YES Mini VRF Series - YORK® Variable Refrigerant Flow (VRF)

YES Mini VRF Series
RESIDENTIAL DC INVERTER VRF AIR-CONDITIONERS YOU CAN TRUST
Table of Contents
Serving your needs since 1874
1
Product Benefits
3
Product Features
4
Product Functions
6
Product Technologies
9
Smart Control
10
Indoor Units
14
Product Portfolio
20
Product Nomenclature
21
Product Specifications
23
Serving Your Needs Since 1874.
A century of innovation
Established in 1874 in York, Pennsylvania, YORK® has
Significant Milestones
helped our customers meet their temperature control
1935
needs for over a century.
First to develop a successful single-room air
conditioner
Now a Johnson Controls brand, YORK® continues to
benefit customers through research that has gone on to
claim several significant firsts in design and innovation.
Johnson Controls is able to provide our customers with
the best temperature control solutions available around
the world today.
Pioneer in Inverter technology
Our customers can be assured that they will enjoy the
benefits of the latest technology when they choose a
Johnson Controls product, as YORK® has always been
at the forefront of adopting new technologies for their
offerings.
From being the first to offer a low pressure VSD unit in
1954
First to offer year-round air-conditioning
1979
Launched the first Low Pressure VSD Driven
Centrifugal Chiller
2004
Launched the first VSD Driven Air Cooled
Screw Chiller
2005
Applied VSD in YORK® Industrial Refrigeration
Screw Chiller
2011
century, YORK® has demonstrated its pioneering spirit.
Launched the YES Mini Residential Inverter
VRF, Magnetic VSD Centrifugal Chiller, VSD
Driven Water Cooled Screw Chiller
Leader in reliability
2012
When constructing products, YORK® places our
Launched the YES Slim Residential/
Commercial Inverter VRF, YES Super
Commercial Inverter VRF
1979 to introducing the inverter technology in the 21st
customers’ needs as the top priority of our design
process.
Our inverter VRF units are produced using state-ofthe-art lean manufacturing techniques, and rigorous
quality testing is implemented at every step of the
manufacturing process, before they are shipped to
customers.
YES Mini VRF Series | 1
Endorsed by Iconic Buildings.
YORK®’s HVAC systems have been installed in many of the world’s most famous landmarks. YORK® makes
systems for structures of all sizes that bring innovation, comfort and design wherever people live, work and play.
2 | YES Mini VRF Series
Product Benefits
YORK® Variable Refrigerant Flow (VRF)
At Johnson Controls, we always seek to anticipate what customers are looking for and strive to provide the
temperature control systems that will meet their myriad of needs.
YORK® VRF air-conditioners offer customers a range of benefits that is unparalleled in the air-conditioner
market.
Energy Efficient
Customers looking to save money will be delighted to know our air-conditioners can help
reduce costs as the highly energy-efficient VRF units will help you decrease the power
you use.
Wide Ambient Range
Customers can take comfort in knowing that our inverter VRF air-conditioners can
operate in extreme weather conditions, running safely even when ambient temperature is
up to 520C for cooling or -200C for heating.
48 to 520C cooling or -15 to -200C heating will be running at intervals.
Smart Control
Customers can take more effective control of their air-conditioners with a variety of
technology tools available for our units. Our advanced suite of control solutions include:
three types of touch screen controllers, smart home connection and building automation
systems using the Metasys® software.
Versatility
We understand that no two customers are the same. That’s why we’ve designed our
air-conditioning systems to be versatile enough to meet our customers’ differing needs.
From product selection to installation to commissioning, YORK® YES Series offers
impressive flexibility.
Greater Comfort
We know that enjoying comfort at the right temperature is one of our customers’
foremost desires. We have the technology to deliver that comfort, including a BLDC
(Brushless Direct Current) fan motor with adjustable speeds, anti-vibration and soundinsulation technology.
YES Mini VRF Series | 3
Product Features
oling
m
5m
70
Part ceiling
Narrow
install
Heating
Mini Outdoor Fin
General Louvered Fin
Environmental Protection
Our highly energy efficient Inverter VRF units provide environmental protection by
Night Mode
using the eco-friendly
Cooling R410A refrigerant.
Night Mode
Heating
Outdoor to be set at night mode
Lower fan speed during overnight
operation
JCI YES-Mini Outdoor Fin
General Louvered Fin
Wide Ambient Range
Indoor EXV
52C
-20C
gn for models 35/40/50/60
Low-pressure Sensor
Capacity-Priority Mode
Capacity-Priority Mode
High-pressure Sensor
With wide ambient temperatures ranging from 52 C in cooling mode to -20oC in
o
Outdoor to be set at capacitypriority mode
Load needs priority
heating mode, the air-conditioning units can be used in various environments.
Time
Heating Capacities
Inlet/outlet
Temperature
of the Heat
Exchanger
Durations
Outdoor
Temperature
1.8kW~5
0~30Pa
General Air
Conditioner
YES-mini
15~80Pa
6.6kW~11.5kW
15~100Pa
14kW~17.5kW
3-row Heat
Exchanger
1. Diagnostic Kit
2. Outdoor Control
Board
Ind
Heating
Cooling
3. Computer Software
Three-row design for models 35/40/50/60
Communication cables
Power cables
Heating
JCI YES-Mini
Cooling
Outdoor Fin
General Louvered Fin
Touch Screen Wired Control
JCI YES-Mini Outdoor Fin
General Louvered Fin
Take control of your system with our smart touch screen wired controllers, which is
Inl
Tem
available in different colours to suit your own personal taste. It also features a built-in
of
Nig
Ex
signal receiver.
