Type Test Report Fronius IG Plus 100 V-3

ENG
GINEERING RECOM
MMENDA
ATION G83/2
G
MATERIALS & SAF
FETY - R&D
APPEN
NDIX 4
page 1 of 8
TR 20234
TYPE
E VERIFIC
CATION TEST
T
REP
PORT
GENERATING PLANT
P
DETAILS
D
Type A
Approval and
d manufactturer/supplie
er declaration of compliance withh the requiirements off
Enginee
ering Recom
mmendation
n G83/2.
SSEG Type referencce number
Fronius IG
G Plus 100V--3
SSEG Type
High Freq
quency Trans
sformer
System S
Supplier nam
me
Fronius In
nternational GmbH
G
Address
Guenter Fronius
F
Str 1
4600 Wells-Thalheim, Austria
Tel
+43
3-7242-241-0
0
Fax
x
+43-7242--241-224
E:mail
pv@
@fronius.com
m
We
eb site
www.froniuus.com
Connection
C
Option
O
Maximum
m rated
capacityy, use separa
ate
sheet if m
more than on
ne
connection option.
8
kW single
e phase, single, split or thhree phase system
8
kW three phase
--
kW two ph
hases in thre
ee phase sysstem
--
kW two ph
hases split phase system
m
SSEG m
manufacturer//supplier dec
claration.
I certify on behalf off the company named a
above as a manufacturer
m
r/supplier of Small Scale
e Embedded
d
Generato
ors, that all products manufacture
m
ed/supplied by
b the company with tthe above SSEG
S
Type
e
reference number will
w be manuffactured and
d tested to ensure
e
that they
t
perform
m as stated in this Type
e
Verification Test Rep
port, prior to shipment to site and thatt no site mod
difications aree required to
o ensure thatt
the product meets all the requirements of G8 3/2.
Signed
On behalff of
Fronius Innternational GmbH
G
Note tha
at testing can
n be done by
y the manufa
acturer of an individual co
omponent, byy an externa
al test house,,
or by the
e supplier of the complete
e system, or any combina
ation of them
m as approprriate.
Where p
parts of the te
esting are ca
arried out by persons or organisations
o
s other than tthe supplier then the
supplier shall keep copies
c
of all test records a
and results supplied
s
to th
hem to verifyy that the testting has
been carrried out by people
p
with sufficient
s
tech
hnical compe
etency to carrry out the teests.
Type Veriification Test Report
R
for Fron
nius IG Plus 1
100V-3_TR202
234_G83-2.do
ocx
Bacckup: Fronius IG Plus V UK
K
ENGINEERING RECOMMENDATION G83/2
MATERIALS & SAFETY - R&D
page 2 of 8
TR 20234
Power Quality. Harmonics. The requirement is specified in section 5.4.1, test procedure in
Annex A or B 1.4.1
2,66
SSEG rating per phase (rpp)
Harmonic
At 45-55% of rated output
Measured
Value (MV)
in Amps
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Normalised
Value
(NV) in
Amps
kW
NV=MV*3.68/rpp
100% of rated output
Measured
Value (MV)
in Amps
Normalised
Value
(NV) in Amps
0,038
0,052
0,021
0,029
0,164
0,226
0,087
0,120
0,015
0,021
0,018
0,025
0,078
0,107
0,037
0,051
0,011
0,015
0,011
0,015
0,051
0,070
0,014
0,019
0,008
0,011
0,008
0,011
0,024
0,033
0,022
0,031
0,007
0,010
0,007
0,009
0,009
0,013
0,028
0,038
0,007
0,010
0,006
0,008
0,010
0,013
0,026
0,035
0,007
0,010
0,006
0,009
0,011
0,015
0,023
0,032
0,008
0,011
0,006
0,009
0,038
0,052
0,021
0,029
0,164
0,226
0,087
0,120
0,015
0,021
0,018
0,025
0,078
0,107
0,037
0,051
0,011
0,015
0,011
0,015
Type Verification Test Report for Fronius IG Plus 100V-3_TR20234_G83-2.docx
Limit in
BS EN
610003-2 in
Amps
Higher limit for
odd harmonics
21 and above
1.080
2.300
0.430
1.140
0.300
0.770
0.230
0.400
0.184
0.330
0.153
0.210
0.131
0.150
0.115
0.132
0.102
0.118
0.092
0.107
0.160
Backup: Fronius IG Plus V UK
ENGINEERING RECOMMENDATION G83/2
MATERIALS & SAFETY - R&D
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
page 3 of 8
TR 20234
0,014
0,019
0,021
0,029
0,013
0,017
0,013
0,018
0,013
0,018
0,025
0,034
0,012
0,017
0,019
0,026
0,010
0,014
0,020
0,027
0,008
0,011
0,009
0,012
0,007
0,010
0,014
0,019
0,007
0,009
0,003
0,004
0,006
0,009
0,012
0,016
0,007
0,009
0,003
0,004
0,006
0,009
0,010
0,014
0,006
0,009
0,003
0,003
0,006
0,009
0,009
0,013
0,006
0,009
0,002
0,003
0,007
0,010
0,007
0,010
0,007
0,009
0,002
0,003
0,008
0,012
0,007
0,009
0,006
0,009
0,002
0,003
0.084
0.098
0.147
0.077
0.090
0.135
0.071
0.083
0.124
0.066
0.078
0.117
0.061
0.073
0.109
0.058
0.068
0.102
0.054
0.064
0.096
0.051
0.061
0.091
0.048
0.058
0.087
40
0.046
0,009
0,013
0,006
0,009
Note the higher limits for odd harmonics 21 and above are only allowable under certain conditions, if
these higher limits are utilised please state the exemption used as detailed in part 6.2.3.4 of BS EN
61000-3-2 in the box below.
