TM SYMBOL DESCRIPTION SYMBOL SURFACE MOUNTED 2X4 LUMINAIRE RECESSED 1X4 LUMINAIRE SURFACE MOUNTED 1X4 LUMINAIRE SHADING OF ANY LUMINAIRE INDICATES CONNECTION TO ALTERNATE POWER SOURCE (EMERGENCY, UPS, STANDBY, ETC.) PER CIRCUITING INDICATED "ON ALT." RECESSED DOWNLIGHT, CEILING MOUNTED F FUSED DISCONNECT SWITCH, SIZE AS NOTED. SIZE FUSE PER MANUFACTURER'S RECOMMENDATIONS C ENCLOSED CIRCUIT BREAKER DISCONNECT SWITCH, TRIP SIZE AS NOTED. SURFACE DOWNLIGHT, CEILING MOUNTED WW DIRECTION WW DIRECTION SURFACE WALLWASH RECESSED LINEAR WALLWASH SURFACE LINEAR WALLWASH RECESSED CEILING ADJUSTABLE POINT SOURCE SURFACE CEILING ADJUSTABLE POINT SOURCE EQUIPMENT OR TERMINAL ENCLOSURE AS NOTED, SURFACE AND RECESS MOUNTED WALL MOUNTED LUMINAIRE BUILDING GROUND BUS, SEE DETAILS DM WALL MOUNTED DIRECTIONAL (SIZE VARIES) GFI C F +42" BUSWAY RISER POKE THRU UNIT WITH DOUBLE DUPLEX RECEPTACLE - FLUSH, PEDESTAL MOUNTED. BUSWAY STAB-IN TYPE CIRCUIT BREAKER OR FUSE DISCONNECT. SIZE AS NOTED. J OVERLOADS INDICATES ROTATED OPTICS POST TOP MOUNTED LUMINAIRE NORMALLY CLOSED CONTACTOR OR RELAY CONTACTS IN-GRADE POINT SOURCE NORMALLY OPEN CONTACTOR OR RELAY CONTACTS J J GARAGE LIGHTING LUMINAIRE WITH CUTOFF LOUVERS BUS DUCT LUMINAIRE MARKING CONVENTION LEGEND: HA = LUMINAIRE TYPE IDENTIFICATION. SEE LUMINAIRE SCHEDULE. 3c = CIRCUIT NUMBER VIA LOCAL SWITCH (LOWERCASE LETTER) THAT SERVES THE LUMINIARE. 3A = CIRCUIT NUMBER/UPPERCASE LETTER COMBINATION INDICATES LOW VOLTAGE RELAY OR LIGHTING CONTACTOR THAT SERVES THE LUMINAIRE BUS BAR CONNECTOR, FEMALE AND MALE RESPECTIVELY R Sa D TVSS S3 THREE WAY SWITCH NORMALLY OPEN PUSH BUTTON S4 FOUR WAY SWITCH SK KEY OPERATED SWITCH D DIMMER SWITCH. NUMBER INDICATES WATTAGE RATING. IF NOT SHOWN THEN EQUAL TO LOAD. S 5A,5B S 5C EXPLOSION PROOF SWITCH SWP WEATHERPROOF SWITCH SV LINE VOLTAGE, VARIABLE SPEED FAN CONTROL SWITCH, PROVIDED BY DIV. 15, INSTALLED BY DIV. 16. LOCATE ADJACENT TO ADJACENT TO LIGHT SWITCHES. MOTOR-RATED THERMAL OVERLOAD SWITCH SOR1 LIGHTING CONTROL OVERIDE SWITCH, SEQ. NUMBER C EQUIPMENT OPERATOR PUSH BUTTON STATION. PROVIDED WITH EQUIPMENT, INSTALLED AND CONNECTED BY DIV. 16, UON. STB TC TIME CLOCK OS OCCUPANCY SENSOR - WALL MOUNTED OS 360 DEGREE OCCUPANCY SENSOR - CEILING MTD. OS 180 DEGREE OCCUPANCY SENSOR - CEILING MTD. OS CORRIDOR/AISLE OCCUPANCY SENSOR - CEILING MOUNTED COMBINATION OCCUPANCY SENSOR & SWITCH GANGED UNDER A COMMON COVER PLATE. OCCUPANY SENSOR TO CONTROL ALL LUMINAIRES IN ROOM WITH 1/2 LIGHT REDUCTION CONTROLLED BY SWITCH, DESIGNATED BY LETTER. 2-GANG BOX WITH SINGLE-GANG MUDRING, UON SPECIFIED THERMOSTAT - WALL, CEILING. PROVIDED BY DIV. 15, INSTALLED AND WIRED BY DIV. 16 T LCP ? LIGHTING CONTROL PANEL AND ASSOCIATED COMPONENTS. PROVIDE 120V OR 277V CONTROL POWER AS REQUIRED OR AS INDICATED. M R/C,F,R HEAT DETECTOR (R/C=RATE OF COMBUSTION, F=FIXED TEMP. ONLY, R=RATE OF RISE ONLY) EARLY WARNING SMOKE DETECTION SYSTEM INCLUDES ALL PIPING BY DIV. 16. LIGHT (LAMP, SIGNAL LIGHT, INDICATOR LAMP, STROBE) FIRE ALARM OUTPUT OR RELEASE ABORT PUSHBUTTON, REFER TO SPECIFICATIONS AND DETAILS. AGENT RELEASE INITIATING VALVE BELL SILENCE SWITCH AGENT DISCHARGE SWITCH POWER CONNECTION TO DIV 15 FIRE/SMOKE DAMPER. REFER TO FSD CONNECTION DETAIL IF NOT SHOWN SECURITY SYSTEM SYSTEM CLOCK - WALL , CEILING I M M DIGITAL METER UNIT. REFER TO SPECIFICATIONS. SYMBOL INTERCOM STATION - WALL, DESK M = MASTER STATION CCTV SECURITY INDOOR DOME CAMERA D MICROPHONE JACK - WALL, FLOOR CCTV SECURITY PAN/TILT/ZOOM CAMERA PTZ MRIB PUSHBUTTON OR PUSHBUTTONS RF COAX CABLE OUTLET (TV, VCR, ETC.) TERMINAL FOR FIELD CONNECT, SIZE & TYPE SUITABLE FOR CONDUCTOR INSTALLED. COMBINATION RF COAX CABLE AND DATA OUTLET RF COAX CABLE SIGNAL SPLITTER INTELLIGENT CARD READER INTERFACE ROLL-UP DOOR MOTOR CONTROL OUTPUT MO DOOR POSITION MONITOR SWITCH D RX RX I I FLUSH FLOOR DEVICE - DEVICE TYPE PER SYMBOLS ABOVE CIRCUIT BREAKER, WITH TRIP & FRAME AMPERE RATING 225AF 400AS FUSED SWITCH, WITH FUSE AND SWITCH AMPERE RATING PA S D S D INDIVIDUALLY MOUNTED CIRCUIT BREAKER 52 GF CIRCUIT BREAKER, MEDIUM VOLTAGE, DRAWOUT DRAWOUT CIRCUIT BREAKER GROUND FAULT TRIP UNIT BA BELL ALARM TRIP MODULE CONTACTS ST SHUNT TRIP UNIT, 120VAC OR VOLTAGE AS NOTED CM MONITORING COMMUNICATION MODULE AM INTEGRAL AMMETER DISPLAY K KEY INTERLOCK MECHANICAL INTERLOCK 10 CAPACITOR, POWER FACTOR CORRECTION, SIZE IN KVAR GENERATOR FUSE, HOLDER & PULLER C CONNECTION TO DIV. 15 CHILLER CR PEDESTAL FLOOR DEVICE - DEVICE TYPE PER SYMBOLS ABOVE S SYMBOL G GC DESCRIPTION BARE GROUNDING GRID OR CONDUCTORS, UON. GROUNDING CONDUCTOR(S) ROUTED IN CODE SIZED CONDUIT, UON. GROUND GRID BOND POINT GROUND GRID BOND POINT - MECHANICAL CONNECTION GROUND GRID BOND POINT - EXOTHERMIC WELD CONNECTION REQUEST TO EXIT DEVICE WALL,MULLION MOUNTED INTERCOM STATION - WALL, DESK MOUNTED. M = MASTER STATION 60" GROUND BAR GROUND ROD LOCATION GROUND ROD IN TEST WELL DURESS PUSHBUTTON STATION DS CONNECTION TO GROUND 100AT 225AF GROUNDING SYSTEM 24" GROUND BAR RF COAX CABLE DISTRIBUTION AMPLIFIER. PROVIDE 120V POWER AS REQUIRED OR AS INDICATED. SEE RISER DIAGRAM. GROUNDED WYE CONNECTION DESCRIPTION CCTV SECURITY FIXED