Release Date: 2014-04-15 Version

Version: V2.0.8
Release Date: 2014-04-15
Copyright 2014, Builder: 2.3.0.0, Time: 08:36:01
LMT
Vendor ID
Vendor Name
Vendor Text
Vendor URL
Device ID
310 d / 01 36 h
ifm electronic gmbh
www.ifm.com
http://http://www.ifm.com/ifmgb/web/io-link-download.htm
370 d / 00 01 72 h
Communication
IO-Link Revision
Bitrate
Minimum Cycle Time
SIO Mode Supported
V1.1
COM2
2.300 ms
Yes
Features
Block parametrization
Data storage
Yes
Yes
Device Variant
LMT102
Electronic level sensor, 0...100 %, Length 38 mm
LMT104
Electronic level sensor, 0...100 %, Length 153 mm
LMT105
Electronic level sensor, 0...100 %, Length 253 mm
LMT202
Electronic level sensor, 0...100 %, Length 28 mm
LMT302
Electronic level sensor, 0...100 %, Length 38 mm
LMC502
Electronic level sensor, 0...100 %, Length 31.6 mm, Process connection 1/2'' NPT
Page 1
Process Data
(Process Data Input)
Total BitLength = 16
Name
Description
Datatype
Bitoffset
Bitlength
Value Range
Gradient Offset Unit
Level
Current level
UIntegerT
2
14
0 to 100
1
Switchstate [OUT2].
State depends on [OU2]
BooleanT
1
0
%
(false) inactive
(true) active
Switchstate [OUT1].
State depends on [OU1]
BooleanT
0
(false) inactive
(true) active
Page 2
Variables
Name
Standard Command
Description
Index
Subindex DataType
bitOffset
2
Sub 0
UIntegerT
Length
Access Default
Rights
8 Bit
wo
Value Range
Gradient Offset Unit
(130) Restore Factory
Setting
(240) IO-Link 1.1
system test command
240, Event 8DFE will
appear
(241) IO-Link 1.1
system test command
241, Event 8DFE will
disappear
(242) IO-Link 1.1
system test command
242, Event 8DFF will
appear
(243) IO-Link 1.1
system test command
243, Event 8DFF will
disappear
(255) Command
without effect, for
internal use only
Device Access Lock
12
Data Storage Lock
Sub 0
RecordT
16 Bit
bitOffs 1
BooleanT
1 Bit
rw
(0)
Vendor Name
16
Sub 0
ro
ifm electronic
gmbh
Vendor Text
17
Sub 0
ro
www.ifm.com
Product Name
18
Sub 0
ro
Product ID
19
Sub 0
ro
Product Text
20
Sub 0
ro
Electronic level
Page 3
Variables
Name
Description
Index
Subindex DataType
bitOffset
Length
Access Default
Rights
Value Range
Gradient Offset Unit
sensor
Serial Number
21
Sub 0
ro
Hardware Version
22
Sub 0
ro
Firmware Version
23
Sub 0
ro
Application Specific
Tag
24
Sub 0
Switch point 1, [SP1] shall be 67
greater than [rP1]. Please
consider to the current [rP1]
value. If the [SP1] will be set
below [rP1] it will be refused.
Sub 0
Sub 0
SP1
16 Byte
rw
IntegerT
16 Bit
rw
62
4 to 98
1
0
%
IntegerT
16 Bit
rw
54
2 to 96
1
0
%
The smaller the percentage of
water within the medium, the
smaller SP/rP shall be set.
rP1
Reset point 1, [rP1] shall be 68
smaller than [SP1]. Please
consider to the actual [SP1]
value. If the [rP1] will be set
above [SP1] it will be refused.
Page 4
Variables
Name
Description
Index
OU1
Output configuration [OUT 1] 69
Subindex DataType
bitOffset
Sub 0
UIntegerT
Length
Access Default
Rights
8 Bit
rw
Value Range
Gradient Offset Unit
(3) Hno / Hysteresis
fct normally open
(3) Hno / Hysteresis
fct normally open
(4) Hnc / Hysteresis
fct normally closed
(5) Fno / Window fct
normally open
(6) Fnc / Window fct
normally closed
(8) tch / Teach input
SP2
Switch point 2, [SP2] shall be 70
greater than [rP2]. Please
consider to the current [rP2]
value. If the [SP2] will be set
below [rP2] it will be refused.
