Data Centre Cooling Technologies

Data Centre Cooling Technologies
1
Jon Pettitt, EMEA DataCenter Business Development Manager
Munters Group – Key facts
• 3.000 Employees
• Global DC Support
• 30 Countries
• 25+ Data Centers
• Turnover of €470 M
• 95 MW+ Cooling
• HQ in Sweden
• 455 Installed units
• Founded1955
Munters – Your Perfect Climate
2
Global Manufacturing & Logistics Support
Manufacturing plants
Logistic & assembly hubs
16 Manufacturing Plants
5 Logistic & Assembly Hubs
53 Sales & Service Centres
Munters Data Centre Installations to May 2013
• Challenges in DC Development
no. 8
Key Challenges & Drivers Impacting the Data Centre Industry
• Reliability/Uptime
• SLA’s
• Contamination
• Energy Costs
• Carbon Emissions
• Modularity
Air Contamination
Infrastructure
•
Power Supplies
• Data Centre size is often restricted by availability of power to site.
• By reducing cooling power consumption, more power becomes
available for critical processes and server operations.
•
Space
• Land cost
• Availability
• Planning Consents
•
Water
• Availability
• Cost
• Cooling Technologies
no. 18
Indirect Evaporative Cooling
no. 19
Oasis IEC Video
Munters Oasis Final English.wmv video runs here
Oasis Indirect Evaporative Cooler Using Polymer Tube HX
Exhaust
Outside
23°C
35°C
Three Modes of Operation
• Mode 1
– Cold Ambient
– Operation:- DRY MODE
– Air to Air Heat exchanger only
• Mode 2
– Warm Ambient
– Operation:- EVAP MODE
– Indirect Evaporative Cooling only
• Mode 3
– Very Warm/Hot Ambient (above approx 22°C WB)
– Operation:- EVAP + DX MODE
– Indirect Evaporative Air Cooling only + DX Cooling circuit
Polymer Heat Exchanger
● Flexible Polymer Tubes
● 2.44 meters length
● 75-80% approach to outdoor
scavenger air wet bulb temp
● 55% dry heat recovery
• Scale Limiting design
• Corrosion Resistant
• Independently tested
• UL 900 Class II
• Flame retardant (UL94-V0)
14
Water Spray Operation
Oasis wetted EPX Video
no. 27
Beneath the Heat Exchanger
16
Legionella Risk Analysis
• The Risk Assessment of the OASIS unit
confirms that the risks of causing growth and
spread of Legionella bacteria are negligible.
• If the temperature is below 25°C, no risk of
occurrence of Legionella in the system,
which is the case most of the time.
• In the operating conditions for water above
25°C, the system is designed so that water
flows continuously in the circuit so that there
is no stagnation of water and no risk of
emergence of bacteria.
• The Oasis IEC has an automatic emptying
system that starts if installation is at standstill
for agreed hours. Therefore no risk of
proliferation of legionella in the water
recovery pan.
OASISTM IEC Range
Oasis 100
< 100 kW
18.000m3/h
22.000m3/h
Oasis 200
< 200 kW
36.000m3/h
44.000m3/h
Oasis 300
< 310 kW
54.000m3/h
66.000m3/h
1 block
1 block
2 prefab blocks
6.9 x 1.4 x 3.6 / 9.4 m2
6.9 x 2.6 x 3.6 / 17.8m2
6.9 x 3.94 x 3.6 / 27.2m2
2.8 Ton
6.6 Ton
8.8 Ton
• #5: Performance & Cost Comparisons
no. 33
Section 5
Independent Performance Verification
Oasis™ Indirect Evaporative Cooler Energy savings vs Chillers
Oasis™ Indirect Evaporative Cooler Energy savings vs Chillers
Results of Independent Engineering Review
Benefits of Oasis™ IEC Cooling over
high efficiency free-cooling chillers:
• Lower capital costs
• Reduced Infrastructure
• 40% lower annual operating cost
• Low partial PUE
Source: Cundall Product Engineering Review. Based on 1MW data centre (N+1)
Hours pa that Oasis IEC can provide 23°C without Mechanical Cooling
Based on Hot Aisle return air temperature of 35DegC
Hours run with
EPX only
Hours run with
EPX and
supplementary
cooling
Hours of operation per year
Hours pa that Oasis IEC can provide 27°C without Mechanical Cooling
Based on Hot Aisle return air temperature of 39DegC
Hours run with
EPX only
Hours run with
EPX and
supplementary
cooling
Hours of operation per year
Existing Installations
no. 39
DCO2 Belgium – 5 MW
●
Winner Datacenter Dynamics leadership award –
'Green Datacentre' 2011 & European Code of
Conduct Award for new Data Centre 2011
●
With free cooling system: dust & pollution from surrounding farmland caused
- Frequent replacement of filters
- Required man power & frequent inspection
- Caused pressure drop & increased fan power
Solution: Munters Oasis Indirect Evaporative Cooler replaced full free cooling system
DataInn, Lithuania – Oasis IEC key to advanced cost
efficiency
“Munters cooling solutions enable us to achieve
an annual PUE of 1.3 or less, which will make us
very cost-effective and competitive in the market.
Every 0.01 reduction in our PUE represents an
energy saving of approximately 210,000 kWh in
our data centre.”
• Secure, reliable data hall climate
• Data centre air fully separated from outside air
• 65% lower energy than common free cooling
solutions
• 25% reduction in refrigeration, switchgear,
generator sets
28
Data Inn Development Manager Edvinas Bakanas,
says:
“The Lithuanian electric energy sector, data
communication operators and biggest banks need their
data to be safe and accessible without interruptions, as
well as cost –effective and eco friendly. The high
efficiency and innovative design were our main reasons
for choosing Munters’ Oasis™ IEC”
“The proven technology fits well with the climate
conditions in Vilnius and offers a high degree of
flexibility, operating in different cooling modes –
depending on weather conditions.”
DigiPlex Oslo – Largest Indirect Evaporative Cooled DC
in Europe
Energy efficiency of 1.12 PUE
•
•
•
•
Annual pPUE of 1.06
Data centre air fully separated from outside
Lower capital costs on refrigeration/switchgear
52 Oasis IEC 200’s
Greg MCCulloch DigiPlex’s Chief Operating Officer:
“Driving energy efficiency in our industry is a major
focus for us and this system halves the amount of
energy used to keep our servers working at an ideal
temperature.
This not only helps save our customers thousands
of pounds in energy costs but also ensures that our
facilities are amongst the most sustainable in the
sector”
29
Australia
T5 El Segundo, CA.
Sabey Intergate Quincy
no. 46
Sabey Case Study
Oasis Sabey Quincy Video runs here
33
Data Centre Test Facility – Dison Belgium
Benefits Oasis™ IEC Systems
• Contamination Control
•
•
•
•
Supply and outdoor airflow do not mix
Corrosion Prevention:
No added moisture/humidity to supply
Usable for any kind of sweet water
Rain water harvesting
Eliminating DX cooling
100% IEC Cooling in some regions
IEC efficiency can increase further
As allowable supply air temperature to server inlet increases,
Thank you
Questions?