Appendix 2.2 Electrical Drawings

TM
SYMBOL
DESCRIPTION
SYMBOL
SURFACE MOUNTED 2X4 LUMINAIRE
RECESSED 1X4 LUMINAIRE
SURFACE MOUNTED 1X4 LUMINAIRE
SHADING OF ANY LUMINAIRE INDICATES CONNECTION
TO ALTERNATE POWER SOURCE (EMERGENCY, UPS,
STANDBY, ETC.) PER CIRCUITING INDICATED
"ON ALT."
RECESSED DOWNLIGHT, CEILING MOUNTED
F
FUSED DISCONNECT SWITCH, SIZE AS NOTED. SIZE
FUSE PER MANUFACTURER'S RECOMMENDATIONS
C
ENCLOSED CIRCUIT BREAKER DISCONNECT
SWITCH, TRIP SIZE AS NOTED.
SURFACE DOWNLIGHT, CEILING MOUNTED
WW DIRECTION
WW DIRECTION
SURFACE WALLWASH
RECESSED LINEAR WALLWASH
SURFACE LINEAR WALLWASH
RECESSED CEILING ADJUSTABLE POINT SOURCE
SURFACE CEILING ADJUSTABLE POINT SOURCE
EQUIPMENT OR TERMINAL ENCLOSURE AS NOTED,
SURFACE AND RECESS MOUNTED
WALL MOUNTED LUMINAIRE
BUILDING GROUND BUS, SEE DETAILS
DM
WALL MOUNTED DIRECTIONAL (SIZE VARIES)
GFI
C
F
+42"
BUSWAY RISER
POKE THRU UNIT WITH DOUBLE DUPLEX
RECEPTACLE - FLUSH, PEDESTAL MOUNTED.
BUSWAY STAB-IN TYPE CIRCUIT BREAKER
OR FUSE DISCONNECT. SIZE AS NOTED.
J
OVERLOADS
INDICATES ROTATED OPTICS
POST TOP MOUNTED LUMINAIRE
NORMALLY CLOSED CONTACTOR OR RELAY
CONTACTS
IN-GRADE POINT SOURCE
NORMALLY OPEN CONTACTOR OR RELAY CONTACTS
J
J
GARAGE LIGHTING LUMINAIRE WITH CUTOFF LOUVERS
BUS DUCT
LUMINAIRE MARKING CONVENTION LEGEND:
HA = LUMINAIRE TYPE IDENTIFICATION. SEE
LUMINAIRE SCHEDULE.
3c = CIRCUIT NUMBER VIA LOCAL SWITCH
(LOWERCASE LETTER) THAT SERVES
THE LUMINIARE.
3A = CIRCUIT NUMBER/UPPERCASE LETTER
COMBINATION INDICATES LOW VOLTAGE
RELAY OR LIGHTING CONTACTOR THAT
SERVES THE LUMINAIRE
BUS BAR
CONNECTOR, FEMALE AND MALE RESPECTIVELY
R
Sa
D
TVSS
S3
THREE WAY SWITCH
NORMALLY OPEN PUSH BUTTON
S4
FOUR WAY SWITCH
SK
KEY OPERATED SWITCH
D
DIMMER SWITCH. NUMBER INDICATES WATTAGE
RATING. IF NOT SHOWN THEN EQUAL TO LOAD.
S 5A,5B S 5C
EXPLOSION PROOF SWITCH
SWP
WEATHERPROOF SWITCH
SV
LINE VOLTAGE, VARIABLE SPEED FAN CONTROL
SWITCH, PROVIDED BY DIV. 15, INSTALLED
BY DIV. 16. LOCATE ADJACENT TO ADJACENT
TO LIGHT SWITCHES.
MOTOR-RATED THERMAL OVERLOAD SWITCH
SOR1
LIGHTING CONTROL OVERIDE SWITCH, SEQ. NUMBER
C
EQUIPMENT OPERATOR PUSH BUTTON STATION.
PROVIDED WITH EQUIPMENT, INSTALLED AND
CONNECTED BY DIV. 16, UON.
STB
TC
TIME CLOCK
OS
OCCUPANCY SENSOR - WALL MOUNTED
OS
360 DEGREE OCCUPANCY SENSOR - CEILING MTD.
OS
180 DEGREE OCCUPANCY SENSOR - CEILING MTD.
OS
CORRIDOR/AISLE OCCUPANCY SENSOR - CEILING
MOUNTED
COMBINATION OCCUPANCY SENSOR & SWITCH
GANGED UNDER A COMMON COVER PLATE.
OCCUPANY SENSOR TO CONTROL ALL LUMINAIRES IN
ROOM WITH 1/2 LIGHT REDUCTION CONTROLLED BY
SWITCH, DESIGNATED BY LETTER. 2-GANG BOX WITH
SINGLE-GANG MUDRING, UON SPECIFIED
THERMOSTAT - WALL, CEILING. PROVIDED BY DIV.
15, INSTALLED AND WIRED BY DIV. 16
T
LCP ?
LIGHTING CONTROL PANEL AND ASSOCIATED
COMPONENTS. PROVIDE 120V OR 277V CONTROL
POWER AS REQUIRED OR AS INDICATED.
M
R/C,F,R
HEAT DETECTOR (R/C=RATE OF COMBUSTION,
F=FIXED TEMP. ONLY, R=RATE OF RISE ONLY)
EARLY WARNING SMOKE DETECTION SYSTEM INCLUDES ALL PIPING BY DIV. 16.
LIGHT (LAMP, SIGNAL LIGHT,
INDICATOR LAMP, STROBE)
FIRE ALARM OUTPUT OR RELEASE ABORT
PUSHBUTTON, REFER TO SPECIFICATIONS AND
DETAILS.
AGENT RELEASE INITIATING VALVE
BELL SILENCE SWITCH
AGENT DISCHARGE SWITCH
POWER CONNECTION TO DIV 15 FIRE/SMOKE DAMPER.
REFER TO FSD CONNECTION DETAIL IF NOT SHOWN
SECURITY SYSTEM
SYSTEM CLOCK - WALL , CEILING
I
M
M
DIGITAL METER UNIT. REFER
TO SPECIFICATIONS.
SYMBOL
INTERCOM STATION - WALL, DESK
M = MASTER STATION
CCTV SECURITY INDOOR DOME CAMERA
D
MICROPHONE JACK - WALL, FLOOR
CCTV SECURITY PAN/TILT/ZOOM CAMERA
PTZ
MRIB
PUSHBUTTON OR PUSHBUTTONS
RF COAX CABLE OUTLET (TV, VCR, ETC.)
TERMINAL FOR FIELD CONNECT, SIZE & TYPE
SUITABLE FOR CONDUCTOR INSTALLED.
COMBINATION RF COAX CABLE AND DATA OUTLET
RF COAX CABLE SIGNAL SPLITTER
INTELLIGENT CARD READER INTERFACE
ROLL-UP DOOR MOTOR CONTROL OUTPUT
MO
DOOR POSITION MONITOR SWITCH
D
RX
RX
I
I
FLUSH FLOOR DEVICE - DEVICE TYPE PER
SYMBOLS ABOVE
CIRCUIT BREAKER, WITH TRIP & FRAME AMPERE
RATING
225AF
400AS
FUSED SWITCH, WITH FUSE AND SWITCH AMPERE
RATING
PA
S D
S D
INDIVIDUALLY MOUNTED CIRCUIT BREAKER
52
GF
CIRCUIT BREAKER, MEDIUM VOLTAGE, DRAWOUT
DRAWOUT CIRCUIT BREAKER
GROUND FAULT TRIP UNIT
BA
BELL ALARM TRIP MODULE CONTACTS
ST
SHUNT TRIP UNIT, 120VAC OR VOLTAGE AS NOTED
CM
MONITORING COMMUNICATION MODULE
AM
INTEGRAL AMMETER DISPLAY
K
KEY INTERLOCK
MECHANICAL INTERLOCK
10
CAPACITOR, POWER FACTOR CORRECTION, SIZE
IN KVAR
GENERATOR
FUSE, HOLDER & PULLER
C
CONNECTION TO DIV. 15 CHILLER
CR
PEDESTAL FLOOR DEVICE - DEVICE TYPE PER
SYMBOLS ABOVE
S
SYMBOL
G
GC
DESCRIPTION
BARE GROUNDING GRID OR CONDUCTORS, UON.