Type Verification Test Report for Fronius IG Plus 100V-3_TR20234_G83-2.docx
Backup: Fronius IG Plus V UK
ENGINEERING RECOMMENDATION G83/2
MATERIALS & SAFETY - R&D
page 4 of 8
TR 20234
Power Quality. Voltage fluctuations and Flicker. The requirement is specified in section
5.4.2, test procedure in Annex A or B 1.4.3
Starting
Stopping
Running
d
d
max
d
c
d
(t)
d
max
d
c
P
(t)
P 2 hours
st
lt
-
-
-
-
-
-
-
-
Normalised
to standard
impedance
and 3.68kW
for multiple
units
0,320
0,021
0,420
0,293
0,017
0,000
0,226
0,222
Normalised
to required
maximum
impedance
-
-
-
-
-
-
-
-
Measured
Values
Limits set
under BS EN
61000-3-11
4%
3.3%
Test
Impedance
Standard
Impedance
Maximum
Impedance
3.3%
4%
3.3%
3.3%
1.0
0.65
-
-
-
-
-
-
R
0.24
Ω
XI
0.15
Ω
Ω
XI
R
Test start
Ω
Test end
Fronius R&D Laboratories, Fronius International GmbH,
Guenter Fronius Str 1, A-4600 Wels-Thalheim, Austria
Test location
Power quality. DC injection. The requirement is specified in section 5.5, test procedure in
Annex A or B 1.4.4
Test power
level
10%
55%
100%
Recorded
value
±20mA
±20mA
±20mA
as % of
rated AC
current
0,06%
0,06%
0,06%
Limit
0.25%
0.25%
0.25%
Power quality. Power factor. The requirement is specified in section 5.6, test procedure in
Annex A or B 1.4.2
216.2V
Measured
value
Limit
0,99
>0.95
230V
0,99
>0.95
253V
0,99
Measured at three voltage levels and at full
output. Voltage to be maintained within ±1.5%
of the stated level during the test.
>0.95
Type Verification Test Report for Fronius IG Plus 100V-3_TR20234_G83-2.docx
Backup: Fronius IG Plus V UK
ENGINEERING RECOMMENDATION G83/2
MATERIALS & SAFETY - R&D
page 5 of 8
TR 20234
Protection. Frequency tests The requirement is specified in section 5.3.1, test procedure in
Annex A or B 1.3.3
Function
Setting
Frequency
Trip test
U/F stage 1
47.5Hz
Time
delay
20s
U/F stage 2
47Hz
0.5s
O/F stage 1
51.5Hz
90s
O/F stage 2
52Hz
0.5s
Frequency
“No trip tests”
Time
delay
47.46Hz
20,06s
46,98Hz
0,549s
51,59Hz
90,3s
52,02Hz
0,551s
Frequency
/time
47.7Hz
25s
47.2Hz
19.98s
46.8Hz
0.48s
51.3Hz
95s
51.8Hz
89.98s
52.2Hz
0.48s
Confirm no trip
no trip occurred
no trip occurred
no trip occurred
no trip occurred
no trip occurred
no trip occurred
Protection. Voltage tests The requirement is specified in section 5.3.1, test procedure in
Annex A or B 1.3.2
Function
Setting
Voltage
Trip test
Time
delay
2.5s
Voltage
“No trip tests”
Time
delay
Voltage
Confirm no trip
/time
U/V stage 1
200.1V
204.1V
200,2V
no trip occurred
2,554s 3.5s
U/V stage 2
184V
0.5s
188V
no trip occurred
184,2V
0,553s 2.48s
180V
no trip occurred
0.48s
O/V stage 1
262.2V
1.0s
258.2V
no trip occurred
262,6V
1,04s
2.0s
O/V stage 2
273.7V
0.5s
269.7V
no trip occurred
274,75V
0,559s 0.98s
277.7V
no trip occurred
0.48s
Note for Voltage tests the Voltage required to trip is the setting ±3.45V. The time delay can be measured
at a larger deviation than the minimum required to operate the protection. The No trip tests need to be
carried out at the setting ±4V and for the relevant times as shown in the table above to ensure that the
protection will not trip in error.
Type Verification Test Report for Fronius IG Plus 100V-3_TR20234_G83-2.docx
Backup: Fronius IG Plus V UK
ENGINEERING RECOMMENDATION G83/2
MATERIALS & SAFETY - R&D
page 6 of 8
TR 20234
Protection. Loss of Mains test. The requirement is specified in section 5.3.2, test procedure in
Annex A or B 1.3.4
To be carried out at three output power levels with a tolerance of plus or minus 5% in Test
Power levels.
