Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Hazard
Calculations – What does it
all mean?
Robert E. Fuhr, P.E.
PowerStudies.com
Why are Arc Flash Hazard
Studies Needed?
To Increase Electrical Safety at your
facility!
 Required by National Electric Code (NEC)
and OSHA
 To Protect You!

OSHA Requirements
Standard 29 CFR 1910 Subpart S, 1910 to
1910.336
 Must identify all hazards above 50 Volts
 Must put safeguards in place for these
hazards
 Must train employees on safe work
practices
 OSHA has officially adopted NFPA 70E


Employers must provide workers with
appropriate PPE as per the OSHA 29
1910.132 (h)(1) PPE payment
requirement, i.e., (PPE) used to comply
with this part, shall be provided by the
employer at no cost to employees.
Paragraph (h) became effective February
13, 2008, and employers must implement
the PPE payment requirements no later
than May 15, 2008
Key References in NEC ® -2008
 110.16
Flash Protection. Switchboards,
panel boards, industrial control panels,
and motor control centers in other than
dwelling occupancies, that are likely to
require examination, adjustment,
servicing, or maintenance while
energized, shall be field marked to warn
qualified persons of potential electric
arc flash hazards.
NEC 110.16
 The
(continued)
marking shall be located so as to
be clearly visible to qualified persons
before examination, adjustment,
servicing, or maintenance of the
equipment.
Key References in NEC ® -2005

FPN No. 1 : NFPA 70E-2004, Standard For
Electrical Safety in the Workplace,
provides assistance in determining severity
of potential exposure, planning safe work
practices and selecting personal protective
equipment.
NFPA 70E -Flash Hazard Analysis



130.3 – A flash hazard analysis shall be done
in order to protect personnel from the
possibility of being injured by an arc flash.
The analysis shall determine:
–
–
Flash Protection Boundary
Personal protective equipment
–
Formulas in 130.3.A and Table 130.7(C)(9)(a)* in
NFPA 70E
* - Use with extreme caution!!!
Equations in IEEE 1584
Calculate using
–
–
Industry standards and
regulations:



OSHA 29 CFR 1910
Subpart S
NFPA 70 - The
National Electrical
Code (2008 Edition)
NFPA 70E - Standard
for Electrical Safety in
the Workplace (2004
Edition)
Arc Flash Hazard Analysis Key
Steps

Use NFPA 70E* Tables, IEEE 1584, or Lee
Equations to Determine
– Incident energy levels
– Arc Flash hazard distance

* Use with extreme caution!
Arc Flash Hazard Analysis Key
Steps

Use
– Calculated Incident
Energy
– NFPA 70E Table
130.7(C)(11)
– to determine


Hazard/Risk Category
Required PPE
Acceptable & Informative Labels
NFPA 70E Table 130.7(C)(11)
Obtain Equipment
Nameplate Data
& Settings
Short Circuit
Fault Study
3 Phase Bolted
Fault Current
Arcing
Fault Current
Coordination (PDC)
Study
Device
Operating Time
Arc Flash Label
Energy Level
Boundaries
Required PPE
Arc Flash Study
Arc Flash Energy Calculation
Use 85%Ia
 Determine Upstream Protective Device
Clearing Times (PDC Study)
 Repeat process for 100%Ia
 Use largest energy calculation

Arc Flash Hazard Analysis Key
Steps
 Determine:
– Bolted Fault Currents (Short Circuit
Study)
– Arcing Fault (AF) Current
– Upstream Protective Device Clearing
Times (PDC Study) using AF
Arc Flash Hazard Analysis Key
Steps
 Calculate
Arc Flash Energy
 Use NFPA 70E Tables to determine:
– Glove Rating Class
– Limited Approach Boundary
– Prohibited Approach Boundary
– Restricted Approach Boundary
– Required PPE
Arc Flash Hazard Analysis Key
Steps

Arc Flash Warning Labels showing the
details.
How a Short Circuit Study is
Performed

Obtain distribution system nameplate data
for:
– Transformers
– Motors
– Circuit breakers, fuses, relays
– Switchgear
– Motor Control Centers
– Conductor sizes and lengths
How a Short Circuit Study is
Performed



Enter data into the
computer program.
Simulate short circuit
at each location and
calculate the fault
current.
Compare calculated
fault current to
equipment short
circuit rating.
What is Protective Device
Coordination (PDC) Study?

Determines:
– fuse sizes
– Settings for relays
and circuit breakers
– Device operating
time

The study has 2
conflicting goals
Goal #1 - Maximum Selective
Coordination Between Equipment
Correct fuse sizes and settings will allow
the device closest to a fault to trip.
 If the first device fails to operate, then the
next upstream device will trip.
 Longer device trip delays = increased
device coordination= greater incident
energy

P
Selective
Coordination
2- XFMR-UTILS
S
XFMR-UTILS
3
3-MSWBD MAIN
SWBD
2
E
5-Fdr to ATS-E
N
ATS 260 Amp
1
6-PNL-A MAIN
PNL-A - 250 A
Goal #2 - Maximum Equipment
Protection and Reduction in Arc
Flash Energy
Correct fuse sizes and device settings will
quickly interrupt the fault current for a
short circuit downstream.
 Shorter device delays = decreased
equipment damage = less Incident Energy

Maximum
Equipment
Protection
P
2- XFMR-UTILS
S
XFMR-UTILS
1
3-MSWBD MAIN
SWBD

(No Selective Coordination)
1
E
5-Fdr to ATS-E
N
ATS 260 Amp
1
6-PNL-A MAIN
PNL-A - 250 A

Must balance these two conflicting goals
based upon the type of facility.
PDC Vocabulary
Time Current Curve (TCC)
 Log-log graph of time versus current
 Every breaker, fuse, and relay has a
time current characteristic curve.