GROUNDING CONDUCTOR(S) ROUTED IN CODE SIZED
CONDUIT, UON.
GROUND GRID BOND POINT
GROUND GRID BOND POINT - MECHANICAL
CONNECTION
GROUND GRID BOND POINT - EXOTHERMIC
WELD CONNECTION
REQUEST TO EXIT DEVICE WALL,MULLION MOUNTED
INTERCOM STATION - WALL, DESK MOUNTED.
M = MASTER STATION
60" GROUND BAR
GROUND ROD LOCATION
GROUND ROD IN TEST WELL
DURESS PUSHBUTTON STATION
DS
CONNECTION TO GROUND
100AT
225AF
GROUNDING SYSTEM
24" GROUND BAR
RF COAX CABLE DISTRIBUTION AMPLIFIER.
PROVIDE 120V POWER AS REQUIRED OR AS
INDICATED. SEE RISER DIAGRAM.
GROUNDED WYE CONNECTION
DESCRIPTION
CCTV SECURITY FIXED CAMERA - WALL,CEILING
CURRENT TRANSFORMER SHORTING TERMINAL BLOCK.
SOLENOID
REMOTE MOUNTED LINE TO LOW-VOLTAGE FUSED
TRANSFORMER. CONCEAL FROM VIEW.
HEAT DETECTOR, CEILING MOUNTED. RATE OF
RISE AND FIXED TEMPERATURE TYPE, UON.
UNDERFLOOR RACEWAY
FLEXIBLE CONDUIT CONNECTION
M
EMERGENCY POWER OFF, HEAVY-DUTY, OIL-TIGHT
RED MUSHROOM-HEAD PUSHBUTTON W/ GUARD.
EPO
I
UTILITY CO. APPROVED SOCKET WITH METER
INSTALLED. SQUARE = REMOTE MOUNTED
C
LED INDICATOR LIGHT, PUSH TO TEST, R=RED
G= GREEN, B= BLUE, Y= YELLOW, W= WHITE
PUSHBUTTON OR PUSHBUTTONS, BY DIV. 16
b OSa
METER: KILOWATT HOUR
M
PHOTOCELL
PC
FLAME DETECTOR (FLICKER DETECTOR)
BUZZER
DELTA CONNECTION
ST
PB
P
METER: POWER FACTOR
DMU
SXP
BELL
FIRE/SMOKE DAMPER BY DIV 15. WIDTH OF
SYMBOL WILL VARY WITH DUCT WIDTH. PROVIDE
POWER AND MONITORING AS INDICATED.
REFER TO FSD CONNECTION DETAIL.
WIRING EXTENSION POINT - CONDUIT TO MC CABLE
OR MANUFACTURED WIRING SYSTEM J-BOX ABOVE
ACCESSIBLE CEILINGS AREAS, OR EXTEND CONDUIT &
WIRE IN EXPOSED OR "HARD" CEILING AREAS.
SHADED= ON ALT. POWER SOURCE (EMERG,UPS,ETC.)
PULL BOX, MIN. SIZE PER NEC., UON.
CHIME
PF
SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN
SWITCH IS "OFF").
LOW VOLTAGE MOMENTARY CONTACT SWITCH,
UPPER CASE LETTER SUPERSCRIPT INDICATES
CONNECTION TO LOW VOLTAGE RELAY
CONTROLLING SIMILARLY MARKED LUMINAIRES.
B
FIREMAN'S PHONE HANDSET, WALL MOUNTED
JUNCTION BOXES, WALL, CEILING AND FLUSH FLOOR
MOUNTED. 4" SQ. BOX MIN., LARGER IF REQUIRED
J
SPEAKER - WALL, CEILING
VOLUME CONTROL - WALL
FIREMAN'S PHONE JACK, WALL MOUNTED
LADDER TYPE CABLE TRAY WITH 90 DEGREE ELBOW
SHOWN
TELEPHONE OUTLET - WALL, W = USE HIGHER
MOUNTING HEIGHT PER MOUNTING HT. DETAIL
V
FUSED VOLTAGE SENSE LEADS
M
S 5A
S
END OF LINE RESISTOR (NOT SHOWN ON PLANS)
NORMALLY CLOSED PUSH BUTTON
SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN
SWITCH IS "ON").
TIMER SWITCH
TX
S
ADDRESSABLE CONTROL MODULE
BASKET TYPE CABLE TRAY WITH 90 DEGREE ELBOW
SHOWN
CURRENT TRANSFORMER
KWH
T
W
DIMMER SWITCH UNDER SEPARATE COVERPLATE
STS
TELEPHONE/DATA SLEEVE THROUGH WALL, ABOVE
CEILING. EXTEND TO ACCESSIBLE TILE CLG. BOTH
SIDES. TERMINATE WITH BUSHINGS. (1) 1.25" CO
UON. COORDINATE LOCATIONS WITH CABLE
INSTALLER(S) PRIOR TO ROUGH-IN.
DATA OUTLET - WALL
POTENTIAL TRANSFORMER
SPL
CONDUIT STUBBED OUT AT LOCATION SHOWN.
PROVIDE INSULATED BUSHING & PULLROPE.
COMBO TELEPHONE/DATA OUTLET - WALL
TRANSIENT VOLTAGE SURGE SUPPRESSOR
S2
SP
TWO OR THREE COMPARTMENT SURFACE METAL
RACEWAY WITH RECEPTACLES AND OUTLETS AS
INDICATED, LENGTH AS INDICATED ON THE
DRAWINGS. PROVIDE ALL FITTINGS AS
REQUIRED.
J J
ELECTROMAGNETIC DOOR HOLDER - WALL, FLOOR,
DOOR CLOSURE MOUNTED. PROVIDED BY DIV. 8
UON.
DATA LOOP ISOLATION MODULE
CONDUIT RUN TURNED DOWN THROUGH FLOOR OR
CEILING. CORE & FIREPROOF AS REQUIRED.
SIGNAL SYSTEM EQUIPMENT ENCLOSURES AS NOTEDSURFACE, RECESSED MOUNTED
LIGHTNING SURGE ARRESTOR D= DISTRIBUTION
CLASS I = INTERMEDIATE CLASS
C
HOME RUN WIRING TO INDICATED DESTINATION,
3/4"C. MIN. OR AS OTHERWISE NOTED. CONTRACTOR
SHALL USE CIRCUIT SIZES NOTED IN RESPECTIVE
SCHEDULES AND INFORMATION IN THE FEEDER AND
BRANCH CIRCUIT SCHEDULES.
CONDUIT RUN TURNED UP THROUGH FLOOR OR
CEILING. CORE & FIREPROOF AS REQUIRED.
TERMINAL/MOUNTING BOARD, 8' HIGH X WIDTH AS
SHOWN, FIRE TREATED.
RELAY COIL
SINGLE POLE SWITCH (SUPERSCRIPT DENOTES
SIMILARLY MARKED LUMINAIRES CONTROLLED
TOGETHER)
TWO POLE SWITCH
D
L1A-1,3
HD1A
DESCRIPTION
CONTACTOR COIL
SMOKE DETECTOR MOUNTED BELOW RAISED FLOOR
NEUTRAL
TWO-PIECE SURFACE METAL RACEWAY WITH
RECEPTACLES AS NOTED, LENGTH AS
INDICATED ON THE DRAWINGS AND WITH ALL
FITTINGS AS REQUIRED.
