Testing Device for GLT BMS Controls

Testing Device for 0-10 V GLT / BMS Controls
Ord.no. 533996)
Important User Instructions:
!
Prerequisite for warranty claims is the professional use of the device in accordance with
instructions of the manufacturer.
Use device only if very familiar with operating mode of device to be tested (see product
description for GLT control unit).
We explicitly deny any and all liability for damages due to improper use of this testing device.
Establish and remove any and all plug and socket connections only with power turned off.
Ensure that device is not exposed to humidity or high temperatures.
Note: There is an inherent danger (of crushing or clamping) from electromotively operated
windows controlled by this testing device !
Mode of operation
The testing device serves to test and adjust 24 V DC ventilation control units with a variable controlling or measuring-signal
from 0 - 10 V DC (e.g. for operating timer GLT-LZM 2 or for ventilation control unit module with GLT control).
Scope of delivery of testing device: 4 connecting cables with banana jacks ( 2 x red (+), 2 x black (-)).
Connection, Displays and Control Elements
Dispense
set output voltage?
0 = no /
= yes
setting
output voltage
display
output voltage
(+) red
(+) red
0 - 10 V DC
24 V DC
(0 - 100 % stroke)
(-) black
(-) black
Power supply
e.g. from EMB
SHEVS or
ventilation control unit
operation
on / off
display
Operation
Technical Data
Ensure that unit is turned off when making any
connections (see above).
Power supply
24 - 32 V DC
Current consumption:
approx. 80 mA
Operating switch set to ON (green display lights up).
With the GLT / BMS voltage switched to output
(switch position
), the setting control follows.
When switch is set to “0” position there is no output
(Output voltage = 0 V).
Output voltage
0 - 10 V DC (adjustable)
Setting accuracy:
1 % of full scale 10 V
Output load
max. 2 mA
Display:
3,5 decimals (resolution 10 mV)
If the output voltage is set to a specific value a change
of the switch position from “0” to
makes it possible
to move the drive from the closing position to the desired
opening position (e.g. 5 V = 50 % stroke). By switching
to “0” ( = 0 V), the drive moves back to the closing position
without having to change the set output voltage.
Connections
4 x banana jacks
Operating temperature range: +20 - 30 °C