Nig
Ou
Ceiling
Three-row Heat-Exchanger
1. Diagnostic Kit
Ca
Indoor EXV
Low-pressure Sensor
High-pressure Sensor
Our units are built with a three-row heat-exchanger,
improving unit
performance even
Three-row design for models 35/40/50/60
Three-row design for
models 35/40/50/60
Ou
pri
Loa
2. Outdoor Control
Board
Time
Heating Capacities
Three-row design for models 35/40/50/60
Field Wiring Design
Inlet/outlet
Temperature
of the Heat
Exchanger
The field wiring design on our outdoor units provides convenience in wiring connection
3. Computer
Software
Durations
General Air
Conditioner
through the availability of a detachable handle on its side. This also prevents
noise
YES-mini
problems and damage
to the exteriror.
1. Diagnostic Kit
Outdoor
Temperature
cables
3. Computer Software
1. Diagnostic Kit
Communication cables
Power cables
4 | YES Mini VRF Series
Ca
under extreme temperatures.
2. Outdoor Control
Communication
Board
Power cables
Low
op
2. Outdoor Control
Board
3-row Heat
Exchanger
Rare-earth Permanent Magnet DC Inverter Compressors
The rare-earth permanent magnet DC inverter compressors in our units are capable
of forming powerful and permanent magnetic fields, which enables the compressor to
operate at high efficiency when switched on.
The rotors in these compressors are fixed with slip-rings to seal the cylinder, thereby
reducing abrasion and extending the lifespan of the compressor.
Noise Reduction Technology
The noise reduction technology, made possible by DC scroll inverter compressors,
BLDC fan motor with adjustable speeds, anti-vibration and sound-insulation technology,
ensures that the air-conditioners operate quietly by cutting down the operational noise
levels.
YES Mini VRF Series | 5
Product Functions
Intelligent Piping Length Adaptation
This system consists of a high-pressure sensor, low-pressure sensor and real-time
temperature monitor, measuring compressor discharge and suction temperatures, indoor
Heating
evaporator temperatures, as well as tube temperatures in the heat exchanger. This allows
operating pressure and compressor operating frequency to be automatically adjusted
under different piping length conditions.
uvered Fin
Indoor EXV
Low-pressure Sensor
High-pressure Sensor
Two Quiet Operation Modes
Part ceiling
Part ceiling
The availability of “Night Mode” and “Capacity-Priority Mode” allows for quiet operation
Heating Capacities
throughout the day. The “Night Mode” prompts the fan to be running at lower speed
during overnight operations, while the “Capacity-Priority Mode” takes into consideration
Inlet/outlet
surrounding air Temperature
fluctuations
to adjust fan speed.
of the Heat
Exchanger
Durations
Outdoor
Temperature
2. Outdoor Control
Board
Indoor EXV
Low-pressure Sensor
High-pressure Sensor
Indoor EXV
Low-pressure Sensor
High-pressure Sensor
Night Mode
Outdoor to be set at night mode
3-row Heat
Exchanger
Capacity-Priority Mode
Capacity-Priority
Mode
Capacity-Priority Mode
Capacity-Priority Mode
Outdoor to be set at capacitypriority mode
Outdoor to be set at capacitypriority mode
Load needs priority
Load needs priority
3. Computer Software
Durations
Durations
Time
Heating
Heating
Capacities
Capacities
6 | YES Mini VRF Series
Outdoor
General Air
Conditioner
YES-mini
Outdoor to be set at night mode
Lower fan speed during overnight
operation
Lower fan speed during overnight
operation
1. Diagnostic Kit
Inlet/outlet
Temperature
Inlet/outlet
of
the Heat
Temperature
Exchanger
of the Heat
Exchanger
Night Mode
Night
Mode
Night Mode
General Air
Conditioner
General Air
YES-mini
Conditioner
Time
15~80Pa
15~80Pa
15~100Pa
15~100Pa
3-row Heat
0
0
6
6
1
1
JCI YES-Mini Outdoor Fin
General Louvered Fin
Cooling
Heating
Three External Static Pressure (ESP) Settings
JCI YES-Mini
General
Louvered
Fin
A 3-4HP
outdoorOutdoor
unit withFina single fan can reach
external
static pressures
as high as 30
Pa, while a 4.5-6HP outdoor unit with two fans can reach 40 Pa. Installing an air duct to
redirect airflow is feasible with the ESP setting.
Indoo
Three-row design for models 35/40/50/60
Inlet/o
Tempe
of the
Excha
Three-row design for models 35/40/50/60
1. Diagnostic Kit
Three Approaches for Address Setting
The system offers three system setting approaches for ease of testing and installation of
2. Outdoor Control
Board
units:
• Auto address setting with diagnostic kit
• Auto address setting with outdoor unit
3. Computer Software
• Auto address setting on computer
1. Diagnostic Kit
Communication cables
Power cables
2. Outdoor Control
Board
3. Computer Software
Communication cables
Maximum Safety Power cables
Our units guarantee safety by having in place:
m
5m
70
Part ceiling
1. High pressure/low pressure protections
Narrow corridor
installation
1.8kW~7.1kW
8.0kW
2. Compressor internal overload protection
Fin
9.0kW~11.2kW
2.8kW
4.5kW
5.6kW/7.1
3. Time delay for compressor restart, among other protection systems
Night Mode
Night Mode
Outdoor to be set at night mode
Lower fan speed during overnight
operation
Top air outlet
Sid
Cooling: good
He
good
Coo
He
B
A
York air outlet
YES Mini VRF Series | 7
Capacity-Priority Mode
Indoor EXV
Low-pressure Sensor
High-pressure Sensor
Capacity-Priority Mode
Outdoor to be set at capacitypriority mode
Load needs priority
Cooling: good
He
weak
ating
Automatic Fault Alarm
vered Fin
The wired controllers of the indoor and seven-segment LED of outdoor units
automatically display information of any system failure, which makes trouble-shooting Night Mode
Night Mode
problems easier.