SYMBOL
P,B,R,C
SMOKE DETECTOR - WALL, CEILING MOUNTED
(P=PLENUM MOUNTED, B=W/RELAY BASE,
R=ELEVATOR RECALL, C=INTEGRAL TO DOOR
CLOSURE)
ADDRESSABLE MONITOR MODULE
GROUND
HOT
SIGNAL DEVICES
PIPE GROUND
C
DESCRIPTION
GC
BATTERY GENERAL
RESISTOR
SMOKE DETECTOR, LOW AIR VELOCITY IN DUCT
MOUNTED PHOTOELECTRIC TYPE U.O.N.
BARE GROUNDING GRID OR CONDUCTORS, UON.
GROUNDING CONDUCTOR(S) ROUTED IN CODE SIZED
CONDUIT, UON.
STROKES INDICATE QUANTITY OF #12 AWG.
CONDUCTORS, UON. NOTE: WIRING STROKES FOR
20A BRANCH CIRCUITS ARE NOT SHOWN ON
DRAWINGS. CONTRACTOR SHALL USE INFORMATION
IN PANEL AND BRANCH CIRCUIT SCHEDULES TO
PROVIDE REQUIRED CIRCUITING.
G
TELE/POWER POLE WITH WHIP CONNECTION TO
ELECTRIFIED FURNITURE
J
D
TELEPHONE SYSTEM CONDUIT
MEDIUM VOLTAGE CONDUIT
TELE/POWER POLE, POWER POLE
J
SMOKE DETECTOR, DUCT MOUNTED, WITH FULL
WIDTH SAMPLING TUBES. PHOTOELECTRIC TYPE
UON.
(F) FUTURE WORK
POKE THRU UNIT WITH JUNCTION BOX.
RACEWAY COMPONENTS RC-700 SERIES.
J
LIGHT BEAM TYPE SMOKE DETECTOR (BR=BEAM
RECEIVER, BT=BEAM TRANSMITTER)
(D) EXISTING WORK TO BE REMOVED
MULTI-SERVICE FLOOR BOX CAST IN CONC. OR
IN RAISED FLOOR - SEE ARCH DWGS; WITH
RECEPTACLES & SIGNAL OUTLETS AS NOTED.
J
SPRINKLER FLOW SWITCH CONNECTION
(E) EXISTING WORK TO REMAIN
COMBO POKE THRU UNIT WITH DUPLEX
RECEPTACLE AND TELEPHONE OUTLET - FLUSH,
PEDESTAL MOUNTED.
DESCRIPTION
DESCRIPTION
NEW WORK
T
COMBINATION MINI HORN/STROBE - WALL, CEILING
MOUNTED (# = CANDELA RATING)
SPRINKLER VALVE TAMPER SWITCH CONNECTION
WIRING CONCEALED IN FLOOR OR UNDER GRADE
OR ROUTED IN CEILING SPACE OF FLOOR BELOW.
DAMPER MOTOR
COMBINATION HORN/STROBE - WALL, CEILING
MOUNTED (# = CANDELA RATING)
MINI HORN - WALL, CEILING MOUNTED
EQUIPMENT BY OTHERS IDENTIFICATION TAG
SYMBOL
PEDESTAL FLOOR DEVICE - DEVICE TYPE PER
SYMBOLS ABOVE
FIELD INSTALLED CONTROL CIRCUIT WIRING
TO DESTINATION SHOWN, U.O.N.
15
WIRING
FLUSH FLOOR BOX DEVICE - DEVICE TYPE PER
SYMBOLS ABOVE
SWITCH
POLE MOUNTED LUMINAIRE- SINGLE OR DUAL HEAD
SYMBOL
EQUIP NAME
COMBINATION SPEAKER/STROBE, WALL MOUNTED
(# = CANDELA RATING)
HORN - CEILING, WALL MOUNTED
MECHANICAL EQUIPMENT IDENTIFICATION TAG
CLOCK HANGER RECEPTACLE
HAND/OFF/AUTO SWITCH
BOLLARD
SWITCHING CONTROLS
KITCHEN EQUIPMENT REFERENCE, REFER TO KITCHEN
EQUIPMENT SCHEDULE
CH
1
STROBE LIGHT - WALL, CEILING MOUNTED
(# = CANDELA RATING)
SPEAKER - WALL, CEILING MOUNTED
15
WALL MOUNTED ELECTRICAL CONNECTION TO
ELECTRIFIED FURNITURE. PROVIDE 8 WIRES
(4 HOTS, 1 DEDICATED NEUTRAL, 1 COMMON
NEUTRAL, 1 ISOLATED GROUND) NEUTRALS
TO BE #10 AWG. USE LIQUID-TIGHT FLEX.
J
POKE THRU UNIT WITH DUPLEX RECEPTACLE FLUSH, PEDESTAL MOUNTED.
SYMBOL
ILLUMINATED EXIT SIGN, SHADED QUADRANT
INDICATES FACES, ARROWS AS SHOWN
3A
SECTION TAG: REFER TO SECTION NUMBER ON
DRAWING INDICATED
3
E4.1
RECEPT. TYPE SHOWN AT SPECIAL HEIGHT
DIAGRAMS
CONTINUOUS LINEAR SOURCE (LED, COLD CATHODE,
NEON, FIBER OPTIC, ETC...)
3c
30
K112
RECEPT. TYPE SHOWN W/ WEATHERPROOF COVER
AND INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER
WP
UNDERCABINET FLUORESCENT STRIPLIGHT
BATTERY POWER EMERGENCY UNIT EQUIPMENT (SEE
LUMINAIRE SCHEDULE FOR QUANTITY OF HEADS) WALL, CEILING MOUNTED.
ALARM BELL OR GONG
MV
FLUORESCENT STRIPLIGHT - POWER FEED SECTION,
FEED THROUGH SECTION. LENGTH AS SHOWN.
WALL MOUNTED FLUORESCENT STRIPLIGHT
ELEVATION TAG: REFER TO ELEVATION NUMBER ON
DRAWING INDICATED
DUPLEX RECEPTACLE - WALL - WITH INTEGRAL
GROUND FAULT CIRCUIT INTERRUPTER
DIV. 16 CONNECTION TO EQUIPMENT WITH
INTEGRAL DISCONNECT THAT IS PROVIDED BY
OTHERS. SHADED = ON ALT. POWER SOURCE NOTED
TRACK LIGHTING WITH HEADS AS INDICATED.
2
E4.1
FIRE ALARM SYSTEM MANUAL PULL STATION,
WALL MOUNTED
COMBINATION SWITCH/DUPLEX RECEPTACLE
DIV. 16 CONNECTION TO EQUIPMENT PROVIDED BY
OTHERS. SHADED = ON ALT. POWER SOURCE NOTED
RECESSED WALL MOUNTED LUMINAIRE
FIRE ALARM SYSTEM ANNUNCIATOR
FIRE ALARM CONTROL PANEL AND ASSOCIATED
COMPONENTS. PROVIDE 120V POWER AS REQUIRED
OR AS INDICATED.
15
DISCONNECT W/ MAGNETIC MOTOR STARTER
(CONTROLLER) OR CONTACTOR. SIZE PER
LOAD SERVED. NEMA SIZE #1 MINIMUM.
MAGNETIC MOTOR STARTER (CONTROLLER)
OR CONTACTOR. SIZE PER LOAD SERVED.
NEMA SIZE #1 MINIMUM.
