IPC4012 - ProTrol AB

IPC4012
Fault Detector and Remote Terminal Unit
IPC4012 is a fault detector for overcurrent and earth faults with
integrated remote terminal unit functionality. It has I/O for
indications and orders and is therefore suitable for a typical
secondary substation. Powerful relays enable direct operation of
switching devices. The communication interface is IEC 60870-5-104.
Since the algorithm for earth fault detection does not require any
voltage measurement, IPC4012 provides cost efficient fault
detection and grid automation with high sensitivity for pass-through
faults, also in networks where the earth fault currents are low.
DATASHEET
IPC4012
Fault Detection
Other Functions
Overcurrent, OC1 and OC2
HMI – User Interface
Settings 0.1 – 3.5 × rated CT current, 0.04 – 10 s.
Detected overcurrent or earth fault is indicated by
diodes and can be reset by a push button, remote
control and/or after a pre-defined time.
Earth Fault, EF
Protrol’s patented Fault Pass Through earth fault
detection for all indirectly earthed networks. Capable
of detecting high impedance and arcing earth faults.
Note that no voltage measurement is necessary for
good selectivity at very low currents. The sensitivity is
comparable with that of a directional earth fault
protective relay.
Separate diodes indicate status for power supply,
internal supervision and activity of the communication
ports.
Settings1 0.8 – 300 A, 0.02 – 2 s.
The IPC software can be customized with special logic
(PLC function) when needed.
A non-directional earth fault stage is integrated.
1 The level reflects primary fault current and corresponds to the
base ratio 300/1. If current transformers with ratio 150/1 are used,
the setting range is 0.4 – 150.0 A.
Transient Fault Recorder
The built-in transient fault recording function registers
currents and events from the last two detected faults,
each with a duration of two seconds. It is possible to
connect to the service interface to analyze signals and
events in detail.
Settings and configuration is done in Protrol Tool
(Windows XP/Vista/7/8) using the USB-port.
Customization
Options
IPC4012 can be ordered with an auto-reclosing
function with one reclose attempt after a set time.
Technical Data
General
Dimensions2:
195 × 105(115) × 64 mm.
Assembly:
DIN bracket
Ambient temp:
-20 – +60 °C
Supply voltage:
24 – 48 VDC
Supply current:
appr 30 mA at 24 VDC
Standards:
EN 61000-6-2 – Immunity
EN 61000-6-4 – Emission class B
EN 61000-6-5 – For installation in
medium voltage substations
Remote Terminal Unit
Tests according to: EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
Binary objects:
EU directives:
12 inputs, 4 object for
Start and Trip for OC and EF
respectively (Single Point /
Double Point)
2
ROHS, EMC, LVD
Height 115 mm includes the female contacts.
Service Port:
6 outputs, 1 object for remote
acknowledge (Single Cmd /
Double Cmd)
Analogue objects:
Protrol AB
Ullevigatan 19
411 40 Göteborg
USB:
Type B
Temperature + 3 phase currents
Ver 1409
Tel: 031- 45 82 00
internet: www.protrol.se
e-mail: [email protected]
Technical Data, cont´d
Ordering Information
Inputs and Outputs:
Article Number
Binary inputs:
12 st, 24 – 110 VDC.
The article number is specified as 101132(-WXY-Z).
Binary outputs:
4 power relays, 8 A breaking
current at 30 VDC.
2 signal relays3, 3 A breaking
current at 30 VDC.
Basic version:
Analogue inputs:
Options
IPC4012 can also be ordered with additional
functionality which is specified by the following postfix
to the article number of the basic version
3 st, 1 A or 5 A
All binary in- and outputs are equipped with LED
indications.
3
101132
Option W = Hardware version 0-9
0 – Basic version
1 – Latching relay at output 5
These can be replaced with one latching relay when required.
Option X = Communication protocol 0-9
System Port:
Ethernet
0 – IEC 60870-5-104
RJ45
Option Y = Software options 0-9
Communication Protocol:
0 – Basic version
1 – Auto-reclosing function
IEC60870-5-104
Option Z = Other adjustments 00-99
00 – Standard software
01-99 – Software version 01-99
Example article number
IPC4012 with auto-reclosing function: 101132-001-00
Schematic Overview
Binary input
X5
1
Binary output
X6
2
C
3
12
4
11
5
10
9
X7
2
1
C
4
3
8
7
5
6
6
5
8
7
4
3
9
1
2
X8
2
C
1
3
6
X9
1
5
2
C
3
4
1
3
2
C
3
2
1
IPC4012
or
RUN
PWR
S1
S2
S3
S4
S5
AUT
Ethernet
USB
RJ45
Type B
TxL
Tx
RxL
Rx
RUN
AUX
OC
EVNT
IRF
EF
IA
C
1
IB
5A 1A
2
3
X1
Protrol AB
Ullevigatan 19
411 40 Göteborg
C
1
X2
Ver 1409
ACN
6
5
IC / IN
5A 1A
2
C
3
C
1
X3
5A 1A
2
3
PWR
+ GND 1
2
PWR
3
X4
Tel: 031- 45 82 00
internet: www.protrol.se
e-mail: [email protected]
Typical Application
In the figure below it is illustrated how a number of IPC4011 are connected to each other and the operations center
using the remote communication protocol IEC60870-5-104.
When a fault occurs in the loop, each IPC unit will send information if the fault has passed (earth fault and
overcurrent) to the operations center via remote protocol. The operation engineer can then order disconnection of
the faulty segment by sending orders to suitable IPC units. IPC4012 is prepared for automatic fast disconnection in
stations equipped with circuit breakers. Fault isolation using load disconnectors must be performed on a dead line.
In the station with two outgoing cables (top right), an alternative solution featuring two IPS2 units and a Protrol RTU is
demonstrated.
Protrol AB, Ullevigatan 19, 411 40 Göteborg
Tel: 031-45 82 00. E-post: [email protected]
www.protrol.se
Protrol AB
Ullevigatan 19
411 40 Göteborg
Ver 1409
Tel: 031- 45 82 00
internet: www.protrol.se
e-mail: [email protected]