Outdoor to be set at nig
Lower fan speed during
operation
Intelligent Defrost
By monitoring outdoor temperatures, inlet/outlet temperatures of the heat exchanger,
as well as the duration for intelligent defrost, the system can efficiently conduct defrost
cycles.
Heating
Indoor EXV
Low-pressure Sensor
This also eliminates the problem of dust affecting the heat exchange capacity and
possibly triggering an auto-defrost, which thus enables uninterrupted heating.
Inlet/outlet
Temperature
of the Heat
Exchanger
Durations
Outdoor
Temperature
Outdoor to be set at ca
priority mode
Load needs priority
Time
Heating Capacities
ouvered Fin
Capacity-Priority
Capacity-Priority Mode
High-pressure Sensor
Night Mode
Night Mode
Outdoor to be set a
Lower fan speed du
operation
General Air
Conditioner
YES-mini
3-row Heat
Exchanger
Capacity-Prior
1. Diagnostic Kit
Indoor EXV
Low-pressure Sensor
Capacity-Priority M
High-pressure Sensor
Outdoor to be set a
priority mode
2. Outdoor Control
Board
Load needs priority
Refrigerant Recovery
If the indoor or outdoor unit fail in the system, the refrigerant may be recovered to
Time
Heating Capacities
3. Computer Software
reduceInlet/outlet
its wastage.
Temperature
of the Heat
Exchanger
Outdoor Control Board with Seven-Segment
LED Display
General Air
Durations
Conditioner
YES-mini
Our outdoor units feature
three, seven-segment LED displays
on their control3-row
boards
to show the
Outdoor
Heat
Temperature
1. Diagnostic Kit
2. Outdoor Control
Board
3. Computer Software
8 | YES Mini VRF Series
Exchanger
system’s relevant information to make it more efficient to make diagnosis during servicing.
Product Technologies
180° DC Inverter Driver
We adopted the 180° inverter driver control to reduce motor vibration and noise while
enhancing the compressor operating frequency range.
Special fresh air intake design for drivers (models 45-60)
Our variable speed drivers have incorporated a special fresh air intake design to reduce
the temperature of the driver. This enables the variable speed driver to operate at higher
speeds and at higher ambient temperatures.
Without Fresh Air Intake
With Fresh Air Intake
Sub-Cooling Design
A sub-cooling coil is integrated in the outdoor heat exchanger to enable sub-cooling
and reduce the capacity loss in the event of using long piping (length of piping varies
Without Freshto
Air Intake
With Fresh Air Intakesize, shape and number of indoor units).
according
the apartment
Electronic expansion valve and check valve throttling
On top of having an outdoor electronic expansion valve for heating purposes, our YES
Mini system also comes with a check valve parallel to the electronic valve, so that the
refrigerant may enter through it at cooling mode, thereby improving the life of the valve.
Without Fresh Air Intake
Pressure and temperature sensors
With Fresh Air Intake
The outdoor units come equipped with high and low pressure sensors, as well as
discharge, suction, heat exchanger and ambient temperature sensors. When used in
combination, they provide a stable and effective system operation.
New low resistance fan grille
Our specially designed leaf shape fan grille reduces air resistance, adjusts the air
discharge direction and avoids short circuit of return and discharge air. This improves the
noise data, noise quality and the unit efficiency.
YES Mini VRF Series | 9
Smart Control
Individual & Group control
The indoor units in our YES Series can be controlled using wired and wireless controllers.
Moreover, the wired controllers include a group control function and can connect up to
four indoor units.
Wired
Controller
Wireless
Controller
Group
Control
Group
Control
Individual
Control
The touch screen wired controllers come in a range of colours to suit your personal
taste, and is equipped with TiO₂ control and wireless controller receivers.
Gray
10 | YES Mini VRF Series
Sky blue
Green
Brown
On/Off Controller
Our touch screen controllers can connect up to 256 indoor units or four VRF systems,
and can switch those within the same zone on or off simultaneously .
** YDHW/YDCC can't connect to on/off controller.
ON/OFF controller which can support Modbus or BACnet
protocol for different application (need to choose the corresponding type of the controller).
Central on/off control
at the entrance/exit
Central Controller
Our seven-inch touch screen central controller can be mounted on the wall easily and
connects up to 1,024 indoor units/ 512 groups/ 128 zones/ 16 VRF systems. In addition to
having the same control functions as the wired controller, it also has a weekly schedule
function.
** YDHW/YDCC can’t connect to central controller.
Central controller can
support Modbus or BACnet
protocol for different application (need to select
the protocol mode).
YES Mini VRF Series | 11
Door Card Function
The control boards in the YES indoor units come with a door card on/off signal function
and feature two selection modes, which may be chosen using the door card and signal
interface communication.
Mode 1:The system automatically returns to the last operation mode when the card is
inserted.
Door Card
Door Card
Insert the
door card
Pull out the
door card
Mode 2:The system needs to be switched on manually when the card is inserted, so as
to reduce electricity wastage.
Door Card
Door Card
Door Card
Pull out
the door
card
12 | YES Mini VRF Series
Insert the
door card
BAS Connection
Our YES Series can be connected to the Building Automation System to allow an
integrated smart control solution.
** YDHW/YDCC can’t connect to BAS connection.
Metasys/Other
BAS System
NAE Converter (JCI)
BACnet
communication
board
BACnet
BACnet/IP
YES Mini VRF Series | 13
Indoor Units
Compact Ducted Indoor Unit
Compact design
45
m
m
00
0m
m
With a height of just 200mm and depth of 450mm, its
7
Part ceiling
Narrow corridor
installation
compact size makes installation ideal for narrow spaces
such as corridor of bedrooms or hotel rooms.
Flexible air return
The detachable air return baffle enables the direction
of air return to be adjusted either downwards or
backwards.
ESP adjustable
The adjustable external static pressure of the ceilingpackaged indoor unit supports different installations and
generates optimal airflow.