RECESSED WALLWASH
REFER TO DETAIL NO. ON DRAWING INDICATED
NOT ALL DETAIL REFERENCES ARE SHOWN. ALL
DETAILS APPLY TO ALL APPLICABLE SITUATIONS, UON.
DUPLEX RECEPTACLE - WALL - HALF SWITCHED
S
SUSPENDED PENDANT LUMINAIRE (SIZE VARIES)
DISCONNECT SWITCH, SIZE AS NOTED OR IF NOT
SHOWN SIZE PER CONNECTED MOTOR SIZE AND
MOTOR DISCONNECT SCHEDULE
WALL MOUNTED LINEAR LUMINAIRE (SIZE VARIES)
1
E4.1
SHADED RECEPTACLES NOTED "ON ALT." ABOVE ARE
CONNECTED TO ALTERNATE POWER SOURCE (EMERG.,
STANDBY, UPS, ETC.) PER CIRCUITING INDICATED
CONNECTION TO DIV. 15 FURNISHED VARIABLE
FREQUENCY DRIVE WITH INTEGRAL DISCONNECT
DIV. 16 TO INSTALL VFD EQUIPMENT
VFD
BRANCH CIRCUIT OR FEEDER NOMINAL AMPACITY &
TYPE; REFER TO BRANCH CIRCUIT AND FEEDER
SCHEDULES FOR WIRE AND CONDUIT SIZES & QTY.
RECEPTACLE TYPE SHOWN -WALL -ABOVE COUNTER
BACKSPLASH. SEE ARCHITECTURAL DRAWINGS.
CONNECTION TO MOTOR PROVIDED BY OTHERS
SUSPENDED LINEAR LUMINAIRE (SIZE VARIES)
125.4
TRANSFORMER WITH CODE CLEARANCES SHOWN
SERVICE AND/OR DISTRIBUTION EQUIPMENT
WITH CODE CLEARANCES SHOWN
SHEET NOTE REFERENCE
DESCRIPTION
DUPLEX RECEPTACLE - WALL, CEILING, ON ALT.
SPECIAL PURPOSE RECEPTACLE -WALL, CEILING
ON ALT. POWER; NEMA CONFIGURATION AS NOTED
AB
SYMBOL
12
DOUBLE DUPLEX RECEPTACLE - WALL, CLG, ON ALT.
L5-15R
DESCRIPTION
FIRE ALARM SYSTEM
SIMPLEX RECEPTACLE - WALL, CEILING, ON ALT.
MOTOR CONTROL CENTER W/ CODE CLEARANCES
SHOWN, DASHED EQUIP. = FUTURE
RECESSED 2X2 LUMINAIRE
SURFACE MOUNTED 2X2 LUMINAIRE
SYMBOL
DESCRIPTION
BRANCH CIRCUIT PANELBOARDS, SURFACE AND
RECESS MOUNTED
RECESSED 2X4 LUMINAIRE
REFERENCE SYMBOLS
CR
CARD READER- WALL MOUNTED/MULLION MOUNTED
LIGHTNING PROTECTION PARAPET MOUNTED AIR
TERMINAL
LIGHTNING PROTECTION MID ROOF MOUNTED
AIR TERMINAL
ER
EMERGENCY DOOR RELEASE BREAK-GLASS STATION
PAGING SYSTEM HORN (OUTDOOR)
N
LOCAL DOOR MONITOR WARNING NOISE DEVICE
DUAL COIL SPEAKER - SURFACE CEILING,
RECESSED CEILING.
EB
ELECTRIC BOLT
LIGHTNING PROTECTION CONDUCTOR ROUTED DOWN
EL
ELECTRIC LOCK/LATCH
LIGHTNING PROTECTION BOND PLATE
ES
ELECTRIC STRIKE
LIGHTNING PROTECTION BIMETAL CONNECTION
ML
MAGNETIC LOCK
GB
GLASS BREAK SENSOR
H
ELECTRIC POWER TRANSFER HINGE
S
PAGING OR PAGING/SOUND MASKING SPEAKER,
MOUNTED ABOVE ACOUSTIC TILE CEILING.
AV
AV INPUT OUTLET, 1"C WITH 3-GANG BOX. CONDUIT
STUBBED ABOVE ACCESSIBLE TILE CEILING.
IR
ASSISTIVE LISTENING INFRARED TRANSMITTER PANEL,
1"C WITH 2-GANG BOX. CONDUIT STUBBED ABOVE
ACCESSIBLE TILE CEILING.
LIGHTNING PROTECTION AIR TERMINAL
SECURITY ELECTRONIC MOTION SENSOR
ELECTRICAL EQUIPMENT NAMING CONVENTION LEGEND
EXAMPLES / LEGEND
MCCDP-
U
XFR-
EQUIPMENT TYPE
H
M
1
A
L
D
1
A
H
L
1
A
SWBD-
M
H
SN
1
A
PNL-
E
H
K
2
B
POWER
ADDN'L
SEQ.
SYSTEM
DESIG.
LETTERS
DESIG.
EQUIP.
SYSTEM
FLOOR
TYPE
VOLTAGE
SUB - UNIT SUBSTATION
SWBD - SWITCHBOARD
SWGR - SWITCHGEAR
DP - DISTRIBUTION PANEL
PNL - BRANCH PANEL
ATS - AUTOMATIC TRANSFER SWITCH
BIATS - BYPASS ISOLATION ATS
MTS - MANUAL TRANSFER SWITCH
XFR - TRANSFORMER
UTX - UTILITY MAIN TRANSFORMER
MCC - MOTOR CONTROL CENTER
CB - ENCLOSED CIRCUIT BREAKER
FSW - FUSED DISCONNECT SWITCH
DSW - NON-FUSED DISCONNECT SW.
POWER SYSTEM
BLANK - NORMAL LOADS
M - MAIN UTILITY SERVICE
EM - EMERGENCY POWER (Life Safety)
S - STANDBY POWER
(E)
(F)
(R)
(RL)
AB
ACU
AC
A, AMP
AF
AFF
AFG
AIC
EXISTING TO REMAIN
FUTURE
EXISTING TO BE REMOVED
EXISTING TO BE RELOCATED
ABOVE COUNTER BACKSPLASH
AIR CONDITIONING UNIT
ALTERNATING CURRENT
AMPERES
AMPERE (RATED) FUSE OR CB FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
EQUIPMENT SHORT CIRCUIT INTERRUPT
RATING (RMS SYM. AMPS)
AL
ALUMINUM (ALLOY)
ALC
AUTOMATIC LIGHTING CONTROL
AS
AMPERE (RATED) SWITCH
AT
CIRCUIT BRKR TRIP SETTING (AMPS)
ATS
AUTOMATIC TRANSFER SWITCH
AUTO
AUTOMATIC
AUX
AUXILIARY
AWG
AMERICAN WIRE GAUGE
BAT
BATTERY
BG
BELOW GRADE
BRKR
CIRCUIT BREAKER
C
CONDUIT (CIRCULAR RACEWAY)
CAB
CABINET
CB
CIRCUIT BREAKER
CFM
CUBIC FEET PER MINUTE
CKT
CIRCUIT
CLG
CEILING
CO
CONDUIT ONLY
CPT
CONTROL POWER TRANSFORMER
CT
CURRENT TRANSFORMER
CU
COPPER
DC
DIRECT CURRENT
DISC
DISCONNECT
DIA
DIAMETER
DIV
DIVISION
DP
DISTRIBUTION PANEL
DPDT
DOUBLE POLE DOUBLE THROW
DPST
DOUBLE POLE SINGLE THROW
DWG
DRAWING
E,EMERG EMERGENCY
EF
EXHAUST FAN
EMT
ELECTRICAL METALLIC TUBING
ENCL
ENCLOSURE
EO
ELECTRICALLY OPERATED
EOL
END OF LINE
EWC
ELECTRIC WATER COOLER
EWH
ELECTRIC WATER HEATER
FA
FIRE ALARM
FAA
FIRE ALARM ANNUNCIATOR
FBO
FURNISHED BY OTHERS
FC
FOOT CANDLES
FF
FLUSH FLOOR MOUNTED
FLA
FULL LOAD AMPERES
FLEX
FLEXIBLE
FPB
FAN POWERED BOX
FSD
FIRE/SMOKE DAMPER
FW
FLUSH WALL MOUNTED
FU
FUSE
GEN
GENERATOR
GFI
GROUND FAULT CIRCUIT INTERRUPTER
GND
GROUND
GRAP
GENERATOR REMOTE ANNUNCIATOR PNL
GRC
GALVANIZED RIGID STEEL CONDUIT
HLO
HANDLE LOCK-ON(OFF)
HP
HORSEPOWER
HPF
HIGH POWER FACTOR
HTR
HEATER
HZ
HERTZ (CYCLES PER SECOND)
IES
ILLUMINATING ENGINEERING SOCIETY
IBC
INDIVIDUAL BRANCH CIRCUIT
ID
INSIDE DIAMETER
IG
ISOLATED GROUND
IMC
INTERMEDIATE METAL CONDUIT
KCMIL
THOUSAND CIRCULAR MILS
KO
KNOCK OUT
KW
KILOWATTS
KVA
KILOVOLT-AMPERES
LTG
LIGHTING
LCP
LIGHTING CONTROL PANEL
MAX
MAXIMUM
MCA
MINIMUM CIRCUIT AMPERES
MFR
MANUFACTURER
MIN
MINIMUM
MISC
MISCELLANEOUS
MLO
MAIN LUGS ONLY
MO
MANUAL OPERATOR
MTD
MOUNTED
MTR
MOTOR
-NNEUTRAL (GROUNDED CONDUCTOR)
NC
NORMALLY CLOSED
NEC
NATIONAL ELECTRICAL CODE
-,NEG
NEGATIVE
NEMA
NATIONAL ELECTRICAL MFGR'S ASSOC.