Sub 0
IntegerT
16 Bit
rw
62
4 to 98
1
0
%
Sub 0
IntegerT
16 Bit
rw
54
2 to 96
1
0
%
The smaller the percentage of
water within the medium, the
smaller SP/rP shall be set.
rP2
Reset point 2, [rP2] shall be 71
smaller than [SP2]. Please
consider to the actual [SP2]
value. If the [rP2] will be set
above [SP2] it will be refused.
Page 5
Variables
Name
Description
Index
OU2
Output configuration [OUT 2] 72
Subindex DataType
bitOffset
Sub 0
UIntegerT
Length
Access Default
Rights
8 Bit
rw
Value Range
Gradient Offset Unit
(4) Hnc / Hysteresis
fct normally closed
(3) Hno / Hysteresis
fct normally open
(4) Hnc / Hysteresis
fct normally closed
(5) Fno / Window fct
normally open
(6) Fnc / Window fct
normally closed
FOU1
[OUT 1] behaviour in case of 77
fault
Sub 0
UIntegerT
8 Bit
rw
(4) OFF
(4) OFF
(2) On
dS1
Switch-On delay [OUT 1]
78
Sub 0
UIntegerT
16 Bit
rw
0
0 to 100
0.1
0
s
dr1
Switch-OFF delay [OUT 1]
79
Sub 0
UIntegerT
16 Bit
rw
0
0 to 100
0.1
0
s
FOU2
[OUT 2] behaviour in case of 80
fault
Sub 0
UIntegerT
8 Bit
rw
(4) OFF
(4) OFF
(2) On
dS2
Switch-On delay [OUT 2]
81
Sub 0
UIntegerT
16 Bit
rw
0
0 to 100
0.1
0
s
dr2
Switch-OFF delay [OUT 2]
82
Sub 0
UIntegerT
16 Bit
rw
0
0 to 100
0.1
0
s
P-n
Output polarity for the
switching outputs
85
Sub 0
UIntegerT
8 Bit
rw
(0) PnP
(0) PnP
(1) nPn
Page 6
Variables
Name
Description
Index
Subindex DataType
bitOffset
Length
Access Default
Rights
Value Range
Gradient Offset Unit
dFo
Delay time of outputs after
fault
86
Sub 0
UIntegerT
16 Bit
rw
0 to 50
0.1
Commands
Performs action on the sensor 241
Sub 0
UIntegerT
8 Bit
wo
0
0
s
(253) [rES] Reset to
factory settings
(1) [tSP1] Teach
Switchpoint 1 is only
available if [OU1] =
Hno, Hnc
(2) [tSP2] Teach
Switchpoint 2 is only
available if [OU2] =
Hno, Hnc
Events
Code
Name
Type
Description
20480 d / 50 00 h
Device hardware fault
Error
Device Exchange
25376 d / 63 20 h
Parameter error
Error
Check data sheet and values
30480 d / 77 10 h
Short circuit
Error
Check installation
36032 d / 8C C0 h
Signal fault
Error
Please check your application
36350 d / 8D FE h
Test Event 1
Warning
Event appears by setting index 2 to value 240, Event disappears by setting index 2 to value 241
36351 d / 8D FF h
Test Event 2
Warning
Event appears by setting index 2 to value 242, Event disappears by setting index 2 to value 243
Page 7
Error Types
ErrorCode
Name
Description
32768 d / 80 00 h
Device application error - no
details
Service has been refused by the device application and no detailed information of the incident is available
32785 d / 80 11 h
Index not available
Access occurs to a not existing index
32786 d / 80 12 h
Subindex not available
Access occurs to a not existing subindex
32800 d / 80 20 h
Service temporarily not available Parameter is not accessible due to the current state of the device application
32803 d / 80 23 h
Access denied
Write access on a read-only parameter
32816 d / 80 30 h
Parameter value out of range
Written parameter value is outside its permitted value range
32819 d / 80 33 h
Parameter length overrun
Written parameter length is above its predefined length
32820 d / 80 34 h
Parameter length underrun
Written parameter length is below its predefined length
32821 d / 80 35 h
Function not available
Written command is not supported by the device application
32822 d / 80 36 h
Function temporarily unavailable Written command is not available due to the current state of the device application
32832 d / 80 40 h
Invalid parameter set
Written single parameter collides with other actual parameter settings
32833 d / 80 41 h
Inconsistent parameter set
Parameter inconsistencies were found at the end of block parameter transfer, device plausibility check failed
32898 d / 80 82 h
Application not ready
Read or write service is refused due to a temporarily unavailable application
33025 d / 81 01 h
Parameter hidden
33026 d / 81 02 h
Parameter currently not available
Page 8