SHT-C-M-5000 Rev1 - Edge Hill University

ISO A0 841mm x 1189mm
PROJECT
Approved: SJB
STUDENT
RESIDENCES
Checked: ADT
PHASE 10
CLIENT
Designer: AC
ROOF VOID
FROM L TO R:
35Ø MCWS , 20Ø HTG F&R, 35Ø DHWS F
AND 22Ø DHWS R TO SECOND FLOOR
APARTMENTS
ROOF VOID
FROM L TO R:
35Ø MCWS, 20Ø HTG F&R, 35Ø DHWS F AND 22Ø
DHWS R TO SECOND FLOOR APARTMENTS
Project Management Initials:
FROM L TO R:
35Ø MCWS, 35Ø DHWS F, 22Ø DHWS R
AND 20Ø HTG F&R TO SECOND FLOOR
APARTMENTS
35Ø MCWS
CONSULTANT
HOT WATER CIRCULATING
PUMP
EXPANSION
VESSEL
SV
EXPANSION
VESSEL
THERMOSTATIC VALVE ON
RETURN
AAV
CONSTANT FLOW BYPASS VALVE
(10% OF BLOCK FLOW RATE)
THERMOSTATIC VALVE ON
RETURN
AECOM
1 New York Street
MANCHESTER, M1 4HD
+44 (0) 161 601 1700 tel
+44 (0) 161 601 1799 fax
www.aecom.com
SV
SV
AAV
CONSTANT FLOW BYPASS VALVE
(10% OF BLOCK FLOW RATE)
EDGEHILL
UNIVERSITY
42Ø MCWS
EXPANSION
VESSEL
CHECK VALVE
NOTES
35Ø MCWS
42Ø MCWS
FLUSHING
BYPASS
HTG
MAINS
20Ø HTG F&R
H C
42Ø MCWS
CHECK VALVE
54Ø MCWS
40Ø HTG F&R
HTG TO BLOCK
32Ø HTG F&R
FLUSHING
BYPASS (NC)
H C
HTG
MAINS
H C
40Ø HTG F&R
HEATING AND HOT WATER PLATE HEAT
EXCHANGER TO SERVE BEDROOMS, STAIRWELL
AND KITCHEN
20Ø HTG F&R
HTG
MAINS
20Ø HTG F&R
28Ø CONDENSATE EXTEND INTO LOCAL
POD PLANT CUPBOARD AND CONNECT
TO WASTE STACK WITH TUNDISH AND
TRAP ARRANGEMENT REFER TO DETAIL
'B'
HTG TO BLOCK
HTG TO BLOCK
HEATING AND HOT WATER PLATE HEAT
EXCHANGER TO SERVE BEDROOMS, STAIRWELL
AND KITCHEN
1.
THIS DRAWING IS TO BE READ IN
CONJUNCTION WITH ALL OTHER DRAWINGS,
SPECIFICATIONS AND SCHEDULES.
2.
SERVICES REQUIRING MAINTENANCE OR
ACCESS FOR COMMISSIONING PURPOSES TO
BE KEPT WITHIN ACCESSIBLE AREAS.
3.
FIRE COLLARS SHALL BE FITTED ON ALL
PIPEWORK PENETRATIONS THROUGH
FLOORS AND FIRE COMPARTMENT WALLS.
ALL PENETRATIONS THROUGH FLOORS AND
FIRE COMPARTMENT WALLS SHALL BE FIRE
STOPPED IN LINE WITH THE ARCHITECT'S
FIRE COMPARTMENTATION DRAWINGS.
4.
DRAIN COCKS SHALL BE FITTED AT LOW
POINTS AND AIR VENTS SHALL BE FITTED AT
HIGH POINTS.
5.
PIPEWORK SHALL BE INSULATED AS DEFINED
IN THE MECHANICAL SPECIFICATION
DOCUMENT.
6.
THE CONTRACTOR SHALL LIAISE WITH A
THERMAL EXPANSION SPECIALIST AND MAKE
A SUITABLE ALLOWANCE FOR THE
ACCOMMODATION OF EXPANSION WITHIN ALL
PIPEWORK SYSTEMS BASED UPON THEIR
FINAL DESIGN.
7.