CAMERA - WALL,CEILING CURRENT TRANSFORMER SHORTING TERMINAL BLOCK. SOLENOID REMOTE MOUNTED LINE TO LOW-VOLTAGE FUSED TRANSFORMER. CONCEAL FROM VIEW. HEAT DETECTOR, CEILING MOUNTED. RATE OF RISE AND FIXED TEMPERATURE TYPE, UON. UNDERFLOOR RACEWAY FLEXIBLE CONDUIT CONNECTION M EMERGENCY POWER OFF, HEAVY-DUTY, OIL-TIGHT RED MUSHROOM-HEAD PUSHBUTTON W/ GUARD. EPO I UTILITY CO. APPROVED SOCKET WITH METER INSTALLED. SQUARE = REMOTE MOUNTED C LED INDICATOR LIGHT, PUSH TO TEST, R=RED G= GREEN, B= BLUE, Y= YELLOW, W= WHITE PUSHBUTTON OR PUSHBUTTONS, BY DIV. 16 b OSa METER: KILOWATT HOUR M PHOTOCELL PC FLAME DETECTOR (FLICKER DETECTOR) BUZZER DELTA CONNECTION ST PB P METER: POWER FACTOR DMU SXP BELL FIRE/SMOKE DAMPER BY DIV 15. WIDTH OF SYMBOL WILL VARY WITH DUCT WIDTH. PROVIDE POWER AND MONITORING AS INDICATED. REFER TO FSD CONNECTION DETAIL. WIRING EXTENSION POINT - CONDUIT TO MC CABLE OR MANUFACTURED WIRING SYSTEM J-BOX ABOVE ACCESSIBLE CEILINGS AREAS, OR EXTEND CONDUIT & WIRE IN EXPOSED OR "HARD" CEILING AREAS. SHADED= ON ALT. POWER SOURCE (EMERG,UPS,ETC.) PULL BOX, MIN. SIZE PER NEC., UON. CHIME PF SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN SWITCH IS "OFF"). LOW VOLTAGE MOMENTARY CONTACT SWITCH, UPPER CASE LETTER SUPERSCRIPT INDICATES CONNECTION TO LOW VOLTAGE RELAY CONTROLLING SIMILARLY MARKED LUMINAIRES. B FIREMAN'S PHONE HANDSET, WALL MOUNTED JUNCTION BOXES, WALL, CEILING AND FLUSH FLOOR MOUNTED. 4" SQ. BOX MIN., LARGER IF REQUIRED J SPEAKER - WALL, CEILING VOLUME CONTROL - WALL FIREMAN'S PHONE JACK, WALL MOUNTED LADDER TYPE CABLE TRAY WITH 90 DEGREE ELBOW SHOWN TELEPHONE OUTLET - WALL, W = USE HIGHER MOUNTING HEIGHT PER MOUNTING HT. DETAIL V FUSED VOLTAGE SENSE LEADS M S 5A S END OF LINE RESISTOR (NOT SHOWN ON PLANS) NORMALLY CLOSED PUSH BUTTON SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN SWITCH IS "ON"). TIMER SWITCH TX S ADDRESSABLE CONTROL MODULE BASKET TYPE CABLE TRAY WITH 90 DEGREE ELBOW SHOWN CURRENT TRANSFORMER KWH T W DIMMER SWITCH UNDER SEPARATE COVERPLATE STS TELEPHONE/DATA SLEEVE THROUGH WALL, ABOVE CEILING. EXTEND TO ACCESSIBLE TILE CLG. BOTH SIDES. TERMINATE WITH BUSHINGS. (1) 1.25" CO UON. COORDINATE LOCATIONS WITH CABLE INSTALLER(S) PRIOR TO ROUGH-IN. DATA OUTLET - WALL POTENTIAL TRANSFORMER SPL CONDUIT STUBBED OUT AT LOCATION SHOWN. PROVIDE INSULATED BUSHING & PULLROPE. COMBO TELEPHONE/DATA OUTLET - WALL TRANSIENT VOLTAGE SURGE SUPPRESSOR S2 SP TWO OR THREE COMPARTMENT SURFACE METAL RACEWAY WITH RECEPTACLES AND OUTLETS AS INDICATED, LENGTH AS INDICATED ON THE DRAWINGS. PROVIDE ALL FITTINGS AS REQUIRED. J J ELECTROMAGNETIC DOOR HOLDER - WALL, FLOOR, DOOR CLOSURE MOUNTED. PROVIDED BY DIV. 8 UON. DATA LOOP ISOLATION MODULE CONDUIT RUN TURNED DOWN THROUGH FLOOR OR CEILING. CORE & FIREPROOF AS REQUIRED. SIGNAL SYSTEM EQUIPMENT ENCLOSURES AS NOTEDSURFACE, RECESSED MOUNTED LIGHTNING SURGE ARRESTOR D= DISTRIBUTION CLASS I = INTERMEDIATE CLASS C HOME RUN WIRING TO INDICATED DESTINATION, 3/4"C. MIN. OR AS OTHERWISE NOTED. CONTRACTOR SHALL USE CIRCUIT SIZES NOTED IN RESPECTIVE SCHEDULES AND INFORMATION IN THE FEEDER AND BRANCH CIRCUIT SCHEDULES. CONDUIT RUN TURNED UP THROUGH FLOOR OR CEILING. CORE & FIREPROOF AS REQUIRED. TERMINAL/MOUNTING BOARD, 8' HIGH X WIDTH AS SHOWN, FIRE TREATED. RELAY COIL SINGLE POLE SWITCH (SUPERSCRIPT DENOTES SIMILARLY MARKED LUMINAIRES CONTROLLED TOGETHER) TWO POLE SWITCH D L1A-1,3 HD1A DESCRIPTION CONTACTOR COIL SMOKE DETECTOR MOUNTED BELOW RAISED FLOOR NEUTRAL TWO-PIECE SURFACE METAL RACEWAY WITH RECEPTACLES AS NOTED, LENGTH AS INDICATED ON THE DRAWINGS AND WITH ALL FITTINGS AS REQUIRED. SYMBOL P,B,R,C SMOKE DETECTOR - WALL, CEILING MOUNTED (P=PLENUM MOUNTED, B=W/RELAY BASE, R=ELEVATOR RECALL, C=INTEGRAL TO DOOR CLOSURE) ADDRESSABLE MONITOR MODULE GROUND HOT SIGNAL DEVICES PIPE GROUND C DESCRIPTION GC BATTERY GENERAL RESISTOR SMOKE DETECTOR, LOW AIR VELOCITY IN DUCT MOUNTED PHOTOELECTRIC TYPE U.O.N. BARE GROUNDING GRID OR CONDUCTORS, UON. GROUNDING CONDUCTOR(S) ROUTED IN CODE SIZED CONDUIT, UON. STROKES INDICATE QUANTITY OF #12 AWG. CONDUCTORS, UON. NOTE: WIRING STROKES FOR 20A BRANCH CIRCUITS ARE NOT SHOWN ON DRAWINGS. CONTRACTOR SHALL USE INFORMATION IN PANEL AND BRANCH CIRCUIT SCHEDULES TO PROVIDE REQUIRED CIRCUITING. G TELE/POWER POLE WITH WHIP CONNECTION TO ELECTRIFIED FURNITURE J D TELEPHONE SYSTEM CONDUIT MEDIUM VOLTAGE CONDUIT TELE/POWER POLE, POWER POLE J SMOKE DETECTOR, DUCT MOUNTED, WITH FULL WIDTH SAMPLING TUBES. PHOTOELECTRIC TYPE UON. (F) FUTURE WORK POKE THRU UNIT WITH JUNCTION BOX. RACEWAY COMPONENTS RC-700 SERIES. J LIGHT BEAM TYPE SMOKE DETECTOR (BR=BEAM RECEIVER, BT=BEAM TRANSMITTER) (D) EXISTING WORK TO BE REMOVED MULTI-SERVICE FLOOR BOX CAST IN CONC. OR IN RAISED FLOOR - SEE ARCH DWGS; WITH RECEPTACLES & SIGNAL OUTLETS AS NOTED. J SPRINKLER FLOW SWITCH CONNECTION (E) EXISTING WORK TO REMAIN COMBO POKE THRU UNIT WITH DUPLEX RECEPTACLE AND TELEPHONE OUTLET - FLUSH, PEDESTAL MOUNTED. DESCRIPTION DESCRIPTION NEW WORK T COMBINATION MINI HORN/STROBE - WALL, CEILING MOUNTED (# = CANDELA RATING) SPRINKLER VALVE TAMPER SWITCH CONNECTION WIRING CONCEALED IN FLOOR OR UNDER GRADE OR ROUTED IN