Data Sheet SW108 EAE KNX Switch Actuator General Description

Data Sheet SW108
EAE KNX Switch Actuator
General Description
• Eight independent channels which can be
parameterized with ETS3/ETS4
• Suitable for switching resistive, capacitive
and inductive loads as well as fluorescent
lamp loads to EN 60 669
• Manual operation feature for each
channel. The relay can be switched On/Off
with slide switches(No feedback to the bus)
• Following function list provides,
Staircase
External logic
Internal logic
Priority
Threshold
Operating hour
Sweep
• Each channel can actualize any of these functions separately
• Does not require an additional power supply
• Changeable behavior after voltage return, voltage failure, ETS program
Technical Data
Type of protection
Safety class
IP 20
II
EN 60 529
EN 61 140
Power supply :
- Voltage
- Current consumption
--- Screw terminals
21V… 30V DC, SELV
< 10 mA
External supply
Connections
Output
Output life
Type of contact
Installation
Operating elements
Temperature range
Humidity
Dimensions
Weight
Box
© EAE Enerji A.S
- Max tightening torque
- KNX
- Number
- Switching voltage
- Switching capacity 277 V AC
- Fluorescent lighting load to
EN 60 669-1
- Mechanical life
- potential-free, bistable
- 35mm mounting rail
- LED (red) and button
- Ambient
- Storage
- Transport
- max. air humidity
Width W in mm
Width W in units (18 mm modules)
0.45 kg
Plastic, polycarbonate, color grey
0,5…4 mm² solid and stranded wire
0,5…2,5mm² stranded wire with ferrule
0.8 Nm
Bus connect terminal
8 output
277/440V AC; 50/60 Hz
16A / AC 1
16 AX/250 VAC
> 3 x 106
EN 60 715
For physical address
-5° C + 45° C
-25° C + 55° C
-25° C + 70° C
95 % no moisture condensation
65,5 x W x 89mm
144 mm
8 modules
Page 1/2
Data Sheet SW108
EAE KNX Switch Actuator
CE
Application program
In accordance with the EMC
guideline and low voltage
Communications
Number of addresses(max)
objects
122
253
Number of
assignments(max)
253
Connection Example
Scale Drawings
© EAE Enerji A.S
Page 2/2