ECE 422 Homework 6 Power System Controls 1. Problem 12.2 on page 683 of the course textbook. The automatic voltage regulator (AVR) system of a generator is represented by the simpified block diagram shown in Figure 12.20, in which the sensor is modeled by a simple first-order transfer function. The voltage is sensed through a voltage transformer and then rectified through a bridge rectifier. Parameters of the AVR system are given as follows: Element Amplifier Gain KA Time Constant τA=0.1 Exciter KE=1 τE=0.4 Generator KG=1 τG=1.0 Sensor KR=1 τR=0.05 a. Determine the open loop transfer function of the block diagram and the close loop transfer function relating the generator terminal voltage Vt(s) to the reference voltage Vref(s). The open loop gain can be interpreted as either of two things: the forward path gain or the loop gain. The forward path gain is KE KA KG KA 1 1 GF( s ) = = 1 τA s 1 τE s 1 τG s ( 1 0.1 s ) ( 1 0.4 s ) ( 1 1.0 s ) The loop gain is KE KA KG KR KA 1 1 GOL( s ) = = 1 τA s 1 τE s 1 τG s 1 τR s ( 1 0.1 s ) ( 1 0.4 s ) ( 1 1.0 s ) ( 1 0.05 s ) The closed loop transfer function is K A 1 1 ( 1 0.1 s ) ( 1 0.4 s) ( 1 1.0 s ) GCL( s) = 1 KA 1 1 1 ( 1 0.1 s) ( 1 0.4 s) ( 1 1.0 s) ( 1 0.05 s) KA ( 1 0.05 s) GCL( s) = [ ( 1 0.1 s) ( 1 0.4 s) ( 1 1.0 s) ( 1 0.05 s) ] KA GCL( s) = KA ( 1 0.05 s) 0.002 s4 0.067 s3 0.615 s2 1.55 s K 1.0 A 25 KA s 500 KA GCL( s) = 4 3 2 s 33.5 s 307.5 s 775.0 s 500.0 KA 500.0 b. For the range of KA from 0 to 12.16, comment on the stability of the system. Our characteristic polynomial is 4 3 2 s 33.5 s 307.5 s 775.0 s 500.0 KA 500.0 = 0 KA 0 For our polynomial roots are found as v 1 33.5 307.5 775 For KA 12.15 500 KA 500 T our polynomial roots are found as 1 0.4 polyroots( v ) 0.1 0.05 0.059 6.848i 10 3 v 1 33.5 307.5 775 500 KA 500 3 0.059 6.848i 10 polyroots( v ) 5 2.775 10 0.208i our polynomial roots are found as For KA 12.16 2.775 10 5 0.208i 0.059 6.862i 10 3 T v 1 33.5 307.5 775 500 KA 500 3 0.059 6.862i 10 polyroots( v ) 5 0.208i 1.069 10 MATLAB commands to get a rootlocus for this function are 1.069 10 5 0.208i T >> sys=tf([1],[0.002 0.0667 0.615 1.55 1]) sys = 1 ----------------------------------------------0.002 s^4 + 0.0667 s^3 + 0.615 s^2 + 1.55 s + 1 Continuous-time transfer function. >> K=linspace(0,12.16,500); >> rlocus(sys,K) >> Therefore, we find that the sytem is stable for values of KA up to 12.15 and gives roots in the right half plane for KA=12.16 or greater. 6 4 Root Locus Root Locus 6 Imaginary Axis (seconds-1) 4 2 0 -2 -4 -6 -25 -20 -15 -10 -5 0 5 -1 Real Axis (seconds ) Routh - Hurwitz criterion: 4 S 3 s 2 s 1 307.5 33.5 775 1 307.5 33.5 775 284.366 33.5 1 s 0 s 0 1 500 500 KA 0 33.5 = 500 500 K A 33.5 775 33.5 284.366 500 500 K A = 716.10 58.90 KA 284.366 284.366 500 500 KA 716.10 58.90 KA 0 716.10 58.90 KA 500 500 KA = 500 500 KA 33.5 0 284.366 0 0 284.366 0 From the s 1 row, 716.10 58.90 KA = 0 KA = 12.16 From the s 0 row, 500 500 KA = 0 KA = 1 Therefore, to avoid sign changes in the array, 1 KA 12.16 c. For KA=10, evaluate the steady state step response and steady state error. 500 KA 10 4 GCL( s) = 4 3 2 s 33.5 s 307.5 s 775.0 s 500.0 KA 500.0 Steady state step response is GCLss( s) = s G ( s) 1 CL s s0 lim Recall 25 KA s 500 KA GCL( s) = 4 3 2 s 33.5 s 307.5 s 775.0 s 500.0 KA 500.0 KA 10 Evaluate 25 KA s 500 KA 1 s s 0 s4 33.5 s3 307.5 s2 775.0 s 500.0 K 500.0 s A lim Steady state output (for a unit step input) is 500.0 KA 500.0 KA 500.0 KA 10 500.0 KA GSS KA 500.0 KA 500.0 GSS KA 0.909 Steady state error is the difference between the steady state input and the steady state feedback, Xin 1.0 Xfb GSS KA Xin 0.909 ESS Xin Xfb 0.091 Problem 2. 