2.6.4 KNX Communication drivers for electrical systems and room

213
SBC  Software
2.6.4 KNX
Communication drivers for electrical systems and room automation
Communication drivers
1
RS-
/ IP
DP U
t
g
e
elin
ern
Saia PCD3
Communication &
interaction
KNX
Eth P Tunn
XI
KN
KNX
Saia PCD2

Use of drivers for all SBC automation stations
2
Features
232
European Installation Bus EIB
An efficient networking of building services requires multiservice functions and components for communicating with
external devices. The KNX communication driver is a PG5 FUPLA
library with comprehensive function modules (FBoxes) for
sending and receiving almost all of KNX data types (DPT).
Depending on which interface is available for accessing the KNX
network (RS-232 or Ethernet), the selected components can be
linked to either Saia PCD® or PCS systems.
The direct connection via Ethernet makes access to KNX data
even quicker and more powerful.

Comprehensive support of KNX Data Point Types (DPT)

The drivers support the simple restructuring of existing
systems with KNX-BCU1 on the KNX-BCU2 interface

Standard UDP/IP port: #3671

Communication drivers for:
Serial KNX BCU-1 interfaces via RS-232
(not recommended for new products)
EIB FT1.2
―Clr
Err―
―IniSnd
Err―
―IniPol
EIBNet/IP
―Clr
Con―
―IniSnd
Err―
―IniPol
Err―
RS-232/BCU 2 function box
KNX/IP function box
Serial KNX BCU-2 interfaces via RS-232
3
KNXnet/IP (EIBnet/IP) communication
SBC S-Web Technology

Simple communication using Fulpa modules
Order information
Model
PG5-EIB
Description
PG5-KNX/EIB (KNX standard) communication library for Saia PCD®
and PCS controllers for serial and IP-based communication
Components of other providers
Weinzierl KNX IP Interface 730 (www.weinzierl.de)
Weinzierl KNX IP Router 750 (www.weinzierl.de)
ABB IPS/S2.1 EIB/KNX IP Interface (www.abb.com)
ABB IPS/R2.1 EIB/KNX IP Router (www.abb.com)
Weinzierl KNX BAOS 870 (www.weinzierl.de)
KNXnet/IP-Gateway
KNXnet/IP incl. Router use
KNXnet/IP-Gateway
KNXnet/IP incl. Router use
Serial (RS-232) KNX interface with BCU-2 protocol
Compatibility
As of 2012, the tried-and-tested SIEMENS® Gamma Instabus interfaces are no longer available. The actual devices are no more
fully compatible. The interface from «Weinzierl Engineering GmbH» are recommended as a replacement.
Ethernet Gateways
When planning, it is important to take into consideration that some available Ethernet gateways usually only support one
communication channel. As a result, every PCD or service tool, ETS for example, needs its own interface to the KNX-Bus.
Serial converter
However, connecting using BCU-1 protocols is strictly advised against. The BCU-1 protocol can cause telegrams to be lost
between the gateway and the controller.