 3 tons
Water cooled heat pumps
Water loop designed at 32F in
heating
Gas fired boiler as back up heat for
the water loop
Touch screen central controller
Hospitality
Forestel Hotel
•  Addition of 46 rooms to existing
hotel, phase 1 of 3
•  40 tons
•  46 wall mounted units (1 ton)
•  Air source heat pumps
•  Electric baseboard as backup heat
•  BACnet Gateway
School
Laval College
• 
• 
• 
• 
• 
• 
Cooling and heating of class rooms, phase 1
85 tons
35x 4-way cassette units (0.5 to 3 ton)
Air source heat recovery system
Hot water baseboard as backup heat
BACnet Gateway
26
Thank you