0~30Pa
1.8kW~7.1kW
Sleep mode
Sleep mode may be selected via a wired controller.
Optional drainage pump
0~30Pa
2.0kW~5.3kW
15~80Pa
Ceiling
6.6kW~11.5kW
15~100Pa
14kW~17.5kW
The ceiling-packaged indoor unit fits in the narrowest
of spaces where the drainage pump is not required.
However, a drainage pump is available in case there is
(Unit: mm)
enough room in the ceiling and the drainage distance is
long.
14 | YES Mini VRF Series
Ceiling-concealed (Low Static
Ducted) Indoor Unit
Compact design
m
0m
70
With a height of just 200mm and width of 700mm
Part ceiling
Narrow corridor
installation
(018–045), its compact size makes installation ideal for
narrow spaces such as corridor of bedrooms or hotel
rooms.
Flexible air return
The air return baffle is detachable. The direction of
air return can be adjusted during installation, either
downward or backward.
ESP adjustable
The external static pressure of the ceiling-packaged
indoor unit is adjustable, supporting different
installations and delivering optimal airflow.
1.8kW~7.1kW
8.0kW
9.0kW~11.2kW
Sleep mode
Sleep mode can be selected via a wired controller.
Optional drainage pump
The ceiling-packaged indoor unit fits in the narrowest
Ceiling
of spaces where the drainage pump is not required.
(Unit: mm)
However, if there is enough room in the ceiling and the
drainage distance is long, a drainage pump is available.
YES Mini VRF Series | 15
0~30Pa
1.8kW~5.3kW
15~80Pa
6.6kW~11.5kW
15~100Pa
14kW~17.5kW
Ceiling-concealed (Medium Static
Ducted) Indoor Unit
ESP Adjustable
The external static pressure of our ceiling-concealed
indoor units is adjustable, which supports different
ling packaged indoor
installations and provides optimal airflow.
s up the pace at
the air-conditioner.
0~30Pa
2.0kW~5.3kW
15~80Pa
6.6kW~11.5kW
15~100Pa
14kW~17.5kW
Sleep mode
ndoor unit is ideal for
Sleep mode may be selected via a wired controller.
drooms. Sleep mode can
2-Way Cassette Indoor Unit
a- slim and fits in the
Ceiling
ump is not required.
eiling and the drainage
(Unit: mm)520mm
al for selection.
Complete product line
Seven models ranging from 2.8 kW to 11.2 kW are
available for selection.
310mm
840~1440mm
Compact design
A standard, compact design of 520 mm depth and
310 mm height is adopted across all models, making
installations easier.
Max=500mm
Standard drainage pump
The unit has a standard drainage pump capable of
draining up to 500 mm of water, and is ideal for draining
condensation over longer distances.
Standard
16 | YES Mini VRF Series
Round-way Cassette Indoor Unit
Fresh air Intake
360 degree circulation
Room temperature, airflow and noise control are
regulated and maintained throughout the room.
Blind angles of air distribution
Minified blind angles
Oblique view
Oblique view
360° good air distribution
Elevation view
Elevation view
Different height setting
Wired controllers can be set to normal ceiling mode or
high ceiling mode, providing comfort.
Fresh air intake
Oblique view
Elevation view
Fresh air can be introduced directly.
Fresh air Intake
Fresh air Intake
Brushless Direct Current (BLDC) fan motor
With a spiral multi-blade fan and a large-diameter
design, the fan noise can be effectively reduced and air
volume can be more precisely controlled.
tribution
Fresh air Intake
High efficiency drainage pump
The maximum distance between the cassette unit and
drainage pump is as high as 750 mm.
YES Mini VRF Series | 17
High Wall Indoor Unit
Complete product line
Five compact and attractive models from 2.2 kW to 7.1
kW are available for selection, which are suitable for
residential to light commercial applications.
Whole Package Design
The Electronic Expansion Valve (EEV) fitted inside
the unit chamber eliminates the need for external
installations.
Low noise
High efficiency/ low noise motors and fan impellers are
adopted to enable quiet operations down to 28dB(A).
There is also a standard filter fitted for healthier use.
Floor/ Ceiling Indoor Unit
Complete product line
Eight models from 2.8 kW to 11.2 kW are available.
Floor and ceiling installations are convertible for job
sites.
680mm
240mm
1245~1670mm
Compact design
A standard, compact design of 240 mm depth and
680 mm height is adopted across all models, making
installations easier.
Optional drainage pump
Max=500mm
The indoor ceiling unit has an optional drainage pump
capable of draining up to 500 mm of water, and is ideal
for draining condensation over longer distances.
Option
18 | YES Mini VRF Series
Floor-concealed Indoor unit
Complete product line
Top air outlet
Side air outlet
York air outlet
Four models from 2.8 kW to 7.1 kW are available.
B
A
Better air distribution
Our air outlets are tilted at a 45-degree angle which
helps optimize air distribution for cooling and heating.
Compact design
A standard, compact design of 230 mm depth and 600
mm height is adopted across all models, and is suitable
600mm
230mm
for floor-concealed installations in cabinets.
