SSEG DETAILS SSEG Type reference: Manufacturer: Tel: Fax: Address: Type reference: Max AC Power: PHOTO-VOLTAIC GRID TIED INVERTER SolarEdge Technologies Ltd. +972-9-957-6620 +972-9-957-6591 6 HeHarash St. P.O.Box 7349, Neve Neeman, Hod Hasharon 45240, Israel SE2200, SE3000, SE3300, SE3500, SE4000-16A, SE4000, SE5000, SE6000 2200W, 3000W, 3300W, 3500W, 4000W, 5000W, 6000W TEST HOUSE DETAILS Name and address of test house Bureau Veritas Consumer Product Services GmbH Businesspark A96, 86842 Türkheim, Germany TEST DETAILS - - Power quality O Harmonic current emissions O Voltage fluctuations and flicker O DC injection O Power factor Under/over frequency tests Under/over voltage tests Loss of mains test Reconnection times SolarEdge Technologies | www.solaredge.com USA Germany Italy Japan Israel China Australia The Netherlands 3347 Gateway Boulevard, Fremont, CA, 94538 Werner-Eckert-Straße 6, Munich 81829 VISMUNDA SRL, Corso Del Popolo 50/A, Treviso B-9 Ariake Frontier Building, 3-7-26 Ariake, Koto-Ku, Tokyo 135-0063 6 HeHarash St. P.O.Box 7349, Neve Neeman, Hod Hasharon 45240 City Center, 100 Zunyi Road, Building A, Unit 1204, Shanghai 200051 c/- William Buck (NSW) Pty Ltd, Level 29, 66 Goulburn Street, Sydney 2000 Rietlandpark 125, Amsterdam, 1019 DT POWER QUALITY Harmonic 2nd 3rd 4th 5th 6th 7th 8th 9th 10th 11th 12th 13th THD Note Harmonics P/Pn=50% P/Pn=100% Test value Test value Test value Test value [A] [%] [A] [%] 0.04 0.15 0.06 0.23 0.15 0.58 0.26 1.00 0.01 0.04 0.01 0.04 0.04 0.15 0.17 0.65 0.01 0.04 0.01 0.04 0.11 0.42 0.06 0.23 0.01 0.04 0.01 0.04 0.07 0.27 0.06 0.23 0.01 0.04 0.01 0.04 0.03 0.12 0.05 0.19 0.01 0.04 0.02 0.08 0.03 0.12 0.03 0.12 0.08 0.08 Voltage Fluctuations and Flicker Starting Stopping Running 4% 4% Pst = 1.0 Plt = 0.65 0.60% 0.35% 0.125 0.250 * Maximum permissible voltage fluctuation (expressed as a percentage of nominal voltage at 100% power) and flicker. As per BS EN 61000-3-3. Limit Output power Test value phase 1 Limit Test level Test value Note 8 21.6 4 10.7 2.67 7.2 2 3.8 1.6 3.1 1.33 2 23 * Maximum permissible harmonic current As per BS EN 61000-3-2 Class A. Limit * Test value Note Limit* [%] DC Injection 0.25% of max output current 10% 55% 100% 0.03% 0.03% 0.09% Power factor 0.95 lag– 0.95 lead at three voltage levels 216.2 V (Un-6%) 230 V 0.99 0.99 253 V (Un+10%) 0.99 * The power factor test shall be such that the inverter supplies full load to the DNO system. SolarEdge Technologies | www.solaredge.com USA Germany Italy Japan Israel China Australia The Netherlands 3347 Gateway Boulevard, Fremont, CA, 94538 Werner-Eckert-Straße 6, Munich 81829 VISMUNDA SRL, Corso Del Popolo 50/A, Treviso B-9 Ariake Frontier Building, 3-7-26 Ariake, Koto-Ku, Tokyo 135-0063 6 HeHarash St. P.O.Box 7349, Neve Neeman, Hod Hasharon 