THERMOSTATIC BALANCING VALVES TO BE
FITTED ON EACH MAIN RETURN HWS BRANCH
PIPEWORK FOR COMMISSIONING AND
THERMAL DISINFECTION CONTROL.
STR
28Ø CONDENSATE EXTEND INTO LOCAL
POD PLANT CUPBOARD AND CONNECT
TO WASTE STACK WITH TUNDISH AND
TRAP ARRANGEMENT REFER TO DETAIL
'B'
STR
STR
QUICKFILL
CONNECTION
FLUSHING
BYPASS (NC)
QUICKFILL
CONNECTION
SECOND FLOOR
FROM L TO R:
35Ø MCWS , 20Ø HTG F&R, 35Ø DHWS F
AND 22Ø DHWS R TO SECOND FLOOR
APARTMENTS
FROM L TO R:
35Ø MCWS, 35Ø DHWS F, 22Ø DHWS R AND 20Ø HTG F&R
TO FIRST FLOOR APARTMENTS
SECOND FLOOR
FROM L TO R:
35Ø MCWS, 20Ø HTG F&R, 35Ø DHWS F AND 22Ø
DHWS R TO SECOND FLOOR APARTMENTS
HOT WATER CIRCULATING
PUMP
EXPANSION
VESSEL
SV
HOT WATER CIRCULATING
PUMP
EXPANSION
VESSEL
SV
THERMOSTATIC VALVE ON
RETURN
SV
THERMOSTATIC VALVE ON
RETURN
EXPANSION
VESSEL
FROM R TO L:
35Ø MCWS
35Ø DHWS F
22Ø DHWS R
67Ø MCWS
FLUSHING
BYPASS
35Ø MCWS
FROM R TO L:
35Ø MCWS
35Ø DHWS F
22Ø DHWS R
HTG
MAINS
H C
CHECK VALVE
20Ø HTG F&R
20Ø HTG F&R
50Ø HTG F&R
65Ø HTG F&R
HEATING AND HOT WATER PLATE HEAT
EXCHANGER TO SERVE BEDROOMS, STAIRWELL
AND KITCHEN
54Ø MCWS
HTG TO BLOCK
42Ø MCWS
HTG
MAINS
32Ø HTG F&R
FLUSHING
BYPASS (NC)
H C
HTG
MAINS
H C
20Ø HTG F&R
28Ø CONDENSATE EXTEND INTO LOCAL
POD PLANT CUPBOARD AND CONNECT
TO WASTE STACK WITH TUNDISH AND
TRAP ARRANGEMENT REFER TO DETAIL
'B'
HTG TO BLOCK
HTG TO BLOCK
CHECK VALVE
HEATING AND HOT WATER PLATE HEAT
EXCHANGER TO SERVE BEDROOMS, STAIRWELL
AND KITCHEN
STR
28Ø CONDENSATE EXTEND INTO LOCAL
POD PLANT CUPBOARD AND CONNECT
TO WASTE STACK WITH TUNDISH AND
TRAP ARRANGEMENT REFER TO DETAIL
'B'
STR
STR
FLUSHING
BYPASS (NC)
QUICKFILL
CONNECTION
FLUSHING
BYPASS (NC)
QUICKFILL
CONNECTION
FIRST FLOOR
FROM L TO R:
35Ø MCWS , 20Ø HTG F&R, 35Ø DHWS F
AND 22Ø DHWS R TO SECOND FLOOR
APARTMENTS
FROM L TO R:
35Ø MCWS, 35Ø DHWS F, 22Ø DHWS R AND 20Ø HTG F&R
TO GROUND FLOOR APARTMENTS
FIRST FLOOR
FROM L TO R:
35Ø MCWS, 20Ø HTG F&R, 35Ø DHWS F AND 22Ø
DHWS R TO SECOND FLOOR APARTMENTS
HOT WATER CIRCULATING
PUMP
EXPANSION
VESSEL
SV
HOT WATER CIRCULATING
PUMP
EXPANSION
VESSEL
SV
THERMOSTATIC VALVE ON
RETURN
SV
THERMOSTATIC VALVE ON
RETURN
EXPANSION
VESSEL
FROM R TO L:
35Ø MCWS
35Ø DHWS F
22Ø DHWS R
FLUSHING
BYPASS
42Ø MCWS
HTG
MAINS
H C
HTG
MAINS
CHECK VALVE