730~1334mm
YES Mini VRF Series | 19
Product Portfolio
Indoor
Cooling Capacities kW
Types
1.8
2.2
2.5
2.8
3.2
3.6
4
4.5
5
5.6
Compact Ducted
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Low Static Duct (YDCP)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Medium Static Ducted (YDCC)*
Y
Y
Y
Y
High Wall (YDHW)
Y
Y
Y
Y
Floor/Ceiling (YDEC)
Y
Y
Floor-Concealed (YDVC)
Y
2-Way Cassette (YDDK)
Y
Y
Round Way Cassette (YDCK)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
12.5
14
17.5
Y
Y
Cooling Capacities kW
Types
6.3
7.1
Compact Ducted
Y
Y
Low Static Duct (YDCP)
Y
Y
Medium Static Ducted (YDCC)*
Y
Y
Floor/Ceiling (YDEC)
Y
Floor-Concealed (YDVC)
Y
2-Way Cassette (YDDK)
Y
Y
9
10
11.2
Y
Y
Y
Y
Y
Y
Y
High Wall (YDHW)
Round Way Cassette (YDCK)
8
Y
Y
Y
Y
Y
Y
Y
Y
Y
*approximate data
Capacity
3HP
3.5HP
4HP
4HP
5HP
6HP
Cooling Capacities
8 kW
10 kW
11.2 kW
12 kW
14 kW
16 kW
Heating Capacities
9.5 kW
11.2 kW
12.5 kW
12.5 kW
16 kW
18 kW
Models
YVOH30
YVOH35
YVOH40
YVOH45
YVOH50
YVOH60
20 | YES Mini VRF Series
Y
Y
Y
Product Nomenclature
Outdoor
0 A 1
100
Certification, Default: No Special Certificate
Condition
Conditions, Default: Local
T1, 1:1:Export
Export T1
Design Series No.
Design Series Number
Design Code
Design Code
Power Supply M:380-415V/3-50Hz E:380V/3-50Hz
Structure, H: HorizontalRefrigerant
Discharge
E:R410A
Power Supply, A: 220V/1PH-50Hz, K: 220-240V/1PH-50Hz
Outdoor Unit Type
S:Single Unit V:Modular Unit
Cooling Capacity Code
Structure H:Horizoatal Discharge V:Top Discharge
Mode of Operation, H: Heat Pump
Cooling Capacity Code
H:Heat
Pump
Outdoor
Unit
O:Outdoor Unit
V: Variable Refrigerant Flow (VRF) Air Conditioner
V:DC Inverter
Y:
YORK
Y:YORK
E Series Indoor
0 E 3
Condition, 1: Export T1; 3: Export T3
Design Series Number: E Series(R410A)
Design Code
Power Supply, A: 220V/1PH-50Hz
Expansion Device,
N: Internal EXV No Drainage Pump, P: Interal EXV With Drainage Pump
Auxiliary Electric Heater
0: No Heater, 2: With 2# Heater, 4: With 4# Heater
Mode of Operation, C: Cooling Only, H: Heat Pump
Cooling Capacity Code in 100W
Indoor Unit Type,
CD: Compact Ducted, CP: Ceiling Packaged Ducted (Low Static), CK: Round-way Ceiling Cassette,
DK: 2-way Ceiling Cassette, EC: Floor/Ceiling, VC: Floor Conceal , HW: High Wall
D:Variable Refrigerant Flow(VRF) Air Conditioner
Y:YORK
H
F L E
2 C 3
Condition, 3: Export T3
Design Series Number: C Series(R410A)
YES Mini VRF Series | 21
Design Code
Power Supply, A: 220V/1PH-50Hz
Cooling Capacity Code in 100W
Indoor Unit Type,
CD: Compact Ducted, CP: Ceiling Packaged Ducted (Low Static), CK: Round-way Ceiling Cassette,
DK: 2-way Ceiling Cassette, EC: Floor/Ceiling, VC: Floor Conceal , HW: High Wall
D:Variable Refrigerant Flow(VRF) Air Conditioner
Y:YORK
C Series Indoor Units
H
F L E
2 C 3
Condition, 3: Export T3
Design Series Number: C Series(R410A)
Design Code
Power Supply, A: 220V/1PH-50Hz
Expansion Device,
E: Internal
Piping, L:Left, R: Rightl
Return Plenum,
F: With Back Return Plenum and Filter
Auxiliary Electric Heater
0: No Heater, 2: With 2# Heater, 4: With 4# Heater
Mode of Operation, C: Cooling Only, H: Heat Pump
Cooling Capacity Code in 100W
Indoor Unit Type,
CC: Medium Static Ducted
D: Variable Refrigerant Flow(VRF) Air Conditioner
Y:YORK
Condition 1:Default: Local T1, 1: Export T1, 3: Export T3
Design Series No.
Design Code
Structure H:Horizontal Discharge V:Top Discharge
Power Supply, A: 220V/1PH-50Hz, K: 220-240V/1PH-50/60Hz
Cooling Capacity Code
Mode of Operation, C: Cooling Only, H: Heat Pump
O:Outdoor Unit
V:Variable Refrigerant Flow(VRF) Air Conditioner
Y:YORK
22 | YES Mini VRF Series
Product Specifications
YES Mini Outdoor
Outdoor Unit Model
YVOH30KH
YVOH35KH
YVOH40KH
YVOH45AH
YVOH50AH
YVOH60AH
HP
3.0
3.5
4.0
4.5
5.0
6.0
Power Supply (V/Ph/Hz)
220/1/50
Cooling
8.0
10.0
11.2
12.0
14.0
16.0
Heating
9.5
11.2
12.5
12.5
16.0
18.0
Cooling
2.13
3.00
3.41
3.00
3.88
4.72
Heating
2.31
3.12
3.47
3.12
3.78
4.50
Cooling EER
3.76
3.33
3.28
4.00
3.61
3.39
Heating COP
4.11
3.59
3.60
4.01
4.23
4.00
IPLV (C)
5.25
5.20
5.35
5.35
5.60
5.30
Air Flow (m3/h)
Standard
4100
4100
4700
6500
6500
6500
Dimensions
(mm)
H×W×D
Weight (kg)
Net Weight
90
93
95
110
115
125
Type
R410A
R410A
R410A
R410A
R410A
R410A
Charge (kg)
2.7
3.0
3.5
3.7
4.5
5.1
Cooling/Heating
48/50
49/51
51/51
51/53
52/55
52/55
Capacity (kW)
Power (kW)
Efficiency
(W/W)
882 x 995 x 360
1320 x 995 x 360
Refrigerant
Noise (dB(A))
Liquid
9.52
Gas
15.88
Piping (ømm)
Max.