NL
NIGHT LIGHT (UNSWITCHED)
NO
NORMALLY OPEN
NTS
NOT TO SCALE
NP
NAMEPLATE
OC
ON CENTER
OD
OUTSIDE DIAMETER
OFCI
OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI
OWNER FURNISHED, OWNER INSTALLED
OS
OCCUPANCY SENSOR
P
POLE
PB
PUSHBUTTON
PH, Ø
PHASE
PNL
PANEL
+,POS
POSITIVE
PRI
PRIMARY
REQD
REQUIRED
RNC
RIGID NON-METALLIC CONDUIT (PVC)
RS
RAPID START
RST
REMOTE STATION TRANSMITTER
S.A.D.
SEE ARCHITECTURAL DRAWINGS
SEC
SECONDARY
SN
SHEET NOTE
SOL
SOLENOID
SPDT
SINGLE POLE DOUBLE THROW
SPST
SINGLE POLE SINGLE THROW
SUB
SUBSTATION
SWBD
SWITCHBOARD
SWGR
SWITCHGEAR
TB
TERMINAL BOARD
TDC
TIME DELAY CLOSING
TDO
TIME DELAY OPENING
TEL
TELEPHONE
TYP
TYPICAL
UL
UNDERWRITERS LAB
UON
UNLESS OTHERWISE NOTED
UPS
UNINTERRUPTIBLE POWER SUPPLY
UTX
UTILITY TRANSFORMER
V
VOLTS
VA
VOLT-AMPERES
VFD
VARIABLE FREQUENCY DRIVE
W
WATT
W/
WITH
W/O
WITHOUT
WP
WEATHERPROOF, SEE RECEPT. SYMBOL
XFR
TRANSFORMER
XP
EXPLOSION PROOF
Z
ZONE
", IN
INCHES
', FT
FEET
Ø
PHASE
>
GREATER THAN
<
LESS THAN
>
GREATER THAN OR EQUAL TO
ELECTRICAL DESIGN CRITERIA
1.
2.
3.
4.
OREGON ELECTRICAL SPECIALTY CODE (OREGON AMENDED VERSION OF 2014 NATIONAL
ELECTRIC CODE)
.
FIRE/LIFE SAFETY CODE: 2007 IFC WITH OREGON AMMENDMENTS
.
2010 STATE OF OREGON STRUCTURAL SPECIALTY CODE: OREGON AMMENDED VERSION OF
2009 IBC
.
AMERICANS WITH DISABILITIES ACT, (ADA)
.
Job No.: 02.14.00651
Contact: LRH
www.glumac.com
DESCRIPTION
DISTRIBUTION & EQUIPMENT
ABBREVIATIONS
900 SW Fifth Ave., Suite 1600
Portland, OR 97204-2640
T. 503.227.5280 F. 503.274.7674
SYMBOL
ELECTRICAL LEGEND
POWER DEVICES
engineers for a sust ai nable f uture
LIGHTING
REFER TO DETAILS FOR MOUNTING HEIGHTS OF DEVICES
NOT ALL SYMBOLS, ABBREV., ETC. ARE NECESSARILY USED ON THIS PROJECT
Client
ELECTRICAL BASIS OF DESIGN
1.
2.
3.
4.
5.
THE EXISTING OLD GENERATOR, LOCATED IN THE PENTHOUSE AND SERVING THE
BUILDING'S ELEVATORS, WAS REMOVED. THIS PROJECT IS TO RECONNECT THE
EXISTING ATS SERVING THE ELEVATORS TO THE RECENTLY ADDED GENERATOR
LOCATED IN THE SUB-BASEMENT.
.
DUE TO SELECTIVE COORDINATION REQUIRMENTS OF THE 2014 NATIONAL ELECTRIC
CODE, THE EXISTING PENTHOUSE EMERGENCY PANEL EM2 WAS REPLACED WITH A
FUSED PANELBOARD AND ONLY ONE ELEVATOR CAN BE OPERATED WHILE OPERATING
ON THE GENERATOR.
.
PSU HAS CONFIRMED THAT THE ELEVATOR CONTROLLER IS LAREADY PROGRAMMED
TO ALLOW ONLY ONE ELEVATOR TO OPERATE AT ONE TIME WHILE ON EMERGENCY
POWER.
.
SOME WALLS WILL NEED TO BE REMOVED TO ALLOW ACCESS TO THE EXISTING
CONDUIT RISER THAT IS PART OF THIS PROJECT. THE OWNER WILL PROVIDE DEMO
AND PATCHING OF THOSE WALLS. FIRE AND WATER PROOFING OF ANY NEW FLOOR OR
FIRE RATED WALL PENETRATIONS ARE PART OF THE ELECTRICAL CONTRACTORS
SCOPE OF WORK.
.
SHORT CIRCUIT FAULT CURRENT CALCULATIONS AND A COORDINATION STUDY OF
BREAKERS AND FUSES WERE PERFORMED.
PORTLAND STATE
UNIVERSITY
Project
PSU ELEVATOR
RECONNECTION TO
GENERATOR
ELECTRICAL ADD ALTERNATES
1.
2.
ELECTRICAL CONTRACTOR TO PROVIDE COST OPTION TO REPLACE AND
RECONNECT EXISTING PANEL EM2 INI THE PENTHOUSE PER THE NOTE ON THE
SINGLE-LINE DIAGRAM.
.
ELECTRICAL CONTRACTOR TO PROVIDE COST OPTION TO PROVIDE A NEW 400A, 4P,
208Y,120V ATS IN PLACE OF THE EXISTING ONE.
