+ Info about IGA TEST COMPACT M

Permanent overvoltage protection
IGA TEST COMPACT
Series
Conductores
de bajada
Compact single-phase protector against
Manguitos
transient and temporary overvoltage with MCB integrated
> Data sheet:
IGA TEST COMPACT M
The protector is formed by a protective coil, that includes
a surge protector, together with a main circuit breaker
(MCB).
Description:
IGA TEST COMPACT protectors actuate when detecting a temporary
overvoltage, for example a failure on the neutral, cutting off the power
supply and thus, protecting the equipments installed downstream.
To restore the IGA TEST it is necessary to reconnect the protective
coil in advance using the RESET button. Moreover IGA TEST
COMPACT protector also actuate whenever it detects a transient
overvoltage driving the current to earth and reducing the voltage
to a level that does not damage the connected equipment. Tested
and certified as Type 2 protector in official and independent
laboratories, according to regulations IEC 61643-11 and GUÍA-BT-23
from REBT. It is provided with a thermodynamic control device that
disconnects from the electrical network in case of degrading and a
warning system. When the warning is green the enclosure is in good
shape. If not, replace.
The MCB integrated is available in the most usual nominal currents:
20, 25, 32, 40, 50 and 63A.
> Instalation
They must be installed in series with the Low Voltage line, between the
Power Control Circuit Breaker (ICP) and the Residual Current Device
(ID). Installation should be made without power in the line.
Technical data:
IGA TEST
IGA TEST
IGA TEST
IGA TEST
IGA TEST
IGA TEST
COMPACT M 20
COMPACT M 25
COMPACT M 32
COMPACT M 40
COMPACT M 50
COMPACT M 63
Reference:
AT-9070
AT-9071
AT-9072
AT-9073
AT-9074
AT-9075
Nominal current:
20A
25A
32A
40A
50A
63A
Nominal voltage:
Maximum overvoltage:
Actuating time:
Maximum short-circuit
Un
230VAC
400VAC
@275V -> 8-10s / @400V -> 0,1-0,2s
10kA
current:
Type of tests according to IEC
61643:
Nominal discharge current:
Maximum discharge current:
Protection level:
Dimensions:
Cable range:
Type 2
In
Imax
Up
Certified test according to regulations:
5kA
15kA
1,5kV
51 x 81 x 65mm (3 mod. DIN43880)
Min / Max Section 1,5 / 35mm2
UNE-EN 60898, UNE-EN 50550, UNE-EN 61643-11
Aplicaciones Tecnológicas S.A. - Parque Tecnológico de Valencia - Nicolás Copérnico, 4 - 46980 Paterna (Valencia), España
T +34 961 318 250 - F +34 961 318 206 - [email protected] - www.at3w.com