16.6
20.0
20.0
20.0
30.0
30.0
Circuit Breaker
25
25
25
25
40
40
Nominal Cooling
9.8
13.8
15.7
14.5
17.8
21.7
Nominal Heating
10.6
14.3
15.9
15.1
17.4
20.7
Max. Piping Length
70
70
70
120
120
120
Max. Equivalent Piping Length
100
100
100
150
150
150
20
20
20
10
11
Current (A)
Piping
Length/Height
(m)
Ambient
Range
Max. Height Difference between IU/OU (OU above IU)
Max. Height Difference between IU/OU (IU above OU)
30
15
15
15
Max. Height Difference (IUs)
15
Cooling (°CDB)
-5–52 (Interval Running at 48 to 52°C)
Heating (°CWB)
-20–24 (Interval Running at -20 to -15°C)
Max. Indoor Unit No.
5
7
8
8
YES Mini VRF Series | 23
Compact Ducted Indoor Unit
Indoor Unit Model
YDCD
018
H0NA
YDCD
022
H0NA
YDCD
025
H0NA
YDCD
028
H0NA
YDCD
032
H0NA
YDCD
036
H0NA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
1.8
2.2
2.5
2.8
3.2
3.6
Heating
2.2
2.5
2.8
3.2
3.6
4.0
37
37
46
46
48
50
Capacity (kW)
Power Input (W)
Current (A)
Nominal
0.16
0.16
0.2
0.2
0.21
0.22
Air Flow (m3/h)
-
350
350
450
450
480
480
ESP (Pa)
Standard
(min-max)
0(0-30)
0(0-30)
0(0-30)
0(0-30)
0(0-30)
0(0-30)
Dimensions (mm)
H×W×D
200X700
X450
200X700
X450
200X700
X450
200X700
X450
200X700
X450
200X700
X450
Weight (kg)
Net Weight
23
23
23
23
23
25
Noise (dB(A))
H/M/L
29/25/23
29/25/23
31/27/25
31/27/25
32/29/27
32/29/27
Liquid/Gas
6.35/9.52
6.35/9.52
6.35/9.52
6.35/9.52
6.35/12.70
6.35/12.70
Drainage
DN25
DN25
DN25
DN25
DN25
DN25
Indoor Unit Model
YDCD
040
H0NA
YDCD
045
H0NA
YDCD
050
H0NA
YDCD
056
H0NA
YDCD
063
H0NA
YDCD
071
H0NA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
4.0
4.5
5.0
5.6
6.3
7.1
Heating
4.5
5.0
5.6
6.3
7.1
8.0
70
70
76
106
106
110
Piping (ømm)
Capacity (kW)
Power Input (W)
Current (A)
Nominal
0.3
0.3
0.33
0.46
0.48
0.48
Air Flow (m3/h)
-
560
560
750
900
900
990
0(0-30)
0(0-30)
0(0-30)
0(0-30)
0(0-30)
0(0-30)
ESP (Pa)
Standard
(min-max)
Dimensions (mm)
H×W×D
200X700
X450
200X900
X450
200X900
X450
200X900
X450
200×1100
×450
200×1100
×450
Weight (kg)
Net Weight
25
30
34
34
34
34
Noise (dB(A))
H/M/L
38/35/32
35/32/29
35/32/29
39/36/32
37/34/31
37/35/32
Liquid/Gas
6.35/12.70
6.35/12.70
6.35/12.70
6.35/12.70
9.52/15.88
9.52/15.88
Drainage
DN25
DN25
DN25
DN25
DN25
DN25
Piping (ømm)
24 | YES Mini VRF Series
Ceiling Packaged (Duct) Indoor
Indoor Unit Model
YDCP
018H0NA
YDCP
022H0NA
YDCP
025H0NA
YDCP
028H0NA
YDCP
032H0NA
YDCP
036H0NA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
1.8
2.2
2.5
2.8
3.2
3.6
Heating
2.2
2.5
2.8
3.2
3.6
4.0
Capacity (kW)
Power Input (W)
-
37
37
46
46
48
50
Current (A)
Nominal
0.16
0.16
0.20
0.20
0.21
0.22
Air Flow (m3/h)
-
350
350
450
450
480
480
ESP (Pa)
Standard (min–max)
0 (0–30)
Dimensions (mm)
H×W×D
Weight (kg)
Net Weight
200 × 700 × 620
Noise (dB(A))
H/M/L
27/25/23
27/25/23
28/26/24
Piping (ømm)
Liquid/Gas
6.35/9.52
6.35/9.52
6.35/9.52
23
25
Drainage Piping (mm)
28/26/24
30/27/25
30/27/25
6.35/9.52
6.35/12.7
6.35/12.7
DN25
Indoor Unit Model
YDCP
040H0NA
YDCP
045H0NA
YDCP
050H0NA
YDCP
056H0NA
YDCP
063H0NA
YDCP
071H0NA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
4.0
4.5
5.0
5.6
6.3
7.1
Capacity (kW)
Heating
4.5
5.0
5.6
6.3
7.1
8.0
Power Input (W)
-
70
70
76
106
106
110
Current (A)
Nominal
0.30
0.30
0.33
0.46
0.48
0.48
Air Flow (m3/h)
-
560
560
750
900
900
990
ESP (Pa)
Standard
0 (0–30)
(min–max)
Dimensions (mm)
H×W×D
Weight (kg)
Net Weight
200 × 700 × 620
25
200 × 900 × 620
25
200 × 1100 × 620
30
34
Noise (dB(A))
H/M/L
35/32/29
35/32/29
33/31/28
37/34/30
Piping (ømm)
Liquid/Gas
6.35/12.7
6.35/12.7
6.35/12.7
6.35/12.7
Drainage Piping (mm)
35/33/29
9.52/15.88
36/33/30
9.52/15.88
DN25
Indoor Unit Model
YDCP080H0NA
YDCP090H0NA
YDCP100H0NA