ELECTRICAL DRAWING LIST
E0.1
E3.1
E5.1
E9.1
LEGENDS, ABBREVIATIONA AND DRAWING LIST
PARTIAL FLOOR PLANS - POWER PLAN
ELECTRICAL SINGLE-LINE DIAGRAM
ELECTRICAL DETAILS
© 2014 - GLUMAC ALL RIGHTS RESERVED
THESE DRAWINGS ARE THE PROPERTY OF
GLUMAC ARE NOT TO BE
USED OR REPRODUCED IN ANY MANNER,
WITHOUT PRIOR WRITTEN PERMISSION
Revisions
#
Description
Date
SHEET TITLE:
LEGENDS,
ABBREVIATIONA
AND DRAWING
LIST
DRAWN BY: Author
CHECKED BY: LRH
SHEET
E0.1
U - UNINTERRUPTIBLE POWER (UPS)
C - CRITICAL POWER (Hospital)
Q - EQUIPMENT POWER (Hospital)
S - LIFE SAFETY POWER (Hospital)
JOB NO.
100% CD'S/ PERMIT SET 7/30/14
02.14.00651
7/30/2014 11:19:18 AM
12" = 1'-0"
TM
PNL- EM2
(E)
DISC-UNUSED
(E) DISC
PNL-EM2
XFR-EM2
(E) ATS-EM2
CONNECT (E) SPARE WIRING TO
THIS (E) GENERATOR REMOTE
ANNUNCIATOR. PROGRAM AS
REQUIRED TO ALLOW PENTHOUSE
ATS "ATS IN EMERGENCY" STATUS
TO DISPLAY. ADD LABELS TO
DISPLAY PANEL
DISC-EM2
ROUTE SECONDARY EMT
CONDUIT OVERHEAD AS
REQUIRED.
MOUNT DISCONNECT ON UNISTRUT FRAME
900 SW Fifth Ave., Suite 1600
Portland, OR 97204-2640
T. 503.227.5280 F. 503.274.7674
(E) DISC
ELEV-MECH
Job No.: 02.14.00651
Contact: JJE
www.glumac.com
engineers for a sust ai nable f uture
ROUTE PRIMARY CONDUIT
UNDER SLAB.CORE DRILL
AS REQUIRED
(E) GRAP-1
Client
PORTLAND STATE
UNIVERSITY
Project
PSU ELEVATOR
RECONNECTION TO
GENERATOR
4
PENTHOUSE - ENLARGED ELECTRICAL ROOM
2
SCALE: 1/4" = 1'-0"
0
4
FIRST FLOOR - PARTIAL ELECTRICAL PLAN
SCALE: 1/8" = 1'-0"
0
8
8
16
© 2014 - GLUMAC ALL RIGHTS RESERVED
THESE DRAWINGS ARE THE PROPERTY OF
GLUMAC ARE NOT TO BE
USED OR REPRODUCED IN ANY MANNER,
WITHOUT PRIOR WRITTEN PERMISSION
Revisions
#
(E) EMPTY J-BOX AND CONDUIT.
EXTEND 1" CONDUIT TO PENTHOUSE
AND PROVIDE CONTROL WIRING PER
SINGLE-LINE DIAGRAM
(E) PNL- EM1
(E) CONDUIT SERVING
PENTHOUSE PANEL-EM2.
DEMO CONDUCTORS.
PROVIDE LABEL ON
CONDUIT AS "SPARE
CONDUIT" USING KROY
(E) DISC-EM1
3/4" LABEL
Date
SHEET TITLE:
PARTIAL
FLOOR PLANS POWER PLAN
(E) XFR-EM1
(E) ATS-EM1
Description
PROVIDE CONTROL WIRING
AND CONDUIT TO
PENTHOUSE ATS. CONNECT
TO (E) GENERATOR
CONTROLS
(E) PNL- EMDP
(E) GENSET TERMINAL CABINET
PROVIDE FEEDER TO (E)
PULL BOX FOR ROUTING OF
FEEDER TO XFR-EM2
ROUTE CONTROL CONDUIT NEXT TO
EXISTING CONDUIT RISERS. PROVIDE
WATER AND FIRE PROOFING AT
PENETRATION
(E) PULL BOX
(E) 400A
DISC-FIRE
PUMP
DRAWN BY: LRH
DISC-EM2
CHECKED BY: JJE
SHEET
(E) PANEL-EM2 FEEDER RISER CONDUIT
PROVIDE SEPARATION BETWEEN EMERGENCY AND NORMAL FEEDERS
E3.1
3
SECOND FLOOR - PARTIAL PLAN
1
SCALE: 1/8" = 1'-0"
0
8
16
BASEMENT - ENLARGED ELECTRICAL ROOM PLAN
SCALE: 1/4" = 1'-0"
0
4
8
100% CD'S/ PERMIT SET 7/30/14
JOB NO.
02.14.00651
7/30/2014 11:19:26 AM
As indicated
TM
CONNECT FEEDER WITH CRIMP LUGS TO EXISTING BUS BARS IN GUTTER
2
REMOVE EXISTING 60A FEEDER COMPLETELY. EXISTING RISER CONDUIT IS TO BE
REUSED TO SERVE NEW FEEDER TO TRANSFORMER EM2
3
DEMO EXISTING CONDUIT BELOW SLAB AND REPLACE WITH LARGER SIZE IF REQUIRED
4
MOUNT FUSED DISCONNECT ON UNISTRUT RACK NEXT TO TRANSFORMER
5
PROVIDE LINE ITEM PRICE FOR REPLACING AND INSTALLING A NEW ATS.
6
REMOVE UNUSED DISCONNECT. CLOSE ALL UNUSED HOLES WITH PLUGS.
7
PROVIDE 80A RK1 FUSES IN (E) 100A DISCONNECT
8
PROVIDE CONDUCTOR SUPPORT WEDGE TO MATCH NEW FEEDER SIZE. SUPPORTS TO
BE NO MORE THAN 100' APART FOR ALL VERTICAL DROPS.
9
ROUTE CONDUIT OVERHEAD OR BELOW SLAB. CORE-DRILL SLAB AS REQUIRED IF
ROUTED BELOW. DO NOT ROUTE ON TOP OF FLOOR SLAB.
11
PROVIDE SEPARATE LINE ITEM PRICE TO REPLACE PANEL WITH 100A, 3P, 4W,
208Y/120V, 42-POLE BUSSMAN QUIK-SPEC FUSED PANEL WITH MLO AND BREAKER SIZE
AND QUANTITY TO MATCH EXISTING WITH AN ADDITIONAL (4) 20A/1P SPARE BREAKERS
AND FUSES.
(E) ELEV-1 (E) ELEV-2 (E) ELEV-3
25 HP
25 HP
25 HP
(E)
100.3M?
(E)
100AF
100AS
F
(E)
100.3M?
(E)
100AF
100AS
(E)
100.3M?
(E)
100.3M?
(E)
100AF
100AS
F
(E) ELEV
MACHINE RM
HVAC
?? TONS
12
EXISTING PULLBOX LOCATION PER EXISTING SINGLE-LINE. THIS BOX HAS NOT BEEN
FIELD VERIFIED.
(E)
100.3M?
F
(E)
100.3M?
13
EXISTING PULL BOX. PROVIDE PHYSICAL BARRIER INSIDE PULLBOX TO SEPARATE
NORMAL POWER FROM GENERATOR POWER. USE FLEXIBLE METAL CONDUIT OR SHEET
METAL.
(E)
80.2M?
14
EXISTING GENERATOR REMOTE ANNUNCIATOR PANEL. CONNECT (2) EXISTING
CONDUCTORS TO ANNUNCIATOR TO ANNUNCIATE "ATS-EM2 IN EMERGENCY POSITION".
LABEL WIRING.