CEILING SPACE OF FLOOR BELOW. DAMPER MOTOR COMBINATION HORN/STROBE - WALL, CEILING MOUNTED (# = CANDELA RATING) MINI HORN - WALL, CEILING MOUNTED EQUIPMENT BY OTHERS IDENTIFICATION TAG SYMBOL PEDESTAL FLOOR DEVICE - DEVICE TYPE PER SYMBOLS ABOVE FIELD INSTALLED CONTROL CIRCUIT WIRING TO DESTINATION SHOWN, U.O.N. 15 WIRING FLUSH FLOOR BOX DEVICE - DEVICE TYPE PER SYMBOLS ABOVE SWITCH POLE MOUNTED LUMINAIRE- SINGLE OR DUAL HEAD SYMBOL EQUIP NAME COMBINATION SPEAKER/STROBE, WALL MOUNTED (# = CANDELA RATING) HORN - CEILING, WALL MOUNTED MECHANICAL EQUIPMENT IDENTIFICATION TAG CLOCK HANGER RECEPTACLE HAND/OFF/AUTO SWITCH BOLLARD SWITCHING CONTROLS KITCHEN EQUIPMENT REFERENCE, REFER TO KITCHEN EQUIPMENT SCHEDULE CH 1 STROBE LIGHT - WALL, CEILING MOUNTED (# = CANDELA RATING) SPEAKER - WALL, CEILING MOUNTED 15 WALL MOUNTED ELECTRICAL CONNECTION TO ELECTRIFIED FURNITURE. PROVIDE 8 WIRES (4 HOTS, 1 DEDICATED NEUTRAL, 1 COMMON NEUTRAL, 1 ISOLATED GROUND) NEUTRALS TO BE #10 AWG. USE LIQUID-TIGHT FLEX. J POKE THRU UNIT WITH DUPLEX RECEPTACLE FLUSH, PEDESTAL MOUNTED. SYMBOL ILLUMINATED EXIT SIGN, SHADED QUADRANT INDICATES FACES, ARROWS AS SHOWN 3A SECTION TAG: REFER TO SECTION NUMBER ON DRAWING INDICATED 3 E4.1 RECEPT. TYPE SHOWN AT SPECIAL HEIGHT DIAGRAMS CONTINUOUS LINEAR SOURCE (LED, COLD CATHODE, NEON, FIBER OPTIC, ETC...) 3c 30 K112 RECEPT. TYPE SHOWN W/ WEATHERPROOF COVER AND INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER WP UNDERCABINET FLUORESCENT STRIPLIGHT BATTERY POWER EMERGENCY UNIT EQUIPMENT (SEE LUMINAIRE SCHEDULE FOR QUANTITY OF HEADS) WALL, CEILING MOUNTED. ALARM BELL OR GONG MV FLUORESCENT STRIPLIGHT - POWER FEED SECTION, FEED THROUGH SECTION. LENGTH AS SHOWN. WALL MOUNTED FLUORESCENT STRIPLIGHT ELEVATION TAG: REFER TO ELEVATION NUMBER ON DRAWING INDICATED DUPLEX RECEPTACLE - WALL - WITH INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER DIV. 16 CONNECTION TO EQUIPMENT WITH INTEGRAL DISCONNECT THAT IS PROVIDED BY OTHERS. SHADED = ON ALT. POWER SOURCE NOTED TRACK LIGHTING WITH HEADS AS INDICATED. 2 E4.1 FIRE ALARM SYSTEM MANUAL PULL STATION, WALL MOUNTED COMBINATION SWITCH/DUPLEX RECEPTACLE DIV. 16 CONNECTION TO EQUIPMENT PROVIDED BY OTHERS. SHADED = ON ALT. POWER SOURCE NOTED RECESSED WALL MOUNTED LUMINAIRE FIRE ALARM SYSTEM ANNUNCIATOR FIRE ALARM CONTROL PANEL AND ASSOCIATED COMPONENTS. PROVIDE 120V POWER AS REQUIRED OR AS INDICATED. 15 DISCONNECT W/ MAGNETIC MOTOR STARTER (CONTROLLER) OR CONTACTOR. SIZE PER LOAD SERVED. NEMA SIZE #1 MINIMUM. MAGNETIC MOTOR STARTER (CONTROLLER) OR CONTACTOR. SIZE PER LOAD SERVED. NEMA SIZE #1 MINIMUM. RECESSED WALLWASH REFER TO DETAIL NO. ON DRAWING INDICATED NOT ALL DETAIL REFERENCES ARE SHOWN. ALL DETAILS APPLY TO ALL APPLICABLE SITUATIONS, UON. DUPLEX RECEPTACLE - WALL - HALF SWITCHED S SUSPENDED PENDANT LUMINAIRE (SIZE VARIES) DISCONNECT SWITCH, SIZE AS NOTED OR IF NOT SHOWN SIZE PER CONNECTED MOTOR SIZE AND MOTOR DISCONNECT SCHEDULE WALL MOUNTED LINEAR LUMINAIRE (SIZE VARIES) 1 E4.1 SHADED RECEPTACLES NOTED "ON ALT." ABOVE ARE CONNECTED TO ALTERNATE POWER SOURCE (EMERG., STANDBY, UPS, ETC.) PER CIRCUITING INDICATED CONNECTION TO DIV. 15 FURNISHED VARIABLE FREQUENCY DRIVE WITH INTEGRAL DISCONNECT DIV. 16 TO INSTALL VFD EQUIPMENT VFD BRANCH CIRCUIT OR FEEDER NOMINAL AMPACITY & TYPE; REFER TO BRANCH CIRCUIT AND FEEDER SCHEDULES FOR WIRE AND CONDUIT SIZES & QTY. RECEPTACLE TYPE SHOWN -WALL -ABOVE COUNTER BACKSPLASH. SEE ARCHITECTURAL DRAWINGS. CONNECTION TO MOTOR PROVIDED BY OTHERS SUSPENDED LINEAR LUMINAIRE (SIZE VARIES) 125.4 TRANSFORMER WITH CODE CLEARANCES SHOWN SERVICE AND/OR DISTRIBUTION EQUIPMENT WITH CODE CLEARANCES SHOWN SHEET NOTE REFERENCE DESCRIPTION DUPLEX RECEPTACLE - WALL, CEILING, ON ALT. SPECIAL PURPOSE RECEPTACLE -WALL, CEILING ON ALT. POWER; NEMA CONFIGURATION AS NOTED AB SYMBOL 12 DOUBLE DUPLEX RECEPTACLE - WALL, CLG, ON ALT. L5-15R DESCRIPTION FIRE ALARM SYSTEM SIMPLEX RECEPTACLE - WALL, CEILING, ON ALT. MOTOR CONTROL CENTER W/ CODE CLEARANCES SHOWN, DASHED EQUIP. = FUTURE RECESSED 2X2 LUMINAIRE SURFACE MOUNTED 2X2 LUMINAIRE SYMBOL DESCRIPTION BRANCH CIRCUIT PANELBOARDS, SURFACE AND RECESS MOUNTED RECESSED 2X4 LUMINAIRE REFERENCE SYMBOLS CR CARD READER- WALL MOUNTED/MULLION MOUNTED LIGHTNING PROTECTION PARAPET MOUNTED AIR TERMINAL LIGHTNING PROTECTION MID ROOF MOUNTED AIR TERMINAL ER EMERGENCY DOOR RELEASE BREAK-GLASS STATION PAGING SYSTEM HORN (OUTDOOR) N LOCAL DOOR MONITOR WARNING NOISE DEVICE DUAL COIL SPEAKER - SURFACE CEILING, RECESSED CEILING. EB ELECTRIC BOLT LIGHTNING PROTECTION CONDUCTOR ROUTED DOWN EL ELECTRIC LOCK/LATCH LIGHTNING PROTECTION BOND PLATE ES ELECTRIC STRIKE LIGHTNING PROTECTION BIMETAL CONNECTION ML MAGNETIC LOCK GB GLASS BREAK SENSOR H ELECTRIC POWER TRANSFER HINGE S PAGING OR PAGING/SOUND MASKING SPEAKER, MOUNTED ABOVE ACOUSTIC TILE CEILING. AV AV INPUT OUTLET, 1"C WITH 3-GANG BOX. CONDUIT STUBBED ABOVE ACCESSIBLE TILE CEILING. IR ASSISTIVE LISTENING INFRARED TRANSMITTER PANEL, 1"C WITH 2-GANG BOX. CONDUIT STUBBED ABOVE ACCESSIBLE TILE CEILING. LIGHTNING PROTECTION AIR TERMINAL SECURITY ELECTRONIC MOTION SENSOR ELECTRICAL EQUIPMENT NAMING CONVENTION LEGEND