YDCP112H0NA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
Capacity (kW)
Cooling
8.0
9.0
10.0
11.2
Heating
9.0
10.0
11.2
12.5
Power Input (W)
-
138
206
260
260
Current (A)
Nominal
0.60
0.90
1.25
1.25
-
1200
1500
1700
1700
Air Flow (m3/h)
ESP (Pa)
Standard
15 (0–40)
(min–max)
Dimensions (mm)
H×W×D
200 × 1100 × 620
220 × 1450 × 620
Weight (kg)
Net Weight
34
Noise (dB(A))
H/M/L
39/36/31
39/36/31
Piping (ømm)
Liquid/Gas
9.52/15.88
9.52/15.88
Drainage Piping (mm)
48
41/37/33
41/37/33
9.52/15.88
9.52/15.88
DN25
YES Mini VRF Series | 25
Ceiling Concealed (Medium Static Duct) Indoor
Indoor Unit Model
YDCC
020H0FLEA
YDCC
025H0FLEA
YDCC
034H0FLEA
YDCC
045H0FLEA
YDCC
053H0FLEA
YDCC
066H0FLEA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
2.0
2.5
3.4
4.5
5.3
6.60
Heating
2.20
3.00
3.90
4.95
5.80
6.80
Power Input (W)
-
40
55
75
100
110
185
Current (A)
Nominal
0.35
0.35
0.40
0.46
0.52
0.96
Air Flow (m3/h)
-
380
450
600
800
930
1200
Capacity (kW)
ESP (Pa)
Standard
15 (0–30)
(min–max)
15 (15–80)
226 × 1055 ×
602
226 × 855 × 602
245 × 1475
× 576
226 × 1175 × 602
Dimensions (mm)
H×W×D
Weight (kg)
Net Weight
20
20
23
25
25
32
Piping (ømm)
Liquid/Gas
6.35/9.52
6.35/9.52
6.35/12.7
6.35/12.7
6.35/12.7
9.52/15.88
DN25
Drainage Piping (mm)
Indoor Unit Model
YDCC
078H0FLEA
YDCC
095H0FLEA
YDCC
115H0FLEA
YDCC
140H0FLEA
YDCC
175H0FLEA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
7.80
9.50
11.5
14.0
17.5
Heating
8.20
11.0
13.0
16.5
19.0
Power Input (W)
-
215
270
300
420
510
Current (A)
Nominal
1.08
1.29
1.30
1.90
2.11
Air Flow (m3/h)
-
1360
1600
1900
2200
2700
ESP (Pa)
Standard (min–
max)
Dimensions (mm)
H×W×D
245 × 1475 × 576
Weight (kg)
Net Weight
33
Piping (ømm)
Liquid/Gas
Capacity (kW)
Drainage Piping (mm)
26 | YES Mini VRF Series
15 (15–80)
15 (15–100)
245 × 1805 × 576
41
430 × 1563 × 655
41
9.52/15.88
DN25
58
65
2-way Cassette Indoor
Indoor Unit Model
YDDK028H0PA
YDDK036H0PA
YDDK045H0PA
YDDK056H0PA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
2.8
3.6
4.5
5.6
Heating
3.2
4.0
5.0
6.3
Power Input (W)
-
60
62
68
85
Current (A)
Nominal
0.27
0.28
0.31
0.39
Air Flow (m3/h)
-
500
600
770
900
Capacity (kW)
Unit (H×W×D)
310 × 840 × 520
310 × 960 × 520
Panel (H×W×D)
30 × 1083 × 630
30 × 1203 × 630
Dimensions (mm)
Unit
41
41
47
47
Panel
6
6
7
7
Noise (dB(A))
H/M/L
34/28/22
35/32/27
38/33/28
40/36/34
Piping (ømm)
Liquid/Gas
6.35/9.52
6.35/12.7
6.35/12.7
6.35/12.7
Weight (kg)
Drainage Piping (mm)
DN25
Indoor Unit Model
YDDK
071H0PA
YDDK
090H0PA
YDDK
112H0PA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
Cooling
7.1
9.0
11.2
Heating
8.0
10.0
12.5
Power Input (W)
-
94
129
175
Current (A)
Nominal
0.43
0.59
0.80
Air Flow (m3/h)
-
1160
1500
1700
Unit (H×W×D)
310 × 1200 × 520
310 × 1440 × 520
Panel (H×W×D)
30 × 1443 × 630
30 × 1683 × 630
Unit
53
65
65
Panel
8
9
9
Noise (dB(A))
H/M/L
42/38/35
42/38/35
46/43/38
Piping (ømm)
Liquid/Gas
9.52/15.88
9.52/15.88
9.52/15.88
Capacity (kW)
Dimensions (mm)
Weight (kg)
Drainage Piping (mm)
DN25
YES Mini VRF Series | 27
Round-way Cassette
Indoor Unit Model
YDCK
028H0PA
YDCK
036H0PA
YDCK
040H0PA
YDCK
045H0PA
YDCK
050H0PA
YDCK
056H0PA
YDCK
063H0PA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
2.8
3.6
4.0
4.5
5.0
5.6
6.3
Heating
3.2
4.0
4.5
5.0
5.6
6.3
7.1
Power Input (W)
-
17
19
19
19
26
27
42
Current (A)
Nominal
0.13
0.15
0.15
0.15
0.22
0.28
0.37
Air Flow (m3/h)
-
780
810
810
810
900
960
1100
Capacity (kW)
Unit (H×W×D)
246 × 840 × 840
Panel (H×W×D)
50 × 950 × 950
Dimensions (mm)
Unit
23
26
Weight (kg)
Panel
5.5
Noise (dB(A))
H/M/L
28/27/25
Piping (ømm)
Liquid/Gas
6.35/9.52
29/28/26
6.35/12.7
6.35/12.7
Drainage Piping (mm)
6.35/12.7