12.5 on page 684 of the course text book. An area of an interconnected 60-Hz power system has three turbine generator units rated 200, 300 and 500 MVA. The regulation constants of the units are 0.03, 0.04 and 0.06, respectively, based on their ratings. Each unit is initially operating at one half of its own rating when the load suddenly decreases by 150MW. a. Determine the unit area frequency response characteristic β on a 100MVA base b. Determine the steady state increase in area frequency c. Determine the MW decrease in the mechanical power output of each turbine. Assume that the reference power setting of each turbine governor remains constant. Neglect losses and the dependence of load on frequency. a. Determine the unit area frequency response characteristic β on a 100MVA base 6 MVA 10 V A Sbase 100 MVA fbase 60 Hz S1 200 MVA S2 300 MVA S3 500 MVA R1x 0.03 R2x 0.04 R3x 0.06 Sbase R1 R1x S1 R1 0.015 Sbase R2 R2x S2 R constants are inversely related to MVA. R2 0.013 Sbase R3 R3x S3 R3 0.012 Add the inverse R constants to get β. β 1 R1 1 R2 1 β 225 R3 b. Determine the steady state increase in area frequency Δpm 150 MW Δpm 1.5 Sbase 1 Δf Δpm β 3 Δf 6.667 10 ΔfHz Δf fbase ΔfHz 0.4 Hz c. Determine the MW decrease in the mechanical power output of each turbine. Let ∆pref=0. Δpm = Δpref β Δf Calculate each change in power output Δpm1 Δpm2 Δpm3 1 R1 1 R2 1 R3 Δf Δpm1 0.444 Δpm1 Sbase 44.444 MW Δf Δpm2 0.5 Δpm2 Sbase 50 MW Δf Δpm3 0.556 Δpm3 Sbase 55.556 MW Problem 3. 12.10 on page 685 of the text book. Open PowerWorld simulator case Problem 12.10. The case models the system from Example 12.5 except the following: 1) the load increase is a 50% rise at bus 6 for a total increase of 250MW (from 500MW to 750MW) 2) the value of R for generator 1 is changed from 0.05 to 0.04 per unit. Repeat Example 12.4 for these modified values. Problem 3. 12.11 on page 685 of the text book. Open Power World simulator case problem 12.11, which includes a transient stability representation of the system from example 6.13. Each generator is modeled using a two-axis model, an IEEE Type 1 exciter and a TGOV1 governor with R=0.05 per unit. A summary of the generator models is available by selecting either Stability Case Info, Transient Stability Generator Summary, which includes the generator MVA base, or Stability Case Info, Transient Stability Case Summary. The contingency is the loss of tthe generator at Bus 50, which intially has 42.1MW of generation. Analytically determine the steady state frequency error in Hz following this contingency. Use PowerWorld Simulator to confirm this result. Also determine the magnitude and time of the largest bus frequency deviation. See next page for answers to these two problems. Problem 4. 12.14 and 12.16 on page 685 of the text book. 12.14 A 60 Hz power sytem consists of two interconnected areas. Area 1 has 1200 MW of generation and an area frequency response characteristic β1 = 600MW/Hz. Area 2 has 1800 MW of generation and β2 =800MW/Hz. Each area is initially operating at one half of its total generation, at ∆ptie1 =∆ptie2 =0 and at 60 Hz when the load in Area 1 suddenly increases by 400MW. Determine the steady state frequency error and the steady state tie line error ∆ptie of each area. Assume that the reference power settings of all turbine governors are fixed. That is, LFC is not employed in any area. Neglect losses and the dependence of load on frequency. 