Test Power
Balancing load on
islanded network
Trip time. Limit is
0.5 seconds
10%
95% of
SSEG
output
--
55%
95% of
SSEG
output
--
100%
95% of
SSEG
output
--
10%
105% of
SSEG
output
--
55%
105% of
SSEG
output
--
100%
105% of
SSEG
output
--
For Multi phase SSEGs confirm that the device shuts down correctly after the removal of a
single fuse as well as operation of all phases.
Test Power
Balancing load on
islanded network
Trip time. Ph1
fuse removed
Test Power
Balancing load on
islanded network
Trip time. Ph2
fuse removed
Test Power
Balancing load on
islanded network
Trip time. Ph3
fuse removed
10%
95% of
SSEG
output
--
55%
95% of
SSEG
output
--
100%
95% of
SSEG
output
--
10%
105% of
SSEG
output
--
55%
105% of
SSEG
output
--
100%
105% of
SSEG
output
--
10%
95% of
SSEG
output
--
55%
95% of
SSEG
output
--
100%
95% of
SSEG
output
--
10%
105% of
SSEG
output
--
55%
105% of
SSEG
output
--
100%
105% of
SSEG
output
--
10%
95% of
SSEG
output
--
55%
95% of
SSEG
output
--
100%
95% of
SSEG
output
--
10%
105% of
SSEG
output
--
55%
105% of
SSEG
output
--
100%
105% of
SSEG
output
--
Note for technologies which have a substantial shut down time this can be added to the 0.5
seconds in establishing that the trip occurred in less than 0.5s. Maximum shut down time could
therefore be up to 1.0 seconds for these technologies.
-Indicate additional shut down time included in above results.
Note as an alternative, inverters can be tested to BS EN 62116. The following sub set of tests
should be recorded in the following table.
Test Power and
imbalance
Trip Time. Limit is
0.5s
33%
-5% Q
Test 22
155ms
66%
-5% Q
Test 12
99ms
100%
-5% P
Test 5
213ms
33%
+5% Q
Test 31
180ms
Type Verification Test Report for Fronius IG Plus 100V-3_TR20234_G83-2.docx
66%
+5% Q
Test 21
113ms
100%
+5% P
Test 10
300ms
Backup: Fronius IG Plus V UK
ENGINEERING RECOMMENDATION G83/2
MATERIALS & SAFETY - R&D
page 7 of 8
TR 20234
Protection. Frequency change, Stability test The requirement is specified in section 5.3.3,
test procedure in Annex A or B 1.3.6
Change
Positive Vector Shift
Start
Frequency
49.5Hz
End
Frequency
Negative Vector Shift
50.5Hz
-9 degrees
Positive Frequency drift
49.5Hz
+0.19Hz/sec
51.5Hz
Negative Frequency drift
50.5Hz
-0.19Hz/sec
47.5Hz
Confirm no trip
+9 degrees
no trip occurred
no trip occurred
no trip occurred
no trip occurred
Protection. Re-connection timer. The requirement is specified in section 5.3.4, test procedure
in Annex A or B 1.3.5
Test should prove that the reconnection sequence starts after a minimum delay of 20 seconds
for restoration of voltage and frequency to within the stage 1 settings of table 1.
Time delay
setting
Measured
delay
Checks on no reconnection when voltage or frequency is
brought to just outside stage 1 limits of table 1.
At 266.2V
At 196.1V
At 47.4Hz
At 51.6Hz
No reNo reNo reNo reconnect
connect
connect
connect
occurred
occurred
occurred
occurred
20s
25s
Confirmation that the SSEG does
not re-connect.
Fault level contribution. The requirement is specified in section 5.7, test procedure in Annex A
or B 1.4.6
For a directly coupled SSEG
Parameter
i
--
For a Inverter SSEG
Time
Volts
after fault
20ms
0.5V
Initial Value of aperiodic
current
A
--
100ms
Initial symmetrical shortcircuit current*
I
--
250ms
--
500ms
Symbol
Peak Short Circuit current
Value
p
k
Decaying (aperiodic)
component of short circuit
current*
i
Reactance/Resistance Ratio
of source*
X
DC
/
R
--
Time to
trip
Type Verification Test Report for Fronius IG Plus 100V-3_TR20234_G83-2.docx
Amps
185A
1.3V
47.4A
1.37V
26.6A
1.41V
19.6A
2.32ms
In milliseconds
Backup: Fronius IG Plus V UK
ENGINEERING RECOMMENDATION G83/2
MATERIALS & SAFETY - R&D
page 8 of 8
TR 20234
Self-Monitoring solid state switching The requirement is specified in
section 5.3.1, No specified test requirements.
It has been verified that in the event of the solid state switching device
failing to disconnect the SSEG, the voltage on the output side of the
switching device is reduced to a value below 50 volts within 0.5 seconds.
Yes/or NA
NA
(because electromechanical relays
are used)
Additional comments
Type Verification Test Report for Fronius IG Plus 100V-3_TR20234_G83-2.docx
Backup: Fronius IG Plus V UK