Remote I/O System excom

Remote I/O System excom®
Input Module, Digital, 4-channel
DI40-N
The input module DI40-N is used for the
connection of NAMUR sensors (DIN EN
60947-5-6), 3-wire sensors (NPN, PNP) or
mechanical contacts.
■ Input modules for NAMUR and 3-wire
sensors (NPN and PNP)
The behaviour of the inputs can be adjusted
via the PROFIBUS-DP master. The following
parameters can be adjusted: switching behaviour, switch-on delay, default value, wirebreak and short circuit monitoring.
■ Power supply of the sensors out of the
module (max. 20 mA at 12 VDC)
■ Complete galvanic isolation
Edition • 2017-04-03T15:03:46+02:00
When wire-break or short-circuit monitoring
are activated, mechanical contacts can only
be connected with a corresponding resistor
circuitry (WM1, Ident no. 0912101).
The inputs are galvanically isolated from each
other.
1/2
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Remote I/O System excom®
Input Module, Digital, 4-channel
DI40-N
Type designation
Ident no.
DI40-N
6884213
Supply voltage
Power consumption
Galvanic isolation
Number of channels
via the backplanes, central power supply
ð2W
complete galvanic isolation
4-channel
Input circuits
No-load voltage
Short-circuit current
Switching threshold on/off
Switching frequency
Short-circuit
Wire-break
3-wire input
No-load voltage
Current
0-signal
1-signal
acc. to EN 60947-5-6 (NAMUR)
8.2 VDC
2.7 mA
type 1.8 / type 1.3 mA
ð 100 Hz
< 367 ò
< 0.15 mA
12 VDC
ð 20 mA
ð 4.5 V
ï 6.5 V
Indication
Operational readiness
State/ Fault
1 x green / red
4 x yellow / red
Housing material
Connection mode
Plastic
module, plugged on rack
Protection class
Ambient temperature
Relative humidity
Vibration test
Shock test
EMC
IP20
-20…+70 °C
ð 95 % at 55 °C acc. to EN 60068-2
acc. to IEC 60068-2-6
acc. to IEC 60068-2-27
acc. EN 61326-1 (2013)
acc. to Namur NE21 (2012)
111 acc. to SN 29500 (Ed. 99) 40 °C
18 x 118 x 103 mm
MTTF
Dimensions
The power supply for 3-wire sensors is also monitored for wire breaks and short circuits
Edition • 2017-04-03T15:03:46+02:00
Comments
Dimensions
2/2
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com