15
EXISTING GENERATOR CONTROL TERMINAL PANEL. CONNECT GENERATOR START
WIRING FROM PENTHOUSE ATS IN SERIES WITH EXISTING ATS GENERATOR START
WIRING. CONNECT ATS IN EMERGENCY POSITION WIRING TO EXISTING GENERATOR
REMOTE ANNUNCIATOR USING EXISTING SPARE CONDUCTORS. REPROGRAM
ANNUNCIATOR WITH CATERPILLAR'S ASSISTANCE.
Job No.: 02.14.00651
Contact: JJE
www.glumac.com
1
900 SW Fifth Ave., Suite 1600
Portland, OR 97204-2640
T. 503.227.5280 F. 503.274.7674
#
ROOF
ROOF
engineers for a sust ai nable f uture
KEYED NOTES
1
PNL
EM2
(E)
60AF
60AS
11
10 KAIC
7
6
80.4
F
(E)
80AF
100AS
(D)
60.4
2
(E)
80AF
100AS
F
80.4
3.0
3
F
5
EM2
EMERGENCY
100 A
3-POLE
??KAIC
6.8
8
CS
250AF
400AS
EM2
480Y/277V
75 KVA
.
PENTHOUSE
(E)
400.4
(E) ATS
.
XFR
125.3
(E)
80.2
F
250.4
4
9
10
EXISTING EMPTY J-BOX WITH EMPTY CONDUIT. EXTEND CONDUIT TO PENTHOUSE ATS
AND INSTALL GENERAOTR CONTROL AND MONITORING WIRING.
PORTLAND STATE
UNIVERSITY
PENTHOUSE
COPPER FEEDER SCHEDULE
10
FIFTHEENTH
FLR
FIFTHEENTH FLR
FEEDER
TAG
CONDUITS
CONDUCTORS PER SET
4.00"
(4) 500 KCMIL
500 KCMIL
-
250.4
2.50"
1
3.00"
(4) 250 KCMIL
#4
-
4000.3
3.00"
11
4.00"
(3) 500 KCMIL
500 KCMIL
-
250.3
2.50"
1
3.00"
(3) 250 KCMIL
#4
-
3500.4
3.50"
10
4.00"
(4) 500 KCMIL
500 KCMIL
-
225.4
2.50"
1
3.00"
(4) #4/0
#4
-
3500.3
3.00"
10
4.00"
(3) 500 KCMIL
500 KCMIL
-
225.3
2.00"
1
2.50"
(3) #4/0
#4
-
3000.4
3.50"
8
4.00"
(4) 500 KCMIL
400 KCMIL
-
200.4
2.00"
1
2.50"
(4) #3/0
#6
-
3000.3
3.00"
8
4.00"
(3) 500 KCMIL
400 KCMIL
-
200.3
2.00"
1
2.50"
(3) #3/0
#6
-
2500.4
3.50"
7
4.00"
(4) 500 KCMIL
350 KCMIL
-
175.4
2.00"
1
2.50"
(4) #2/0
#6
-
2500.3
3.00"
7
4.00"
(3) 500 KCMIL
350 KCMIL
-
175.3
1.50"
1
2.00"
(3) #2/0
#6
-
2000.4
3.00"
6
4.00"
(4) 400 KCMIL
250 KCMIL
-
150.4
2.00"
1
2.00"
(4) #1/0
#6
-
2000.3
3.00"
6
4.00"
(3) 400 KCMIL
250 KCMIL
-
150.3
1.50"
1
2.00"
(3) #1/0
#6
-
1600.4
3.00"
5
4.00"
(4) 400 KCMIL
#4/0
-
125.4
1.50"
1
1.50"
(4) #1
#6
-
1600.3
3.00"
5
4.00"
(3) 400 KCMIL
#4/0
-
125.3
1.25"
1
1.50"
(3) #1
#6
-
1200.4
3.00"
4
4.00"
(4) 350 KCMIL
#3/0
-
110.4
1.25"
1
1.50"
(4) #2
#6
-
1200.3
3.00"
4
3.00"
(3) 350 KCMIL
#3/0
-
110.3
1.25"
1
1.50"
(3) #2
#6
-
1000.4
3.00"
3
4.00"
(4) 400 KCMIL
#2/0
-
100.4
1.25"
1
1.50"
(4) #2
#8
-
1000.3
3.00"
3
4.00"
(3) 400 KCMIL
#2/0
-
100.3
1.25"
1
1.50"
(3) #2
#8
-
800.4
3.00"
3
3.00"
(4) 300 KCMIL
#1/0
-
90.4
1.25"
1
1.50"
(4) #2
#8
-
800.3
2.50"
3
3.00"
(3) 300 KCMIL
#1/0
-
90.3
1.25"
1
1.50"
(3) #2
#8
-
700.4
3.50"
2
4.00"
(4) 500 KCMIL
#1/0
-
80.4
1.25"
1
1.50"
(4) #4
#8
-
700.3
3.00"
2
4.00"
(3) 500 KCMIL
#1/0
-
80.3
1.00"
1
1.50"
(3) #4
#8
-
600.4
3.00"
2
4.00"
(4) 350 KCMIL
#1
-
70.4
1.25"
1
1.50"
(4) #4
#8
-
600.3
2.50"
2
3.00"
(3) 350 KCMIL
#1
-
70.3
1.00"
1
1.50"
(3) #4
#8
-
500.4
2.50"
2
3.00"
(4) 250 KCMIL
#2
-
60.4
1.00"
1
1.00"
(4) #6
#10
-
500.3
2.50"
2
2.50"
(3) 250 KCMIL
#2
-
60.3
0.75"
1
1.00"
(3) #6
#10
-
450.4
2.50"
2
3.00"
(4) #4/0
#2
-
50.4
1.00"
1
1.00"
(4) #6
#10
-
450.3
2.00"
2
2.50"
(3) #4/0
#2
-
50.3
0.75"
1
1.00"
(3) #6
#10
-
PGE
400.4
2.00"
2
2.50"
(4) #3/0
#2
-
40.4
0.75"
1
1.00"
(4) #8
#10
-
?.?
0 KVA
12???V DELTA, 3P, 3W
480 WYE/277V
PAD-VAULT MOUNTED
UTILITY PROVIDED
400.3
2.00"
2
2.50"
(3) 3/0
#2
-
40.3
0.75"
1
1.00"
(3) #8
#10
-
350.4
3.50"
1
4.00"
(4) 500 KCMIL
#2
-
30.4
0.75"
1
1.00"
(4) #10
#10
-
350.3
2.50"
1
4.00"
(3) 500 KCMIL
#2
-
30.3
0.75"
1
1.00"
(3) #10
#10
-
300.4
3.00"
1
3.00"
(4) 350 KCMIL
#4
-
20.4
0.75"
1
1.00"
(4) #12
#12
-
300.3
2.50"
1
3.00"
(3) 350 KCMIL
#4
-
20.3
0.75"
1
1.00"
(3) #12
#12
-
12
8
ELEVENTH FLR
ELEVENTH FLR
TENTH FLR
TENTH FLR
SETS
RNC
PHASE/NEUTRAL
NOTES
11
CS
MET
CONDUCTORS PER SET
3.50"
TWELFTH FLR
GROUND
CONDUITS
4000.4
TWELFTH FLR
PHASE/NEUTRAL
FEEDER
TAG
SETS
FOURTEENTH FLR
RNC
NOTES
MET
FOURTEENTH
FLR
GROUND
NINTH FLR
NINTH FLR
125.3
EIGHT FLR
EIGHT FLR
SEVENTH FLR
SEVENTH FLR
Project
PSU ELEVATOR
RECONNECTION TO
GENERATOR
SIXTH FLR
SIXTH FLR
FIFTH FLR
FIFTH FLR
FOURTH FLR
FOURTH FLR
THIRD FLR
THIRD FLR
J
12
PB
16
SECOND FLR
SECOND FLR
14
GRAP (E)
FIRST FLR
FIRST FLR
UTX
DIST
.