EXAMPLES / LEGEND MCCDP- U XFR- EQUIPMENT TYPE H M 1 A L D 1 A H L 1 A SWBD- M H SN 1 A PNL- E H K 2 B POWER ADDN'L SEQ. SYSTEM DESIG. LETTERS DESIG. EQUIP. SYSTEM FLOOR TYPE VOLTAGE SUB - UNIT SUBSTATION SWBD - SWITCHBOARD SWGR - SWITCHGEAR DP - DISTRIBUTION PANEL PNL - BRANCH PANEL ATS - AUTOMATIC TRANSFER SWITCH BIATS - BYPASS ISOLATION ATS MTS - MANUAL TRANSFER SWITCH XFR - TRANSFORMER UTX - UTILITY MAIN TRANSFORMER MCC - MOTOR CONTROL CENTER CB - ENCLOSED CIRCUIT BREAKER FSW - FUSED DISCONNECT SWITCH DSW - NON-FUSED DISCONNECT SW. POWER SYSTEM BLANK - NORMAL LOADS M - MAIN UTILITY SERVICE EM - EMERGENCY POWER (Life Safety) S - STANDBY POWER (E) (F) (R) (RL) AB ACU AC A, AMP AF AFF AFG AIC EXISTING TO REMAIN FUTURE EXISTING TO BE REMOVED EXISTING TO BE RELOCATED ABOVE COUNTER BACKSPLASH AIR CONDITIONING UNIT ALTERNATING CURRENT AMPERES AMPERE (RATED) FUSE OR CB FRAME ABOVE FINISHED FLOOR ABOVE FINISHED GRADE EQUIPMENT SHORT CIRCUIT INTERRUPT RATING (RMS SYM. AMPS) AL ALUMINUM (ALLOY) ALC AUTOMATIC LIGHTING CONTROL AS AMPERE (RATED) SWITCH AT CIRCUIT BRKR TRIP SETTING (AMPS) ATS AUTOMATIC TRANSFER SWITCH AUTO AUTOMATIC AUX AUXILIARY AWG AMERICAN WIRE GAUGE BAT BATTERY BG BELOW GRADE BRKR CIRCUIT BREAKER C CONDUIT (CIRCULAR RACEWAY) CAB CABINET CB CIRCUIT BREAKER CFM CUBIC FEET PER MINUTE CKT CIRCUIT CLG CEILING CO CONDUIT ONLY CPT CONTROL POWER TRANSFORMER CT CURRENT TRANSFORMER CU COPPER DC DIRECT CURRENT DISC DISCONNECT DIA DIAMETER DIV DIVISION DP DISTRIBUTION PANEL DPDT DOUBLE POLE DOUBLE THROW DPST DOUBLE POLE SINGLE THROW DWG DRAWING E,EMERG EMERGENCY EF EXHAUST FAN EMT ELECTRICAL METALLIC TUBING ENCL ENCLOSURE EO ELECTRICALLY OPERATED EOL END OF LINE EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER FA FIRE ALARM FAA FIRE ALARM ANNUNCIATOR FBO FURNISHED BY OTHERS FC FOOT CANDLES FF FLUSH FLOOR MOUNTED FLA FULL LOAD AMPERES FLEX FLEXIBLE FPB FAN POWERED BOX FSD FIRE/SMOKE DAMPER FW FLUSH WALL MOUNTED FU FUSE GEN GENERATOR GFI GROUND FAULT CIRCUIT INTERRUPTER GND GROUND GRAP GENERATOR REMOTE ANNUNCIATOR PNL GRC GALVANIZED RIGID STEEL CONDUIT HLO HANDLE LOCK-ON(OFF) HP HORSEPOWER HPF HIGH POWER FACTOR HTR HEATER HZ HERTZ (CYCLES PER SECOND) IES ILLUMINATING ENGINEERING SOCIETY IBC INDIVIDUAL BRANCH CIRCUIT ID INSIDE DIAMETER IG ISOLATED GROUND IMC INTERMEDIATE METAL CONDUIT KCMIL THOUSAND CIRCULAR MILS KO KNOCK OUT KW KILOWATTS KVA KILOVOLT-AMPERES LTG LIGHTING LCP LIGHTING CONTROL PANEL MAX MAXIMUM MCA MINIMUM CIRCUIT AMPERES MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MLO MAIN LUGS ONLY MO MANUAL OPERATOR MTD MOUNTED MTR MOTOR -NNEUTRAL (GROUNDED CONDUCTOR) NC NORMALLY CLOSED NEC NATIONAL ELECTRICAL CODE -,NEG NEGATIVE NEMA NATIONAL ELECTRICAL MFGR'S ASSOC. NL NIGHT LIGHT (UNSWITCHED) NO NORMALLY OPEN NTS NOT TO SCALE NP NAMEPLATE OC ON CENTER OD OUTSIDE DIAMETER OFCI OWNER FURNISHED CONTRACTOR INSTALLED OFOI OWNER FURNISHED, OWNER INSTALLED OS OCCUPANCY SENSOR P POLE PB PUSHBUTTON PH, Ø PHASE PNL PANEL +,POS POSITIVE PRI PRIMARY REQD REQUIRED RNC RIGID NON-METALLIC CONDUIT (PVC) RS RAPID START RST REMOTE STATION TRANSMITTER S.A.D. SEE ARCHITECTURAL DRAWINGS SEC SECONDARY SN SHEET NOTE SOL SOLENOID SPDT SINGLE POLE DOUBLE THROW SPST SINGLE POLE SINGLE THROW SUB SUBSTATION SWBD SWITCHBOARD SWGR SWITCHGEAR TB TERMINAL BOARD TDC TIME DELAY CLOSING TDO TIME DELAY OPENING TEL TELEPHONE TYP TYPICAL UL UNDERWRITERS LAB UON UNLESS OTHERWISE NOTED UPS UNINTERRUPTIBLE POWER SUPPLY UTX UTILITY TRANSFORMER V VOLTS VA VOLT-AMPERES VFD VARIABLE FREQUENCY DRIVE W WATT W/ WITH W/O WITHOUT WP WEATHERPROOF, SEE RECEPT. SYMBOL XFR TRANSFORMER XP EXPLOSION PROOF Z ZONE ", IN INCHES ', FT FEET Ø PHASE > GREATER THAN < LESS THAN > GREATER THAN OR EQUAL TO ELECTRICAL DESIGN CRITERIA 1. 2. 3. 4. OREGON ELECTRICAL SPECIALTY CODE (OREGON AMENDED VERSION OF 2014 NATIONAL ELECTRIC CODE) . FIRE/LIFE SAFETY CODE: 2007 IFC WITH OREGON AMMENDMENTS . 2010 STATE OF OREGON STRUCTURAL SPECIALTY CODE: OREGON AMMENDED VERSION OF 2009 IBC . AMERICANS WITH DISABILITIES ACT, (ADA) . Job No.: 02.14.00651 Contact: LRH www.glumac.com DESCRIPTION DISTRIBUTION & EQUIPMENT ABBREVIATIONS 900 SW Fifth Ave., Suite 1600 Portland, OR 97204-2640 T. 503.227.5280 F. 503.274.7674 SYMBOL ELECTRICAL LEGEND POWER DEVICES engineers for a sust ai nable f uture LIGHTING REFER TO DETAILS FOR MOUNTING HEIGHTS OF DEVICES NOT ALL SYMBOLS, ABBREV., ETC. ARE NECESSARILY USED ON THIS PROJECT Client ELECTRICAL BASIS OF DESIGN 1. 2. 3. 4. 5. THE EXISTING OLD GENERATOR, LOCATED IN THE PENTHOUSE AND SERVING THE BUILDING'S ELEVATORS, WAS REMOVED. THIS PROJECT IS TO RECONNECT THE EXISTING ATS SERVING THE ELEVATORS TO THE RECENTLY ADDED GENERATOR LOCATED IN THE SUB-BASEMENT. . DUE TO SELECTIVE COORDINATION REQUIRMENTS OF THE 2014 NATIONAL ELECTRIC CODE, THE EXISTING PENTHOUSE EMERGENCY PANEL EM2 WAS REPLACED WITH A FUSED PANELBOARD AND ONLY ONE ELEVATOR CAN BE OPERATED WHILE OPERATING ON THE GENERATOR. . PSU HAS CONFIRMED THAT THE ELEVATOR CONTROLLER IS LAREADY PROGRAMMED TO ALLOW ONLY ONE ELEVATOR TO OPERATE AT ONE TIME WHILE ON EMERGENCY POWER. . SOME WALLS WILL NEED TO BE REMOVED TO ALLOW ACCESS TO THE EXISTING CONDUIT RISER THAT IS PART OF THIS PROJECT. THE OWNER WILL PROVIDE DEMO AND PATCHING OF THOSE WALLS. FIRE AND WATER PROOFING OF ANY NEW FLOOR OR FIRE RATED WALL PENETRATIONS ARE PART OF THE ELECTRICAL CONTRACTORS SCOPE OF WORK. . SHORT CIRCUIT FAULT CURRENT CALCULATIONS AND A COORDINATION STUDY OF BREAKERS AND FUSES WERE PERFORMED. PORTLAND STATE UNIVERSITY Project PSU ELEVATOR RECONNECTION TO GENERATOR ELECTRICAL ADD ALTERNATES 1. 