45240 City Center, 100 Zunyi Road, Building A, Unit 1204, Shanghai 200051 c/- William Buck (NSW) Pty Ltd, Level 29, 66 Goulburn Street, Sydney 2000 Rietlandpark 125, Amsterdam, 1019 DT UNDER / OVER FREQUENCY TESTS Parameter Setting Trip value Parameter Setting Trip value Under Frequency Stage 1 Frequency Time 47.5 Hz 20.0 sec 47.5 Hz 20.495 sec Under Frequency Stage 2 Frequency Time 47.0 Hz 0.5 sec 47.0 Hz 0.982 sec Over Frequency Stage 1 Frequency Time 51.5 Hz 90.0 sec 51.5 Hz 90.19 sec Over Frequency Stage 2 Frequency Time 52.0 Hz 0.5 sec 52.0 Hz 0.979 sec UNDER / OVER VOLTAGE TESTS Parameter Setting Trip value Parameter Setting Trip value Under Voltage Stage 1 Voltage Time 200.1 V 2.5 sec 200.3 V 2.62 sec Under Voltage Stage 2 Voltage Time 184.0 V 0.5 sec 184.0 V 0.538 sec Over Voltage Stage 1 Voltage Time 262.2 V 1.0 sec 263.7 V 1.148 sec Over Voltage Stage 2 Voltage Time 273.7 V 0.5 sec 274.5 V 0.530 sec LOSS OF MAINS TEST according to BS EN 62116 Test power and 33% 66% 100% 33% imbalance -5%Q -5%Q -5%Q +5%Q [Test 22] [Test [Test 5] [Test 31] 12] Setting 0.5 sec 0.5 sec 0.5 sec 0.5 sec Trip value 103 msec 102 216 msec 152 msec msec 66% +5%Q [Test 21] 100% +5%Q [Test 10] 0.5 sec 296 msec 0.5 sec 384 msec SolarEdge Technologies | www.solaredge.com USA Germany Italy Japan Israel China Australia The Netherlands 3347 Gateway Boulevard, Fremont, CA, 94538 Werner-Eckert-Straße 6, Munich 81829 VISMUNDA SRL, Corso Del Popolo 50/A, Treviso B-9 Ariake Frontier Building, 3-7-26 Ariake, Koto-Ku, Tokyo 135-0063 6 HeHarash St. P.O.Box 7349, Neve Neeman, Hod Hasharon 45240 City Center, 100 Zunyi Road, Building A, Unit 1204, Shanghai 200051 c/- William Buck (NSW) Pty Ltd, Level 29, 66 Goulburn Street, Sydney 2000 Rietlandpark 125, Amsterdam, 1019 DT RECONNECTION TIMES Reconnection Time Time delay setting Measured delay Under/Over voltage 300 sec 330 sec Under/Over Frequency 300 sec 330 sec FAULT LEVEL CONTRIBUTION Time after fault 20 ms 100 ms 250 ms 500 ms Time to trip Voltage 77.4 V 77.7 V 76.2 V 75.3 V Current 26.2 A 26.2 A 26.1 A 26.0 A 0.508 sec Note * SE6000 test values provided SELF MONITORING – SOLID STATE SWITCHING There are no solid state switches in the units. Mechanical relays are provided. SolarEdge Technologies | www.solaredge.com USA Germany Italy Japan Israel China Australia The Netherlands 3347 Gateway Boulevard, Fremont, CA, 94538 Werner-Eckert-Straße 6, Munich 81829 VISMUNDA SRL, Corso Del Popolo 50/A, Treviso B-9 Ariake Frontier Building, 3-7-26 Ariake, Koto-Ku, Tokyo 135-0063 6 HeHarash St. P.O.Box 7349, Neve Neeman, Hod Hasharon 45240 City Center, 100 Zunyi Road, Building A, Unit 1204, Shanghai 200051 c/- William Buck (NSW) Pty Ltd, Level 29, 66 Goulburn Street, Sydney 2000 Rietlandpark 125, Amsterdam, 1019 DT
© Copyright 2024 ExpyDoc