PDC Vocabulary

Selective Device Coordination
– The devices plotted on the time current
curves are coordinated for all levels of fault
current and time.
Fuse
TCC
@15 kA
This Fuse
is Current
Limiting –
Clearing
time is
0.004
seconds
3-6 Sec
5 kA
Thermal
Magnetic
Trip Unit


Thermal
Unit is
Fixed
Instantaneous
– Fixed
– Adjustable
Thermal
Magnetic
Breaker
20-50 Sec
4 kA
0.01-0.025 Sec
20 kA
Solid
State Trip
Unit



SQ D NW
40H
4000 Amp
Micrologic
Current Sensors
Rating Plugs
Current Setting
Solid
State Trip
Unit


Varies for
each Trip
Unit!
Some
Functions
are Not
Adjustable!
Long Time Pickup (LTPU)
Long Time Delay (LTD)
Short Time Pickup (STPU)
Short Time
Delay I2T-IN
(I2T)
Short Time Delay (STD)
Instantaneous (I)
Solid
State Trip



170-210 Sec
SQ D NW
40H
4000 Amp
Micrologic
6 kA
0.08-0.12 Sec
30 kA
100 kA
0.01-0.06 Sec
Time Current Curves

An example
of a TCC with
Coordinated
Devices
Current in Amperes X 100
Arc Flash Energy Calculations

Incident Energy Levels are dependent on:
– Level of arcing fault current
– Upstream device clearing time.

Multiple Sources
Typical Assumptions for an
Analysis
Trip time is determined by the upstream
protective device settings.
 Worker is stationary.
 The maximum time that a worker will be
exposed to the arc flash is 2.0 seconds.
(Depends upon location!!!)

Fault Current vs. Incident Energy
In c id e n t E n e rg y
Current
Energy
(TimeVs
Constant
@ 0.025 Sec)Levels
4
3
2
1
1
0
0 0
0
1
1
1
1
1
1
0
20
40
60
Fault Current
Energy
PPE Class
80
100
In c id e n t E n e r g y
Time vs. Incident Energy
Time
Vs
Energy
Levels
(Fault Current Constant @ 30 kA)
30
20
10
1 1 1 2
0
0
0.1
2
3
3
3
4
0.2
0.3
0.4
0.5
Device Operating Time
Incident Energy
PPE Class
0.6
Distance vs. Incident Energy
In c id e n t E n e rg y
(Time Constant
Sec & Fault = 60
kA)
Distance
Vs@ 0.5Energy
Levels
50
40
30 4+ 4 3
20
10
0
0
2
1
0
50
100
150
Distance (Inches)
Energy
Class
200
250
Arc Flash Warning Labels

What does it mean?
Limited Approach Boundary:
An approach limit at a distance from an
exposed live part within which a shock
hazard exists. This value is determined by
NFPA 70E (2004) Table 130.2(B).
 Qualified Persons
 Unqualified if accompanied by a Qualified
Persons
 PPE not required if AF Boundary is not in
Limited Approach Boundary

Restricted Approach Boundary
An approach limit at a distance from an
exposed live part within which there is an
increased risk of shock, due to electrical
arc over combined with inadvertent
movement, for personnel working in close
proximity to the live part.
 Determined by NFPA 70E (2004) Table
130.2(B)

Restricted Approach Boundary
Qualified Persons Only
 Must wear PPE

Prohibited Approach Boundary
An approach limit at a distance from an
exposed live part within which work is
considered the same as making contact
with the live part.
 Determined by NFPA 70E (2004) Table
130.2(B).
 Qualified Persons Only
 PPE Required as if in direct contact

Flash
Protection
Boundary
Boundary
Varies
Flash Protection Range
Qualified Persons Only
PPE Required if Flash Protection Boundary is Crossed
FPB dependent on:
Voltage Level
Fault level
Trip Time of Protective Device
Restricted Boundary
(Fixed by Voltage)
Limited Approach Range
Prohibited Boundary
(Fixed by Voltage)
Restricted Range
Limited Approach Range: Qualified or unqualified persons*
*Only if accompanied by Qualified Person
Restricted Boundary: Qualified Persons Only, PPE required
Prohibited Boundary: Qualified Persons Only. PPE required as if direct contact with
energized part
Prohibited Range
Equipment
Limited Approach
Boundary
(Fixed by Voltage)
Arc Flash Label Installation
Always clean the surface with detergent to
remove all grease and dirt. Wipe surface
dry before applying the label.
 Some locations will have a Line Side Label.
They should be installed at locations
where maintenance staff could be exposed
to energized parts on the line side of a
fuse or circuit breaker. Examples of this
are Main Breakers in Switchboards and
Switchgear.

Arc Flash Label Installation
Transformer Labels are for small
distribution transformers (480/208 V)
where both the 480 and 208 Volts
terminals are exposed.
 Locations where the label will be exposed
to direct sun light should be brought to
the attention of PowerStudies.com. We
will provide labels with a special UV
protective covering to protect the label
from fading.

Line Side vs Bus AF Labels
Need more Information

www.powerstudies.com
– Articles
– Links
– Specifications for Power System Studies
 Short Circuit
 Protective Device Coordination
 Arc Flash Hazard
Phone: 253-639-8535
 Email: [email protected]

Your Report
Thank you for your time!

Questions?????