piconet® stand-alone module for PROFIBUS-DP

piconet® stand-alone module for PROFIBUS-DP
4 analog inputs ±10 V
SDPB-40A-0005
■ 4 analogue inputs ±10 V
■ Configuration interface
■ Parametrizable functions
■ Supported via I/O-ASSISTANT 2
■ Direct connection to the fieldbus
■ Fibre-glass reinforced housing
■ Shock and vibration tested
■ Encapsulated module electronics
■ Metal connector
■ Degree of protection IP67
Fieldbus M12 x 1
SDPB-40A-0005
6824051
Number of channels
Operating / load voltage
Operating current
4
20…29 VDC
ð 140 mA
Fieldbus transmission rate
Fieldbus addressing
Service Interface
Electrical isolation
9.6 kbps … 12 Mbps
0 to 99
parameterisation via I/O-ASSISTANT
Fieldbus to operational voltage
Number of channels
Input resistance
Potential separation
4 analogue inputs ± 10 V
> 100 kò
channels to operational voltage
Common mode voltage
Measuring current
Conversion time
Relative measuring error
Input filter
Sensor supply
max. 35 V
0.5 mA
250 ms
< +- 0.3 % of full scale
variable
from load voltage
Dimensions (W x L x H)
Operating temperature
Storage temperature
Vibration test
Shock test
Electro-magnetic compatibility
Protection class
Approvals
30 x 175 x 26.5mm
0…+55 °C
-25 to 85 °C
as per EN 60068-2-6
acc. to DIN EN 60068-2-27
according to EN 61000-6-2/EN 61000-6-4
IP67
CE, cULus
Input M12 x 1
Connection - Inputs
Voltage Supply M8 x 1
Edition • 2016-05-14T20:24:11+02:00
Type code
Ident no.
1/2
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
piconet® stand-alone module for PROFIBUS-DP
4 analog inputs ±10 V
SDPB-40A-0005
Edition • 2016-05-14T20:24:11+02:00
Data in process image
2/2