IXIO-VIO Cross-talk PDF | 100 KB | 14.08.2014

ENGLISH
IXIO/VIO
Cross-talk can happen when sensors have overlapping
detection fields because they are installed close to each
other and therefore have difficulties distinguishing between
the energy they send. This could lead to false or unwanted
detections.
1
How to avoid cross-talk?
IXIO next to IXIO
All IXIO sensors have 2 frequency settings which can be set via LCD or remote control.
Choose a different frequency for sensors mounted next to or opposite to each other in order to avoid
cross-talk.
B
IXIO-DT
FREQ A
FREQ B
2
IXIO-ST
IXIO-DT
IXIO-ST
B
A
B
VIO next to VIO
When installing several VIO sensors, you have to activate the multi-mode to avoid cross-talk.
To do so, choose the following configuration:
- VIO-DT: select the presetting critical environment via DIP-switch 1 and 2.
- VIO-ST: select frequency B for all VIO sensor (DIP 2 to ON).
VIO-ST
VIO-DT
©BEA | Application Note | 42.8872 / V1 - 08.14
VIO-ST
3
VIO-DT
VIO-ST
VIO-ST
VIO-ST
VIO-ST
IXIO next to VIO
When combining both sensor types, the best configuration to avoid cross-talk is:
- IXIO on frequency A (inside) and B (outside)
- VIO-ST on frequency B (multi-mode)
B
IXIO-DT
FREQ A
FREQ B
VIO-ST
IXIO-DT
A