2. ELECTRICAL CONTRACTOR TO PROVIDE COST OPTION TO REPLACE AND RECONNECT EXISTING PANEL EM2 INI THE PENTHOUSE PER THE NOTE ON THE SINGLE-LINE DIAGRAM. . ELECTRICAL CONTRACTOR TO PROVIDE COST OPTION TO PROVIDE A NEW 400A, 4P, 208Y,120V ATS IN PLACE OF THE EXISTING ONE. ELECTRICAL DRAWING LIST E0.1 E3.1 E5.1 E9.1 LEGENDS, ABBREVIATIONA AND DRAWING LIST PARTIAL FLOOR PLANS - POWER PLAN ELECTRICAL SINGLE-LINE DIAGRAM ELECTRICAL DETAILS © 2014 - GLUMAC ALL RIGHTS RESERVED THESE DRAWINGS ARE THE PROPERTY OF GLUMAC ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER, WITHOUT PRIOR WRITTEN PERMISSION Revisions # Description Date SHEET TITLE: LEGENDS, ABBREVIATIONA AND DRAWING LIST DRAWN BY: Author CHECKED BY: LRH SHEET E0.1 U - UNINTERRUPTIBLE POWER (UPS) C - CRITICAL POWER (Hospital) Q - EQUIPMENT POWER (Hospital) S - LIFE SAFETY POWER (Hospital) JOB NO. 100% CD'S/ PERMIT SET 7/30/14 02.14.00651 7/30/2014 11:19:18 AM 12" = 1'-0" TM PNL- EM2 (E) DISC-UNUSED (E) DISC PNL-EM2 XFR-EM2 (E) ATS-EM2 CONNECT (E) SPARE WIRING TO THIS (E) GENERATOR REMOTE ANNUNCIATOR. PROGRAM AS REQUIRED TO ALLOW PENTHOUSE ATS "ATS IN EMERGENCY" STATUS TO DISPLAY. ADD LABELS TO DISPLAY PANEL DISC-EM2 ROUTE SECONDARY EMT CONDUIT OVERHEAD AS REQUIRED. MOUNT DISCONNECT ON UNISTRUT FRAME 900 SW Fifth Ave., Suite 1600 Portland, OR 97204-2640 T. 503.227.5280 F. 503.274.7674 (E) DISC ELEV-MECH Job No.: 02.14.00651 Contact: JJE www.glumac.com engineers for a sust ai nable f uture ROUTE PRIMARY CONDUIT UNDER SLAB.CORE DRILL AS REQUIRED (E) GRAP-1 Client PORTLAND STATE UNIVERSITY Project PSU ELEVATOR RECONNECTION TO GENERATOR 4 PENTHOUSE - ENLARGED ELECTRICAL ROOM 2 SCALE: 1/4" = 1'-0" 0 4 FIRST FLOOR - PARTIAL ELECTRICAL PLAN SCALE: 1/8" = 1'-0" 0 8 8 16 © 2014 - GLUMAC ALL RIGHTS RESERVED THESE DRAWINGS ARE THE PROPERTY OF GLUMAC ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER, WITHOUT PRIOR WRITTEN PERMISSION Revisions # (E) EMPTY J-BOX AND CONDUIT. EXTEND 1" CONDUIT TO PENTHOUSE AND PROVIDE CONTROL WIRING PER SINGLE-LINE DIAGRAM (E) PNL- EM1 (E) CONDUIT SERVING PENTHOUSE PANEL-EM2. DEMO CONDUCTORS. PROVIDE LABEL ON CONDUIT AS "SPARE CONDUIT" USING KROY (E) DISC-EM1 3/4" LABEL Date SHEET TITLE: PARTIAL FLOOR PLANS POWER PLAN (E) XFR-EM1 (E) ATS-EM1 Description PROVIDE CONTROL WIRING AND CONDUIT TO PENTHOUSE ATS. CONNECT TO (E) GENERATOR CONTROLS (E) PNL- EMDP (E) GENSET TERMINAL CABINET PROVIDE FEEDER TO (E) PULL BOX FOR ROUTING OF FEEDER TO XFR-EM2 ROUTE CONTROL CONDUIT NEXT TO EXISTING CONDUIT RISERS. PROVIDE WATER AND FIRE PROOFING AT PENETRATION (E) PULL BOX (E) 400A DISC-FIRE PUMP DRAWN BY: LRH DISC-EM2 CHECKED BY: JJE SHEET (E) PANEL-EM2 FEEDER RISER CONDUIT PROVIDE SEPARATION BETWEEN EMERGENCY AND NORMAL FEEDERS E3.1 3 SECOND FLOOR - PARTIAL PLAN 1 SCALE: 1/8" = 1'-0" 0 8 16 BASEMENT - ENLARGED ELECTRICAL ROOM PLAN SCALE: 1/4" = 1'-0" 0 4 8 100% CD'S/ PERMIT SET 7/30/14 JOB NO. 02.14.00651 7/30/2014 11:19:26 AM As indicated TM CONNECT FEEDER WITH CRIMP LUGS TO EXISTING BUS BARS IN GUTTER 2 REMOVE EXISTING 60A FEEDER COMPLETELY. EXISTING RISER CONDUIT IS TO BE REUSED TO SERVE NEW FEEDER TO TRANSFORMER EM2 3 DEMO EXISTING CONDUIT BELOW SLAB AND REPLACE WITH LARGER SIZE IF REQUIRED 4 MOUNT FUSED DISCONNECT ON UNISTRUT RACK NEXT TO TRANSFORMER 5 PROVIDE LINE ITEM PRICE FOR REPLACING AND INSTALLING A NEW ATS. 6 REMOVE UNUSED DISCONNECT. CLOSE ALL UNUSED HOLES WITH PLUGS. 7 PROVIDE 80A RK1 FUSES IN (E) 100A DISCONNECT 8 PROVIDE CONDUCTOR SUPPORT WEDGE TO MATCH NEW FEEDER SIZE. SUPPORTS TO BE NO MORE THAN 100' APART FOR ALL VERTICAL DROPS. 9 ROUTE CONDUIT OVERHEAD OR BELOW SLAB. CORE-DRILL SLAB AS REQUIRED IF ROUTED BELOW. DO NOT ROUTE ON TOP OF FLOOR SLAB. 11 PROVIDE SEPARATE LINE ITEM PRICE TO REPLACE PANEL WITH 100A, 3P, 4W, 208Y/120V, 42-POLE BUSSMAN QUIK-SPEC FUSED PANEL WITH MLO AND BREAKER SIZE AND QUANTITY TO MATCH EXISTING WITH AN ADDITIONAL (4) 20A/1P SPARE BREAKERS AND FUSES. (E) ELEV-1 (E) ELEV-2 (E) ELEV-3 25 HP 25 HP 25 HP (E) 100.3M? (E) 100AF 100AS F (E) 100.3M? (E) 100AF 100AS (E) 100.3M? (E) 100.3M? (E) 100AF 100AS F (E) ELEV MACHINE RM HVAC ?? TONS 12 EXISTING PULLBOX LOCATION PER EXISTING SINGLE-LINE. THIS BOX HAS NOT BEEN FIELD VERIFIED. (E) 100.3M? F (E) 100.3M? 13 EXISTING PULL BOX. PROVIDE PHYSICAL BARRIER INSIDE PULLBOX TO SEPARATE NORMAL POWER FROM GENERATOR POWER. USE FLEXIBLE METAL CONDUIT OR SHEET METAL. (E) 80.2M? 14 EXISTING GENERATOR REMOTE ANNUNCIATOR PANEL. CONNECT (2) EXISTING CONDUCTORS TO ANNUNCIATOR TO ANNUNCIATE "ATS-EM2 IN EMERGENCY POSITION". LABEL WIRING. 