32Ø HTG F&R
20Ø HTG F&R
28Ø CONDENSATE EXTEND INTO LOCAL
POD PLANT CUPBOARD AND CONNECT
TO WASTE STACK WITH TUNDISH AND
TRAP ARRANGEMENT REFER TO DETAIL
'B'
FROM R TO L:
35Ø MCWS
35Ø DHWS F
22Ø DHWS R
HEATING AND HOT WATER PLATE HEAT
EXCHANGER TO SERVE BEDROOMS, STAIRWELL
AND KITCHEN
HTG TO BLOCK
FLUSHING
BYPASS (NC)
H C
HTG
MAINS
H C
20Ø HTG F&R
28Ø CONDENSATE EXTEND INTO LOCAL
POD PLANT CUPBOARD AND CONNECT
TO WASTE STACK WITH TUNDISH AND
TRAP ARRANGEMENT REFER TO DETAIL
'B'
HTG TO BLOCK
HTG TO BLOCK
CHECK VALVE
HEATING AND HOT WATER PLATE HEAT
EXCHANGER TO SERVE BEDROOMS, STAIRWELL
AND KITCHEN
STR
20Ø HTG F&R
67Ø MCWS
67Ø MCWS
Last saved by: CHILDSA(2014-12-12) Last Plotted: 2014-12-15
Filename: F:\PROJECTS\BUILDING ENGINEERING - EHU RESIDENCES PHASE 8\PHASE 10\MECHANICAL PLANS\SHT-C-000-M-5000.DWG
50Ø HTG F&R
Printed on ___% Post-Consumer
Recycled Content Paper
STR
STR
65Ø HTG F&R
T
T
T
FLUSHING
BYPASS (NC)
QUICKFILL
CONNECTION
ENERGY METER WITH PULSED OUTLET
TO BMS AND ND METER
ACCESS PANELS REQUIRED WITHIN GROUND
FLOOR RISER CUPBOARD TO ALLOW ACCESS
TO METERS AND VALVES.
EM
IV
QUICKFILL
CONNECTION
DC
IV
IV
DC
FROM T TO B:
- SLEEVED 65Ø (ID) PREINSULATED
HTG F&R (200Ø CASING)
- 90Ø MDPE MCWS
IV
IV
STR
DCV
DC
DRV/OP
ISSUE/REVISION
WATER METER WITH PULSED OUTPUT
TO BMS AND ND METER
WM
STR
DC
ACCESS PANELS REQUIRED WITHIN GROUND
FLOOR RISER CUPBOARD TO ALLOW ACCESS
TO METERS AND VALVES.
EM
WATER METER WITH PULSED OUTPUT
TO BMS AND ND METER
WM
FLUSHING
BYPASS (NC)
QUICKFILL
CONNECTION
ENERGY METER WITH PULSED OUTLET
TO BMS AND ND METER
T
DC
DCV
DC
PREINSULATED MDPE PIPEWORK
TRANSFORM TO COPPER (MCWS)
AND STEEL (HTG)
DRV/OP
IV
GROUND FLOOR
FROM T TO B:
- SLEEVED 75Ø (ID) PREINSULATED
HTG F&R (200Ø CASING)
- 90Ø MDPE MCWS
REFER TO EXTERNALS DRAWING
60287786-SHT-S-U-9000
TYPICAL SINGLE HEATING RISER IN STAIRWELLS. PHASE 10 - 2 No RISERS
NTS
PREINSULATED MDPE PIPEWORK
TRANSFORM TO COPPER (MCWS)
AND STEEL (HTG)
GROUND FLOOR
1
DEC 2014
TENDER ISSUE
I/R
DATE
DESCRIPTION
KEY PLAN
REFER TO EXTERNALS DRAWING
60287786-SHT-S-U-9000
TYPICAL DOUBLE HEATING RISER IN STAIRWELLS. PHASE 10 - 2No RISERS
NTS
PROJECT NUMBER
60321010
SHEET TITLE
HEATING AND DOMESTIC
WATER SERVICES
TYPICAL SCHEMATIC
SHEET NUMBER
C-M-5000