279 - icolim 2014

Function and use of arc fault protection
systems in low-voltage switchgear installations
Rainer Ziehmer, DEHN + SÖHNE GmbH + Co.KG.
© 2014 DEHN + SÖHNE / protected by ISO 16016
Rainer Ziehmer
Product Manager
Safety Equipment
DEHN + SÖHNE
GmbH + CO.KG.
Hans-Dehn-Str. 1
92318 Neumarkt
Tel.: +49 9181 906-1305
FAX: +49 9181 906-1219
[email protected]
www.dehn.de
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
Arc fault risk for persons
Risk
Arc faults cannot be
completely ruled out
High risk of damage to
persons and installations
Direct effects of
arc faults
Thermal effect
Incident energy / high
temperature / hot particles
Radiation effect
Flash / electromagnetic
radiation (IR … UV)
Dynamic effect
Pressure wave / sound / forces
Toxic effect
Pyrolysis / toxic gases / metal
vapours
© 2014 DEHN + SÖHNE / protected by ISO 16016
12.11.13 / 7087_D_1
Arc fault protection
Arc fault risk for persons
Reduction of arc fault effects to
an acceptable level
Reduction of the arc energy by
limiting the arc duration
Short-circuiters allow to
considerably reduce thermal
and toxic effects
Technical solution: DEHNarc arc
fault protection system
© 2014 DEHN + SÖHNE / protected by ISO 16016
AS Seminar Störlichtbogenschutz
16.12.13 / 7087_D_2
Protection of persons during live working
from the effects of an arc fault: Example 1
Operating time of a 630 kVA gTr fuse (400 V, 909 A)
Prospective short-circuit current Ipros for 630 kVA installations: 16 kA to 23 kA
Arc voltage Uarc in 400 V low-voltage systems: up to 200 V
Arc current Iarc: up to 50% lower than the prospective short-circuit current
Pre-arcing time of the fuse in case of a 10 kA arc: 200 ms => tarc > 200 ms
In this case, the energy Warc of a three-pole arc is calculated as follows:
Warc = √3 • Uarc • Iarc • tk = √3 • 200 V • 10 kA • 200 ms = 693 kJ
400 V/
630 kVA
909 A
gTr
arc faults
LV power
distribution
400 V / 909 A / gTr
L1
L2
L3
200 ms
PEN
Parc ≈ 3.5 MW
10 kA
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
07.02.14 / 7284_E_1
Protection of persons during live working
from the effects of an arc fault: Example 2
Limitation of the arc energy in a 630 kVA installation (400 V, 909 A)
An arc fault (for example 10 kA) is detected within about 3.5 ms
A three-pole metallic short-circuit is initiated within about another 1 ms
The arc power is reduced by short-circuiting the voltage after approximately 0.5 ms
The arc energy Warc of a three-pole arc fault is reduced by the factor 40 to:
Warc = √3 • Uarc • Iarc • tk = √3 • 200 V • 10 kA • 5 ms = 17 kJ
400 V/630 kVA
DEHNarc
short-circuiter
909 A gTr
arc faults
LV power distribution
L1
L2
L3
PEN
KST
Parc ≈ 3.5 MW
DEHNarc STG
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
07.02.14 / 7284_E_2
DEHNarc mobile arc fault protection system
Effects without arc fault protection system
Direct thermal exposure without protection:
∆Tmax = 77.9 K
Ei0 = 432 kJ/m²
“STOLL curve “
Without arc fault protection system:
Arc current of 6.2 kA for 500 ms
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
05.11.12 / 7150_E_1
DEHNarc mobile arc fault protection system
Principle of the arc fault protection system
Significant limitation of the thermal effects of arc faults:
“STOLL curve“
∆Tmax = 1.23 K
Ei0 = 638 kJ/m²
With arc fault protection system:
Arc for 8.3 ms and short-circuit current of
7.7 kA for about 500 ms
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
05.11.12 / 7150_E_2
Protective effect of the DEHNarc arc fault protection
system
Significant limitation of the effects of an arc fault:
Toxic effect:
Pyrolysis, toxic gases and metal vapours are minimised
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
07.02.14 / 7285_E_1
DEHNarc mobile arc fault protection system
Arc fault detection
Multiple redundant detection by means of three sensors
Response to light variation 9.000 lx / ms
or absolute illuminance 100.000 lx
Unaffected by extraneous light
Suited for open installations
Monitored fibre optic cable
Typical detection times
Parc ≥ 100 kW ⇒ 20 ms
Parc ≥ 400 kW ⇒ 13 ms
Parc ≥
1 MW ⇒
Parc ≥
3 MW ⇒ 3.5 ms
7 ms
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
07.11.13 / 7151_E_1
DEHNarc mobile arc fault protection system
Fixed components
1
2
Wall-mounted pair of light sensor
supports (sensor 1 and 2)
C-rail-mounted light sensor
support (sensor 3)
4
NH fuse disconnector (4)
3
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
30.01.14 / 7152_E_1
DEHNarc mobile arc fault protection system
Mobile components
Control unit with three light sensors,
power and control line sockets
Disconnecting blade
Short-circuiting cartridges
Junction piece
Technical data
Nominal voltage
230/400 V 50 Hz
Prospective short-circuit 2 – 25 kA
current
Max. short-circuit
duration
70 ms (at 25 kA)
Typical response time
5 ms (at 65 kA)
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
30.01.14 / 7153_E_1
DEHNarc mobile arc fault protection system
Mobile arc fault protection system
ensures the protection of persons and
installations during live working
The direct effects of an arc fault under
fault conditions are actively reduced to a
minimum
Easy initial operation of the mobile arc
fault protection system on the prewired
low-voltage equipment
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
Störlichtbogenschutz
29.01.14 / 7156_E_1
Components of the DEHNarc mobile arc fault
protection system – Design of the cartridge
trigger connection
air gap
movable electrode
spring
melting tube
© 2014 DEHN + SÖHNE / protected by ISO 16016
Arc fault protection
07.02.14 / 7285_E_1
Arc fault test
65 kA low-voltage switchgear installation
© 2014 DEHN + SÖHNE / protected by ISO 16016
AS Seminar Störlichtbogenschutz
07.02.14 / 7286_D_1
Principle of DEHNshort
Point sensors and current transmission
detection device
S4
S3
S2
light sensors
S1
fiber optic output
short-circuiting unit
T1
circuit breaker
>I
© 2014 DEHN + SÖHNE / protected by ISO 16016
current transformer
RZI 240114
Arc fault protection system
Maximum availability of the
installation following an arc fault
thanks to fast recommissioning
Active arc fault protection system
protects persons
© 2014 DEHN + SÖHNE / protected by ISO 16016
AS Seminar Störlichtbogenschutz
03.02.14 / 7163_D_1
Thank you for your attention
© 2014 DEHN + SÖHNE / protected by ISO 16016