MAKING MODERN LIVING POSSIBLE
Termix VX-C Compact 28
Indirect substation for apartments
District cooling substation for indirect cooling.
Designed for wall-mounting.
Application
District cooling (DC)
District cooling is centralised production and distribution of cooling
energy from the cooling plant to the
air conditioning system of industrial,
commercial or residential buildings.
The Termix VX-C Comp. 28 offers a
hydraulic break in the cooling system
ahead of the air handling units (AHU)
or fancoil units (FCU) in the apartments. The Termix VX-C Comp. 28 is a
complete solution with optimal safety, efficient energy transfer, servicefriendly construction and a compact
design. The Termix VX-C Comp. 28
substation is ideal, when a high level
of security against burst pipes and
water damage in the cooling system
is required.
The substation is prefabricated with a
flow controller with integrated control
valve, fitting piece and sensor pockets
for insertion of an energy meter as well
as strainers.
•• Electronic regulation of
cooling (CO) temperature
Cooling (CO)
•• Capacity: 14-26 kW cooling
The apartment cooling circuit consists of a stainless steel plate heat exchanger, safety valve, pressure gauge,
thermometers, drain valve, air valve,
ball valves and circulation pump. The
temperature of the cooling circuit is
controlled by an electronic temperature controller. The electronic controller offers a very accurate setting
of the flow temperature to the AHU
or FCU.
Construction
All pipes are made of stainless steel. The
connections are made by nuts and gaskets. Condensation insulation is not part
of the delivery of the Termix VX-C Comp.
28 unit.
districtenergy.danfoss.com
FEATURES AND BENEFITS
•• Minimum space required
for installation
•• Pipes and plate heat exchanger
made of stainless steel
•• Designed and optimised
to fit the application
•• Customised versions available
Termix VX-C Compact 28
Circuit diagram – example
DC
Supply
CO
Supply
DC
Return
CO
Return
A Heat exchanger
F Electronic controller
1 Ball valve
4 Safety valve
9Strainer
10 Circulator pump
14 Sensor pocket, energy meter
18Thermometer
Technical parameters:
Nominal pressure:
Max. supply temperature:
DCW static pressure:
Brazing material (HEX):
Fluid medium:
wall
PN 16
Tmax = 50 °C
Tmin = 0 °C
Copper
Water
19 Surface sensor
20 Filling / drain valve
24 Delivered loose with unit
25 Pressure gauge with ball valve
26 Pressure gauge
27Actuator
30 Flow control with control valve
41 Fitting piece, energy meter
Connections:
1. District cooling (DC) supply
2. District cooling (DC) return
3. Cooling (CO) supply
4. Cooling (CO) return
Connections sizes:
DC + CO:
Weight:
60 kg
Electrical supply:
230 V AC
Dimensions (mm):
Without cover:
H 940 × W 640 × D 420
G 1“ (int. thread)
seen from above
DHW: Capacity examples
Flat Station type
VX-C-Comp. 28 CO30
VX-C-Comp. 28 CO40
VX-C-Comp. 28 CO50
VX-C-Comp. 28 CO60
Cooling
capacity
[kW]
14
18
22
26
Supply flow
primary
[°C]
6
6
6
6
Return flow
primary
[°C]
11,00
11,10
11,20
11,20
Flow rate
primary
[l/h]
2,423
3,048
3,683
4,310
Pressure loss
primary
[kPa]*
45
50
45
50
Supply flow
secondary
[°C]
8
8
8
8
Supply flow
secondary
[°C]
14
14
14
14
Flow rate
secondary
[l/h]
2,021
2,599
3,174
3,754
* energy meter not included