15 EXISTING GENERATOR CONTROL TERMINAL PANEL. CONNECT GENERATOR START WIRING FROM PENTHOUSE ATS IN SERIES WITH EXISTING ATS GENERATOR START WIRING. CONNECT ATS IN EMERGENCY POSITION WIRING TO EXISTING GENERATOR REMOTE ANNUNCIATOR USING EXISTING SPARE CONDUCTORS. REPROGRAM ANNUNCIATOR WITH CATERPILLAR'S ASSISTANCE. Job No.: 02.14.00651 Contact: JJE www.glumac.com 1 900 SW Fifth Ave., Suite 1600 Portland, OR 97204-2640 T. 503.227.5280 F. 503.274.7674 # ROOF ROOF engineers for a sust ai nable f uture KEYED NOTES 1 PNL EM2 (E) 60AF 60AS 11 10 KAIC 7 6 80.4 F (E) 80AF 100AS (D) 60.4 2 (E) 80AF 100AS F 80.4 3.0 3 F 5 EM2 EMERGENCY 100 A 3-POLE ??KAIC 6.8 8 CS 250AF 400AS EM2 480Y/277V 75 KVA . PENTHOUSE (E) 400.4 (E) ATS . XFR 125.3 (E) 80.2 F 250.4 4 9 10 EXISTING EMPTY J-BOX WITH EMPTY CONDUIT. EXTEND CONDUIT TO PENTHOUSE ATS AND INSTALL GENERAOTR CONTROL AND MONITORING WIRING. PORTLAND STATE UNIVERSITY PENTHOUSE COPPER FEEDER SCHEDULE 10 FIFTHEENTH FLR FIFTHEENTH FLR FEEDER TAG CONDUITS CONDUCTORS PER SET 4.00" (4) 500 KCMIL 500 KCMIL - 250.4 2.50" 1 3.00" (4) 250 KCMIL #4 - 4000.3 3.00" 11 4.00" (3) 500 KCMIL 500 KCMIL - 250.3 2.50" 1 3.00" (3) 250 KCMIL #4 - 3500.4 3.50" 10 4.00" (4) 500 KCMIL 500 KCMIL - 225.4 2.50" 1 3.00" (4) #4/0 #4 - 3500.3 3.00" 10 4.00" (3) 500 KCMIL 500 KCMIL - 225.3 2.00" 1 2.50" (3) #4/0 #4 - 3000.4 3.50" 8 4.00" (4) 500 KCMIL 400 KCMIL - 200.4 2.00" 1 2.50" (4) #3/0 #6 - 3000.3 3.00" 8 4.00" (3) 500 KCMIL 400 KCMIL - 200.3 2.00" 1 2.50" (3) #3/0 #6 - 2500.4 3.50" 7 4.00" (4) 500 KCMIL 350 KCMIL - 175.4 2.00" 1 2.50" (4) #2/0 #6 - 2500.3 3.00" 7 4.00" (3) 500 KCMIL 350 KCMIL - 175.3 1.50" 1 2.00" (3) #2/0 #6 - 2000.4 3.00" 6 4.00" (4) 400 KCMIL 250 KCMIL - 150.4 2.00" 1 2.00" (4) #1/0 #6 - 2000.3 3.00" 6 4.00" (3) 400 KCMIL 250 KCMIL - 150.3 1.50" 1 2.00" (3) #1/0 #6 - 1600.4 3.00" 5 4.00" (4) 400 KCMIL #4/0 - 125.4 1.50" 1 1.50" (4) #1 #6 - 1600.3 3.00" 5 4.00" (3) 400 KCMIL #4/0 - 125.3 1.25" 1 1.50" (3) #1 #6 - 1200.4 3.00" 4 4.00" (4) 350 KCMIL #3/0 - 110.4 1.25" 1 1.50" (4) #2 #6 - 1200.3 3.00" 4 3.00" (3) 350 KCMIL #3/0 - 110.3 1.25" 1 1.50" (3) #2 #6 - 1000.4 3.00" 3 4.00" (4) 400 KCMIL #2/0 - 100.4 1.25" 1 1.50" (4) #2 #8 - 1000.3 3.00" 3 4.00" (3) 400 KCMIL #2/0 - 100.3 1.25" 1 1.50" (3) #2 #8 - 800.4 3.00" 3 3.00" (4) 300 KCMIL #1/0 - 90.4 1.25" 1 1.50" (4) #2 #8 - 800.3 2.50" 3 3.00" (3) 300 KCMIL #1/0 - 90.3 1.25" 1 1.50" (3) #2 #8 - 700.4 3.50" 2 4.00" (4) 500 KCMIL #1/0 - 80.4 1.25" 1 1.50" (4) #4 #8 - 700.3 3.00" 2 4.00" (3) 500 KCMIL #1/0 - 80.3 1.00" 1 1.50" (3) #4 #8 - 600.4 3.00" 2 4.00" (4) 350 KCMIL #1 - 70.4 1.25" 1 1.50" (4) #4 #8 - 600.3 2.50" 2 3.00" (3) 350 KCMIL #1 - 70.3 1.00" 1 1.50" (3) #4 #8 - 500.4 2.50" 2 3.00" (4) 250 KCMIL #2 - 60.4 1.00" 1 1.00" (4) #6 #10 - 500.3 2.50" 2 2.50" (3) 250 KCMIL #2 - 60.3 0.75" 1 1.00" (3) #6 #10 - 450.4 2.50" 2 3.00" (4) #4/0 #2 - 50.4 1.00" 1 1.00" (4) #6 #10 - 450.3 2.00" 2 2.50" (3) #4/0 #2 - 50.3 0.75" 1 1.00" (3) #6 #10 - PGE 400.4 2.00" 2 2.50" (4) #3/0 #2 - 40.4 0.75" 1 1.00" (4) #8 #10 - ?.? 0 KVA 12???V DELTA, 3P, 3W 480 WYE/277V PAD-VAULT MOUNTED UTILITY PROVIDED 400.3 2.00" 2 2.50" (3) 3/0 #2 - 40.3 0.75" 1 1.00" (3) #8 #10 - 350.4 3.50" 1 4.00" (4) 500 KCMIL #2 - 30.4 0.75" 1 1.00" (4) #10 #10 - 350.3 2.50" 1 4.00" (3) 500 KCMIL #2 - 30.3 0.75" 1 1.00" (3) #10 #10 - 300.4 3.00" 1 3.00" (4) 350 KCMIL #4 - 20.4 0.75" 1 1.00" (4) #12 #12 - 300.3 2.50" 1 3.00" (3) 350 KCMIL #4 - 20.3 0.75" 1 1.00" (3) #12 #12 - 12 8 ELEVENTH FLR ELEVENTH FLR TENTH FLR TENTH FLR SETS RNC PHASE/NEUTRAL NOTES 11 CS MET CONDUCTORS PER SET 3.50" TWELFTH FLR GROUND CONDUITS 4000.4 TWELFTH FLR PHASE/NEUTRAL FEEDER TAG SETS FOURTEENTH FLR RNC NOTES MET FOURTEENTH FLR GROUND NINTH FLR NINTH FLR 125.3 EIGHT FLR EIGHT FLR SEVENTH FLR SEVENTH FLR Project PSU ELEVATOR RECONNECTION TO GENERATOR SIXTH FLR SIXTH FLR FIFTH FLR FIFTH FLR FOURTH FLR FOURTH FLR THIRD FLR THIRD FLR J 12 PB 16 SECOND FLR SECOND FLR 14 GRAP (E) FIRST FLR FIRST FLR UTX DIST . 200A PULL 200A SPACE . 200A . 200A . 200A . 200A . 200A . 200A . 200A . 400A (E) MAIN SWITCHBOARD-- ??? M 0 A ,480Y/277V, 3P, 4W ,?? KAIC METER (E) GENERATOR 7.5 HP REMOTE RADIATOR (E) MAIN SWITCHBOARD- ??? 1600 A ,480Y/277V, 3P, 4W ,42 KAIC ,100% NEUTRAL ? MAIN BRKR 1600AT 1600AF . 400A . 600A . 125A . 250A . 125A . 250A GF . 125A . 300A . 125A . 100A . 250AT 400AF 400.4 (E) 125.3 (E) . 600.? (E) 250.? (E) 125.3 (E) . (E) PNL (E) XFR (E) DIST (E) PNL (E) XFR DPA 2H T1 A 35 KAIC 208Y/120V 75 KVA . (E) 200AF 200AS ??KAIC ??KAIC F 480Y/277V 75 KVA . (E) PNL (E) PNL (E) PNL (E) PNL B A 1H C ??KAIC ??KAIC ?? (E) ?? (E) (E) 400A (E) 200A (E) 400A ?? (E) (E) 15AF 30AS F ?? (E) ?? (E) (E) 100A (E) ??AF (E) SATEC TUBE (E) EMCO MAIER FURNACE 342 CNC 80A 10A 80A EM1 SCHD 9 F (E) ??AF F (E) ??AF (E) ARC MELTER 200A (E) 150AF 200AS 125.3 F NOTES: 1. CONDUCTORS AND CONDUITS SHOWN IN THIS SCHEDULE ARE BASED ON COPPER CONDUCTORS WITH THHN/THWN INSULATION. F 3. EM1 208Y/120V 45 KVA . 125.3 (E) 70.3 (E) PNL EMDP (E) ?? TERM (E) ?? 400.3 (E) ELEC RM ?? 125.4 (E) BASEMENT (E) 30.2 (E) 400.3 . (E) XFR (E) ATS-FIRE PUMP FP-1 ?? (E) (E) FP-1 ?? HP ??? EMERGENCY 400 A 3-POLE ??KAIC ?? FIRE PUMP ROOM (E) 500.4 G1 400.4 (E) (E) DIST 480Y/277V 7.5 KVA (E). PNL DPB G1 ??KAIC PWR ZONE ??KAIC 7. 