Model R-ELT is an automatic emergency light test timer. The unit is designed to facilitate
the testing procedures of emergency lighting systems. The R-ELT has selectable time
intervals to carry out both the functional test and a full load duration test.
When the R-ELT is idle, pressing the button on the front activates the timer.
Pressing and holding the button selects longer time intervals. The selected time interval
is indicated by the flash sequence of the LED.
Pressing and holding the button when the timer is active will abort the test and the timer
will return to its idle state.
Order code: R-ELT-230V
Specifications
Supply
: 220-240Vac ±10% 1.5VA idle, 3VA active
Time Ranges
: selectable 60, 90 and 120 minute
Other time ranges on request
Output
Single pole change over relay contacts
Contact rating
: AC1 (non-inductive) 2500VA, 10A 250Vac
: AC15 (inductive) 500VA, 2A 250Vac
Contact material
: AgNi for resistive to slightly inductive loads with inrush currents <25A
Temperature
Operating
Storage
Housing
DIN rail mounted grey polyamide, flame retardant UL 94 V0.
Terminals
Rising clamp, nickeled copper alloy clamp and tin plated copper alloy terminal
Suitable for 2.5mm2 conductor
EMC Approvals
: -10°C to +20°C to +50°C
: -20°C to +70°C
: AS/NZS 3548
: C-Tick Mark
Connections
Housing Dimensions
56.4
Supply
N L
R-ELT
90
98
17.5
External push button
NOTE!
Push button terminals live
NC C NO
Relay
CARREL ELECTRADE LTD
MANUFACTURERS, IMPORTERS AND DISTRIBUTORS OF ELECTRICAL ENGINEERING PRODUCTS
POSTAL ADDRESS: P O BOX 11078, ELLERSLIE 1542, AUCKLAND NEW ZEALAND
FACTORY AND OFFICE: 661 GREAT SOUTH ROAD, PENROSE 1061
TELEPHONE: +64-9-525 1753 FACSIMILE: +64-9-525 1756
CHRISTCHURCH BRANCH: 73B BRISBANE STREET, SYDENHAM
TELEPHONE: 03-366 1242 FACSIMILE: 03-379 1991
EMAIL: sales@ carrel-electrade.co.nz WEB: www.carrel-electrade.co.nz
25 February 2014
R-ELT EMERGENCY LIGHT TEST TIMER
WITH REMOTE OPERATE FACILITY
Button
LED
Relay
tOn hold
1 sec
tOff hold
1 sec
tOn hold
1 sec
tRelay T1
60 mins
Button
LED
Relay
tOn hold T2
2 sec
tRelay T2
90 mins
Button
LED
Relay
tOn hold T3
3 sec
tRelay T3
120 mins
Operation.
•
In the idle state the LED will briefly flash on, in an active state the LED will be on and briefly flash off.
•
To activate the R-ELT press and hold the button on the front of the unit for greater than 1 second. While the
button is held down to activate the timer and select the time period, the LED will flash at a faster rate.
•
The three different time periods are selected by holding the button down for different lengths of time, the time
period is signalled by the LED flash sequence.
•
Press and hold the button for 1 second to select 60 minutes.
- LED flashing briefly off once.
•
Press and hold the button for 2 seconds to select 90 minutes.
- LED flashing briefly off and on twice.
•
Press and hold the button for 3 seconds to select 120 minutes.
- LED flashing briefly off and on three times.
•
Pressing and holding the button for 1 second when the timer is active will abort the test and the timer will
return to its idle state.
CARREL ELECTRADE LTD
MANUFACTURERS, IMPORTERS AND DISTRIBUTORS OF ELECTRICAL ENGINEERING PRODUCTS
POSTAL ADDRESS: P O BOX 11078, ELLERSLIE 1542, AUCKLAND NEW ZEALAND
FACTORY AND OFFICE: 661 GREAT SOUTH ROAD, PENROSE 1061
TELEPHONE: +64-9-525 1753 FACSIMILE: +64-9-525 1756
CHRISTCHURCH BRANCH: 73B BRISBANE STREET, SYDENHAM
TELEPHONE: 03-366 1242 FACSIMILE: 03-379 1991
EMAIL: sales@ carrel-electrade.co.nz WEB: www.carrel-electrade.co.nz
25 February 2014