31/29/27
32/31/28
32/31/28
6.35/12.7
6.35/12.7
9.52/15.88
DN25
Indoor Unit Model
YDCK
071H0PA
YDCK
080H0PA
YDCK
090H0PA
YDCK
100H0PA
YDCK
112H0PA
YDCK
125H0PA
YDCK
140H0PA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
7.1
8.0
9.0
10.0
11.2
12.5
14.0
Heating
8.0
9.0
10.0
11.2
12.5
14.0
16.0
Power Input (W)
-
42
63
63
129
129
142
171
Current (A)
Nominal
0.37
0.54
0.54
1.07
1.07
1.17
1.39
Air Flow (m3/h)
-
1100
1500
1500
1900
1900
2010
2010
Unit (H×W×D)
246 × 840 ×
840
29
32
47/43/38
48/45/42
Capacity (kW)
Dimensions (mm)
288 × 840 × 840
Panel (H×W×D)
Unit
50 × 950 × 950
26
29
29
Weight (kg)
H/M/L
Piping (ømm)
Liquid/Gas
Drainage Piping (mm)
28 | YES Mini VRF Series
29
5.5
Panel
Noise (dB(A))
29
35/31/28
38/35/32
45/39/36
9.52/15.88
DN25
High Wall Indoor
Indoor Unit Model
YDHW
022H0NA
YDHW
028H0NA
YDHW
036H0NA
YDHW
056H0NA
YDHW
071H0NA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
2.2
2.8
3.6
5.6
7.1
Heating
2.80
3.20
4.00
6.30
7.15
Power Input (W)
-
35
35
40
50
70
Current (A)
Nominal
0.18
0.18
0.23
0.25
0.35
Air Flow (m3/h)
-
450
450
570
730
1050
Dimensions (mm)
H×W×D
295 × 890 × 215
295 × 890 × 215
295 × 890 × 215
302 × 1070 × 220
302 × 1070 × 220
Weight (kg)
Net Weight
14
14
14
16
16
Noise (dB(A))
H/M/L
34/30/26
34/30/26
38/35/31
44/41/39
44/41/39
Piping (ømm)
Liquid/Gas
6.35/9.52
6.35/9.52
6.35/12.7
6.35/12.7
9.52/15.88
Capacity (kW)
Drainage Piping (mm)
DN20
YES Mini VRF Series | 29
Floor/Ceiling Indoor
Indoor Unit Model
YDEC028H0NA
YDEC036H0NA
YDEC045H0NA
YDEC056H0NA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
2.8
3.6
4.5
5.6
Heating
3.2
4.0
5.0
6.3
Power Input (W)
-
110
110
130
130
Current (A)
Nominal
0.55
0.55
0.65
0.65
Air Flow (m3/h)
-
600
600
950
950
Dimensions (mm)
H×W×D
680 x 1245 x 240
Weight (kg)
Net Weight
36
Noise (dB(A))
H/M/L
37/33/30
37/33/30
46/44/41
46/44/42
Piping (ømm)
Liquid/Gas
6.35/9.52
6.35/12.7
6.35/12.7
6.35/12.7
Capacity (kW)
Drainage Piping (mm)
DN25
Indoor Unit Model
YDEC071H0NA
YDEC080H0NA
YDEC090H0NA
YDEC112H0NA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
7.1
8.0
9.0
11.2
Heating
8.0
9.0
10.0
12.5
Power Input (W)
-
180
210
210
210
Current (A)
Nominal
0.83
0.97
0.97
1.20
Air Flow (m3/h)
-
1250
1550
1550
1950
Dimensions (mm)
H×W×D
Weight (kg)
Net Weight
36
Noise (dB(A))
H/M/L
47/45/42
Piping (ømm)
Liquid/Gas
Capacity (kW)
Drainage Piping (mm)
30 | YES Mini VRF Series
680 x 1245 x 240
680 x1670 x 240
38
52/48/46
51
52/48/46
9.52/15.88
DN25
52/48/46
Floor-concealed Indoor
Indoor Unit Model
YDVC
028H0NA
YDVC
045H0NA
YDVC
056H0NA
YDVC
071H0NA
Power Supply (V/Ph/Hz)
220/1/50
220/1/50
220/1/50
220/1/50
Cooling
2.8
4.5
5.6
7.1
Heating
3.2
5.0
6.3
8.0
Power Input (W)
-
41
50
60
71
Current (A)
Nominal
0.18
0.23
0.27
0.32
Air Flow (m3/h)
-
420
680
900
1000
Dimensions (mm)
H×W×D
600 x 730 x 230
600 x 980 x 230
600 x 1334 x 230
600 x 1334 x 230
Weight (kg)
Net Weight
20
24
30
31
Noise (dB(A))
Standard
35/32/30
35/32/30
36/33/31
37/34/32
Piping (ømm)
Liquid/Gas
6.35/9.52
6.35/12.7
6.35/12.7
9.52/15.88
Capacity (kW)
Drainage Piping (mm)
DN25
Note:
1. Cooling conditions: indoor 27°CDB/ 19°CWB, outdoor 35°CDB, equivalent length 10m, IU/OU height difference 0m.
2. Heating conditions: indoor 20°CDB, outdoor 7°CDB/6°CWB, equivalent length 10m, IU/OU height difference 0m.
3. Noise data is tested in semi-anechoic chamber and converted to equivalent anechoic chamber data. The actual noise data could vary per different
installation and working conditions.
YES Mini VRF Series | 31
Notes
32 | YES Mini VRF Series
Notes
YES Mini VRF Series | 33
© 2013 Johnson Controls, Inc.
w w w. j o h n s o n c o n t ro l s . c o m
PUBL-6969