8. PROVIDE GROUND WIRE NOTED ABOVE IN ALL FEEDERS AND BRANCH CIRCUITS. WHERE MULTIPLE CONDUITS ARE INDICATED PROVIDE NOTED GROUND WIRE IN EACH CONDUIT. 4. NOT ALL FEEDERS ARE NECESSARILY USED ON THIS PROJECT. 5. NOMINAL AMPACITIES GREATER THAN 100 AMPS ARE FOR 75 DEG..C TERMINALS. 9. © 2014 - GLUMAC ALL RIGHTS RESERVED THESE DRAWINGS ARE THE PROPERTY OF GLUMAC ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER, WITHOUT PRIOR WRITTEN PERMISSION OVERSIZED (173% MIN.) NEUTRAL FOR FEEDERS CONNECTED TO A K-4 OR HIGHER RATED TRANSFORMER. Revisions REFER TO TRANSFORMER SCHEDULE FOR STANDARD PRIMARY AND SECONDARY FEEDER SIZES. # Description Date REFER TO MCC OR PANEL SCHEDULES FOR FEEDER SIZES TO EQUIPMENT NOTED WITH THIS TAG. EM1 EMERGENCY 100 A 3-POLE ??KAIC ?? BASEMENT (E) 400.3 THIS SCHEDULE SHALL BE USED ON ALL FEEDERS SERVING LOADS WHERE THE CIRCUIT BREAKER SIZE MATCHES THE AMPACITY OF ITS FEEDER. USE THE "MOTOR CIRCUIT SCHEDULE" FOR LOADS, SUCH AS MOTORS, PUMPS, FANS, CHILLERS, ETC., WHERE THE CIRCUIT BREAKER SIZE IS LARGER THAN THE AMPACITY OF ITS FEEDER. "MET"= EMT, IMC, GRC, RAC, OR PVC COATED GRC TYPE CONDUITS. "RNC"= PVC 40, PVC 80 OR FIBERGLASS TYPE CONDUITS ROUTED UNDERGROUND. REFER TO SIZING ON DRAWINGS IF "RNC" CONDUITS ARE ROUTED ABOVEGROUND. CONDUIT SIZES NOTED ON SINGLE-LINE DIAGRAM OR ON PLANS SUPERSEDE SIZES NOTED ABOVE IF LARGER. (E) ATS (E) FIRE PUMP DISC 400AF F 100.4 (E) 6. 15 ??KAIC ??KAIC 2. . (E) XFR DISC-EM2 125AF 200AS F (E) 20.3 (E) GLEEBLE (E) BREW 580-C 1500 SYSTEM VAC FURNACE 200A 220A (E) BREW 424-C VAC FURNACE 100A 8 (E) 150.4 13 ?? (E) (E) 100A XFR ?? ?? (E) F 200.4 (E) ??KAIC 125.? (E) T2 (E) 200AF 200AS 200.4 (E) 250.? (E) (E) PNL ??KAIC (E) 20.3 SUB-BASEMENT 16 PROVIDE 1" EMT CONDUIT WITH (6) #12 CONDUCTORS OR (6) CONDUCTOR MC CABLE. (2) BLUE FOR GENERATOR START CONTACT, (2) RED FOR ATS IN EMERGENCY POSITION, (2) BROWN AS SPARE. CONNECT AS REQUIRED TO EXISTING ATS CONTACTS. Client GARAGE (E) DIESEL GENSET GEN-1 300KW/ 375KVA @0.8 PF 277Y/480V,3P,4W EMERGENCY 5.41 500AT . 600AF TRANSFORMER SCHEDULE 480V PRIMARY 480Y/277V SECONDARY 208Y/120V SECONDARY WEIGHT KVA C.B. FEEDER GND SHEET TITLE: ELECTRICAL SINGLE-LINE DIAGRAM C.B. FEEDER C.B. FEEDER GND 15 30/3 30.3 30/3 30.4 #8 50/3 50.4 #8 275 30 50/3 50.3 50/3 50.4 #8 100/3 110.4 #8 340 45 70/3 70.3 70/3 70.4 #6 150/3 150.4 #6 475 75 125/3 125.3 125/3 125.4 #2 225/3 225.4 #2 1060 112.5 175/3 175.3 175/3 175.4 #1/0 400/3 400.4 #1/0 1250 150 225/3 225.3 225/3 225.4 #2/0 500/3 500.4 #2/0 2130 225 350/3 350.3 350/3 350.4 #3/0 800/3 800.4 #3/0 2665 300 450/3 450.3 450/3 450.4 #3/0 1000/3 1000.4 #3/0 4190 500 800/3 800.3 800/3 800.4 #4/0 1600/3 1600.4 #4/0 3480 DRAWN BY: Author 750 1200/3 1200.3 1200/3 1200.4 #4/0 2500/3 2500.4 #4/0 3710 CHECKED BY: JJE NOTES: CONTROLS SUB-BASEMENT 1. THIS SCHEDULE APPLIES TO 3-PHASE, 480:480Y/277V AND 480:208Y/120V DRY-TYPE STEP-DOWN TRANSFORMERS ONLY. 2. ON ONE-LINE DIAGRAMS AND SCHEDULES WHERE FEEDERS AND CIRCUIT BREAKERS ARE SHOWN AS "XFR", PROVIDE RESPECTIVE FEEDERS, GROUND CONDUCTORS AND BREAKERS NOTED ABOVE. PROVIDE SECONDARY BREAKER NOTED ABOVE AS MAIN CIRCUIT BREAKER INTEGRAL IN DISTRIBUTION, PANEL AND SWITCH BOARDS, UON. 3. GROUND CONDUCTOR SIZES INDICATED ABOVE SUPERSEDE GROUND CONDUCTORS SHOWN ON FEEDER SCHEDULE. ROUTE COPPER GROUNDING CONDUCTOR TO GROUNDING ELECTRODE PER NEC. PROVIDE BONDING ALSO PER NEC. COMMON LEAD OF LARGEST REQUIRED SIZE MAY BE EMPLOYED TO SERVE MULTIPLE TRANSFORMERS. 4. NOT ALL TRANSFORMER SIZES INDICATED IN THIS SCHEDULE ARE NECESSARILY USED ON THIS PROJECT. SHEET E5.1 5. WEIGHTS INDICATED ABOVE ARE APPROXIMATE, ACTUAL VALUES MAY VARY. CONFIRM WITH SUBMITTAL INFO. JOB NO. 100% CD'S/ PERMIT SET 7/30/14 02.14.00651 7/30/2014 11:19:53 AM As indicated TM C L CENTERLINE OF INNER DOOR WIDTH AS REQUIRED, MIN 5" WIDTH AS REQUIRED, MIN 4" EQUIPMENT GROUND PRIMARY PRIMARY ELECTROSTATIC SHIELD, WHEN PRESENT 1/2" EXHAUST FAN EF-1 TO GROUND BAR AS INDICATED OR MSGB IF NOT INDICATED GROUNDING CONDUCTOR SIZED PER TRANSFORMER SCHEDULE GROUND >173% NEUTRAL 120VAC EXHAUST FAN EF-1 1" 1ST FLOOR-COL. A3 BOND GROUND BAR MAIN BUS SIZE IF MAIN LUGS ONLY OR TRIP RATING OF MAIN BREAKER. 3/16" 1" 1/4" BOND BOX GROUND ADJACENT ADDITIONAL PANEL SECTIONS AS REQUIRED NOTES: GENERAL NOTES: A. DIAGRAM HAS BEEN SIMPLIFIED TO SINGLE PHASE FOR CLARITY. SIMILAR FOR LUMINAIRES 1. SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS. SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS. 2. PROVIDE ONE NAMEPLATE FOR EACH PANEL OR MCC SECTION. WHERE SECTION NUMBER TWO AND ABOVE ARE WITHIN SAME ROOM AND WITHIN 10' OF EACH OTHER USE THE SMALLER SIZE NAMEPLATE. 2. TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS. 3. CENTER ALL TEXT HORIZONTALLY. 4. TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS. 3. CENTER ALL TEXT HORIZONTALLY 120VAC 6 PORTLAND STATE UNIVERSITY NAMEPLATE MOUNTING LOCATION 120VAC PHASE 3/16" 3/16" 3/16" 1. GND PROVIDE ONE PER CIRCUIT 1/4" 3/16" 3/16" CIRCUIT BREAKERS IN DIST. PANELS GROUND Client 3/16" SECTION 2 3/16" NOTES: BRANCH 1/4" USE "BOLD" STYLE TEXT DIST. PANEL CRPP1A1 DESCRIPTION OF LOAD SERVED POWER RECEPTACLE IN STEEL OUTLET BOX -N- 1/4" 5/8" LOCATION OF LOAD STEEL CONDUIT NEUTRAL 1/4" WIDTH AS REQUIRED, MIN 5" TRANSFORMER SECONDARY LESS THAN 10' LONG SUBFEED FED FROM MDS-A 480V, 3P, 3W, 800A, 65KAIC WIDTH AS REQUIRED, MIN 3.5" PANEL ENCLOSURE >173% NEUTRAL 1/4" GENERAL EQUIPMENT DIV 16 TO PROVIDE COPPER GROUND BAR WITH SEPARATE TERMINATIONS FOR EACH CONDUCTOR. MAIN BREAKER 2.5" USE RIVOTS ON DIV. 16 PROVIDED ITEMS IN EXTERIOR LOCATIONS, USE DOUBLE-STICK TAPE ON OWNER FURNISHED ITEMS (DO NOT DRILL HOLES) AND INTERIOR EQUIPMENT BOND TO TRANSFORMER ENCLOSURE TO SUBFEED PANEL WITH SAME CONNECTIONS 3/16" 3/16" 3/16" 3/16" 1/2" 3/8" 1/2" BOND TO NEAREST STRUCTURAL STEEL PER NEC 250 IF REQUIRED BY LOCAL AUTHORITY HAVING JURISDICTION STEEL CONDUIT DIST. PANEL L1A 1/4" FED FROM DS1A1 10 HP., 480V, 3∅ 2" 1/2" 900 SW Fifth Ave., Suite 1600 Portland, OR 97204-2640 T. 503.227.5280 F. 503.274.7674 NOTE: NEUTRAL-GROUND CONNECTION IS MADE WITHIN THE TRANSFORMER ENCLOSURE ONLY K-RATED TRANSFORMER ENCLOSURE TO MSGB Job No.: 02.14.00651 Contact: JJE www.glumac.com USE "BOLD" STYLE TEXT C L engineers for a sust ai nable f uture USE RIVETS NOT DOUBLE-STICK TAPE FOR EXTERIOR LOCATIONS EQUIPMENT IDENTIFICATION NAMEPLATES 3 SCALE: NONE DISTRIBUTION PANEL, MOTOR CONTROL CENTER & BRANCH PANEL NAMEPLATES Project PSU ELEVATOR RECONNECTION TO GENERATOR SCALE: NONE B. NON-K-RATED (K-1) TRANSFORMER WIRING IS THE SAME EXCEPT NEUTRAL (GROUNDED SECONDARY CONDUCTOR) IS NOT OVERSIZED. 7 TRANSFORMER/PANEL/OUTLET/LUMINAIRE WIRING (NON ISOLATED GROUND PANELS) WIDTH AS REQUIRED, MIN. 6" WIDTH AS REQUIRED, 6" MIN. SCALE: NONE TRANSFORMER TRR-1A1 5/16" FIRE ALARM SYSTEM FAJB-1 1.25" 1/4" 2.5" 3 / 16 " 1/4" PRIMARY FED FROM DS1A1 480Y/277V, 3∅, 3W SECONDARY FEEDS PNL RDP1A1 208Y/120V, 3∅, 4W 75 KVA, K-13 RATED 1/4 " PNL??-## 1/4" 1/4" ENGRAVE PANEL NAME AND BRANCH CIRCUIT NUMBER SERVING ENCLOSURE, OMIT ENGRAVING IF ENCLOSURE IS NOT POWERED USE "BOLD" STYLE TEXT. USE WORDS, NOT ABBREVIATIONS, FOR SYSTEM NAMES AND FUNCTION 1/4" 3/16" 3/16" 3/16" 3/16" 3/16" 3/16" 3/16" 3/16" 1/4" USE "BOLD" STYLE TEXT USE RIVOTS NOT DOUBLE-STICK TAPE FOR ALL LOCATIONS USE RIVETS ON DIV. 16 PROVIDED ITEMS IN EXTERIOR LOCATIONS, USE DOUBLE-STICK TAPE ON OWNER FURNISHED ITEMS (DO NOT DRILL HOLES) AND INTERIOR EQUIPMENT NOTES: NOTES: 5 1. REFER TO SPECIFIACTIONS FOR FOR ADDITIONAL INFORMATION AND COLORS FOR DIFFERENT SYSTEMS. 2. PROVIDE ONE NAMEPLATE FOR EACH ENCLOSURE OR J-BOX LARGER THAN 4" 3. CENTER ALL TEXT HORIZONTALLY AND VERTICALLY IF ONLY ONE LINE. 4. TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS. ENCLOSURE INDENTIFICATION NAMEPLATES 2 SCALE: NONE 1. SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS. 2. PROVIDE ONE NAMEPLATE FOR EACH TRANSFORMER. 3. CENTER ALL TEXT HORIZONTALLY. 4. TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS. TRANSFORMER NAMEPLATE SCALE: NONE © 2014 - GLUMAC ALL RIGHTS RESERVED THESE DRAWINGS ARE THE PROPERTY OF GLUMAC ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER, WITHOUT PRIOR WRITTEN PERMISSION NAMEPLATE COLOR LEGEND NAMEPLATE COLOR 1 SERVICE TEXT BACKGROUND 480V NORMAL WHITE BLACK 322-402 208/120V NORMAL WHITE BLACK 322-402 480/277V UPS WHITE ORANGE 122-612 Revisions # USE "BOLD" STYLE TEXT ON POWER CONDUITS SHOW CIRCUIT NUMBERS OF ALL CIRCUITS IN J-BOX. USE 1" WIDE KROY OR BROTHERS LABELING TAPE WITH BLACK 1/2" HIGH HELVETICA BOLD LETTERING ON WHITE BACKGROUND. WIDTH AS REQUIRED, MIN. 8.5" PANEL, MCC, ENCLOSURE, ETC. WHITE ORANGE 122-612 SECURITY BLACK YELLOW 322-704 BMS CONTROLS GREEN WHITE 222-324 FIRE ALARM WHITE RED 322-602 YELLOW BLACK 322-407 GROUND CONDUITS WHITE GREEN 322-992 480/277V EMERGENCY WHITE RED 322-602 208/120V EMERGENCY WHITE RED 322-602 480/277V STANDBY WHITE BLUE 322-542 208/120V STANDBY WHITE 480/277V GENERATOR WHITE BLUE GREEN 322-542 122-932 208/120V GENERATOR WHITE GREEN 122-932 GENERAL NOTES 15KV MEDIUM VOLTAGE WHITE PURPLE 222-582 A. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. CATV/ MATV WHITE AQUA 122-942 B. TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS. C. ROWMARK # IS THE COLOR OF THE PLASTIC ENGRAVING MATERIAL. USE ROWMARK 1/16" ULTRAMATT AND SATIN STOCK AS NOTED. 4 ENGRAVED NAMEPLATES 3/16" ATS-MTLL499 2 3" PANEL MTES0021 FED FROM: XX 10 HP., 480V, 3∅ RACEWAY AND NAMEPLATE IDENTIFICATION SCALE: 1/8" = 1'-0" Date ROWMARK # 208/120V UPS TELECOM Description STN0012-22,24,26 LIFE SAFETY POWER SYSTEM FED FROM: (N)SWBD-MTNL3003 (G)SWBD-MTGL304 SERVES: SWBD-MTLL500 2500A, 480Y/277V, 3P, 4-POLE 65 KAIC 3/8" 3/16" 1/4" 3/16" 1/4" 3/16" 1/4" 3/16" 1/4" 3/16" 1/4" LINE 1 LINE 2 SHEET TITLE: LINE 3 LINE 4 ELECTRICAL DETAILS LINE 5 LINE 6 3/16" NOTES 1. SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS. 2. TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS. REPLACE QUESTION MARKS WITH CORRECT NUMBERS. 3. CENTER ALL TEXT HORIZONTALLY 4. THIS DETAIL APPLIES TO ALL TRANSFER SWITCHES, MANUAL AND AUTOMATIC 5. DRILL HOLES ON EXTERIOR NAMEPLATES ONLY 1 DRAWN BY: LRH CHECKED BY: JJE TRANSFER SWITCH NAMEPLATES SHEET E9.1 SCALE: NONE JOB NO. 100% CD'S/ PERMIT SET 7/30/14 02.14.00651 7/30/2014 11:19:56 AM 1/8" = 1'-0"
© Copyright 2024 ExpyDoc