12.16 Repeat Problem 12.14 if LFC is employed in both areas. The frequency bias coefficients are Bf1 =β1 =600MW/Hz and Bf2 =β2 =800MW/Hz. Δpm1 400 MW MW β1 600 Hz Δpm2 0 MW MW β2 800 Hz The overall frequency - power droop relation is Δpm1 Δpm2 = Δpref1 Δpref2 β1 β2 Δf Solve this for the frequency Δf Δpm1 Δpm2 β1 β2 Δf 0.286 Hz Δptie2 β2 Δf Δptie2 228.571 MW Δptie1 Δptie2 Δptie1 228.571 MW Checking, Δptie1 Δpm1 β1 Δf Δptie1 228.571 MW Problem 12.16. Area Control restricts the net tie line changes to zero. Area 1 must pick up its own generation increase without any change in system frequency in steady state. Problem 5. 12.19, 12.20, and 12.21 on page 686 of the text book. 12.16 The fuel cost curves for two generators are given as follows: 2 2 C1 P1 600 15 P1 0.05 P1 C2 P2 700 20 P2 0.04 P2 Assuming the system is lossless, calculate the optimal dispatch values of P1 and P2 for a total load of 1000MW, the incremental operating cost, and the total operating cost. PT 1000 The incremental cost functions are IC1 P1 15 0.10 P1 IC2 P2 20 0.08 P2 IC1 = d C1 P1 dP1 IC2 = d C2 P2 dP2 Set the incremental costs equal and solve for the power values. IC1 = IC2 15 0.10 P1 = 20 0.08 P2 0.10 P1 0.08 P2 = 5 P1 P2 = 1000 P1 0.10 0.08 1 5 P2 1 1 1000 P1 472.222 P2 527.778 P units are MW. λ values are the incremental costs. Solve for both as a check. λ IC1 P1 λ 62.222 λ units are dollars/MWh. λ IC2 P2 62.222 Total cost is the sum of the cost functions. C1 P1 600 15 P1 0.05 P1 2 C1 P1 18833.02 Ctotal P1 P2 C1 P1 C2 P2 2 C2 P2 22397.531 C2 P2 700 20 P2 0.04 P2 C units are dollars/hour. Ctotal P1 P2 41230.56 12.20 Rework Problem 12.19 except assume that the limit ouptut are subject to the following inequality constraints: 200 < P1 < 800 MW 100 < P2 <500 MW P2 is over this limit. Set P2 to its limit and solve the problem. P1 is the difference between Ptotal and P2. P2 500 PT 1000 P1 PT P2 P1 500 The units on P are MW. System λ is the λ of the unlimited unit, P1, λ 65 The λ units are dollars/MWh. λ IC1 P1 Total cost is the sum of the cost functions. C1 P1 600 15 P1 0.05 P1 2 Ctotal P1 P2 C1 P1 C2 P2 2 C2 P2 700 20 P2 0.04 P2 C1 P1 20600 C units are dollars/hour. C2 P2 20700 Ctotal P1 P2 41300 12.21 Rework problem 12.19 except assume the 1000MW value also includes losses and that the penalty factor on the first unit is 1.0 and the second 0.95. L1 1.0 L2 0.95 Include the losses in the 1000MW figure. PT = P1 P2 PL PT PL = P1 P2 = 1000 λ is the product of incremental cost and penalty factors. λ = L1 IC1 = L2 IC2 Calculate the incremental costs and multiply by the penalty factors. IC1 P1 15 0.10 P1 IC2 P2 20 0.08 P2 IC1 = d C1 P1 dP1 IC2 = d C2 P2 dP2 L1 IC1 = L2 IC2 1.0 15 0.01 P1 = 0.95 20 0.08 P2 Write the equations from this information. 0.95 0.08 0.076 0.01 P1 0.95 0.08 P2 = 0.95 20 1.0 15 0.95 20 1.0 15 4 0.01 P1 0.076 P2 = 4 P1 P2 = 1000 Solve for the power values. P1 P2 1 0.1 0.076 4 1 1 1000 P1 454.545 P2 545.455 P units are MW. Solve for the λ value; check with the other generator. λ L1 IC1 P1 λ L2 IC2 P2 IC1 P1 15 0.10 P1 λ 60.455 λ units are dollars/MWh. IC2 P2 20 0.08 P2 λ 60.455 Total cost is the sum of the cost functions. C1 P1 600 15 P1 0.05 P1 2 2 Ctotal P1 P2 C1 P1 C2 P2 C2 P2 700 20 P2 0.04 P2 C1 P1 17748.76 C units are dollars/hour. C2 P2 23509.917 Ctotal P1 P2 41258.68
© Copyright 2024 ExpyDoc