200A
PULL
200A
SPACE
.
200A
.
200A
.
200A
.
200A
.
200A
.
200A
.
200A
.
400A
(E) MAIN SWITCHBOARD-- ???
M
0 A ,480Y/277V, 3P, 4W ,?? KAIC
METER
(E) GENERATOR
7.5 HP
REMOTE
RADIATOR
(E) MAIN SWITCHBOARD- ???
1600 A ,480Y/277V, 3P, 4W ,42 KAIC ,100% NEUTRAL
?
MAIN BRKR
1600AT
1600AF
.
400A
.
600A
.
125A
.
250A
.
125A
.
250A
GF
.
125A
.
300A
.
125A
.
100A
.
250AT
400AF
400.4
(E)
125.3
(E) .
600.?
(E)
250.?
(E)
125.3
(E) .
(E) PNL
(E) XFR
(E) DIST
(E) PNL
(E) XFR
DPA
2H
T1
A
35 KAIC
208Y/120V
75 KVA
.
(E)
200AF
200AS
??KAIC
??KAIC
F
480Y/277V
75 KVA
.
(E) PNL
(E) PNL
(E) PNL
(E) PNL
B
A
1H
C
??KAIC
??KAIC
??
(E)
??
(E)
(E)
400A
(E)
200A
(E)
400A
??
(E)
(E)
15AF
30AS
F
??
(E)
??
(E)
(E)
100A
(E)
??AF
(E) SATEC TUBE (E) EMCO MAIER
FURNACE
342 CNC
80A
10A
80A
EM1
SCHD
9
F
(E)
??AF
F
(E)
??AF
(E) ARC MELTER
200A
(E)
150AF
200AS
125.3
F
NOTES:
1. CONDUCTORS AND CONDUITS SHOWN IN THIS SCHEDULE ARE
BASED ON COPPER CONDUCTORS WITH THHN/THWN INSULATION.
F
3.
EM1
208Y/120V
45 KVA
.
125.3
(E)
70.3
(E) PNL
EMDP
(E)
??
TERM (E)
??
400.3
(E)
ELEC RM ??
125.4
(E)
BASEMENT
(E)
30.2
(E)
400.3
.
(E) XFR
(E) ATS-FIRE PUMP
FP-1
??
(E)
(E) FP-1
?? HP
???
EMERGENCY
400 A
3-POLE
??KAIC
??
FIRE PUMP ROOM
(E)
500.4
G1
400.4
(E)
(E) DIST
480Y/277V
7.5 KVA
(E). PNL
DPB
G1
??KAIC
PWR ZONE
??KAIC
7.
8.
PROVIDE GROUND WIRE NOTED ABOVE IN ALL FEEDERS AND
BRANCH CIRCUITS. WHERE MULTIPLE CONDUITS ARE INDICATED
PROVIDE NOTED GROUND WIRE IN EACH CONDUIT.
4.
NOT ALL FEEDERS ARE NECESSARILY USED ON THIS PROJECT.
5.
NOMINAL AMPACITIES GREATER THAN 100 AMPS ARE FOR 75
DEG..C TERMINALS.
9.
© 2014 - GLUMAC ALL RIGHTS RESERVED
THESE DRAWINGS ARE THE PROPERTY OF
GLUMAC ARE NOT TO BE
USED OR REPRODUCED IN ANY MANNER,
WITHOUT PRIOR WRITTEN PERMISSION
OVERSIZED (173% MIN.) NEUTRAL FOR FEEDERS CONNECTED TO A
K-4 OR HIGHER RATED TRANSFORMER.
Revisions
REFER TO TRANSFORMER SCHEDULE FOR STANDARD PRIMARY AND
SECONDARY FEEDER SIZES.
#
Description
Date
REFER TO MCC OR PANEL SCHEDULES FOR FEEDER SIZES TO
EQUIPMENT NOTED WITH THIS TAG.
EM1
EMERGENCY
100 A
3-POLE
??KAIC
??
BASEMENT
(E)
400.3
THIS SCHEDULE SHALL BE USED ON ALL FEEDERS SERVING LOADS
WHERE THE CIRCUIT BREAKER SIZE MATCHES THE AMPACITY OF
ITS FEEDER. USE THE "MOTOR CIRCUIT SCHEDULE" FOR LOADS,
SUCH AS MOTORS, PUMPS, FANS, CHILLERS, ETC., WHERE THE
CIRCUIT BREAKER SIZE IS LARGER THAN THE AMPACITY OF ITS
FEEDER.
"MET"= EMT, IMC, GRC, RAC, OR PVC COATED GRC TYPE
CONDUITS. "RNC"= PVC 40, PVC 80 OR FIBERGLASS TYPE
CONDUITS ROUTED UNDERGROUND. REFER TO SIZING ON DRAWINGS
IF "RNC" CONDUITS ARE ROUTED ABOVEGROUND. CONDUIT SIZES
NOTED ON SINGLE-LINE DIAGRAM OR ON PLANS SUPERSEDE SIZES
NOTED ABOVE IF LARGER.
(E) ATS
(E) FIRE PUMP
DISC
400AF F
100.4
(E)
6.
15
??KAIC
??KAIC
2.
.
(E) XFR
DISC-EM2
125AF
200AS F
(E)
20.3
(E) GLEEBLE
(E) BREW 580-C
1500 SYSTEM
VAC FURNACE
200A
220A
(E) BREW 424-C
VAC FURNACE
100A
8
(E)
150.4
13
??
(E)
(E)
100A
XFR
??
??
(E)
F
200.4
(E)
??KAIC
125.?
(E)
T2
(E)
200AF
200AS
200.4
(E)
250.?
(E)
(E) PNL
??KAIC
(E)
20.3
SUB-BASEMENT
16
PROVIDE 1" EMT CONDUIT WITH (6) #12 CONDUCTORS OR (6) CONDUCTOR MC CABLE.
(2) BLUE FOR GENERATOR START CONTACT, (2) RED FOR ATS IN EMERGENCY
POSITION, (2) BROWN AS SPARE. CONNECT AS REQUIRED TO EXISTING ATS CONTACTS.
Client
GARAGE
(E) DIESEL GENSET
GEN-1
300KW/ 375KVA
@0.8 PF
277Y/480V,3P,4W
EMERGENCY
5.41
500AT
.
600AF
TRANSFORMER SCHEDULE
480V PRIMARY
480Y/277V SECONDARY
208Y/120V SECONDARY
WEIGHT
KVA
C.B.
FEEDER
GND
SHEET TITLE:
ELECTRICAL
SINGLE-LINE
DIAGRAM
C.B.
FEEDER
C.B.
FEEDER
GND
15
30/3
30.3
30/3
30.4
#8
50/3
50.4
#8
275
30
50/3
50.3
50/3
50.4
#8
100/3
110.4
#8
340
45
70/3
70.3
70/3
70.4
#6
150/3
150.4
#6
475
75
125/3
125.3
125/3
125.4
#2
225/3
225.4
#2
1060
112.5
175/3
175.3
175/3
175.4
#1/0
400/3
400.4
#1/0
1250
150
225/3
225.3
225/3
225.4
#2/0
500/3
500.4
#2/0
2130
225
350/3
350.3
350/3
350.4
#3/0
800/3
800.4
#3/0
2665
300
450/3
450.3
450/3
450.4
#3/0
1000/3
1000.4
#3/0
4190
500
800/3
800.3
800/3
800.4
#4/0
1600/3
1600.4
#4/0
3480
DRAWN BY: Author
750
1200/3
1200.3
1200/3
1200.4
#4/0
2500/3
2500.4
#4/0
3710
CHECKED BY: JJE
NOTES:
CONTROLS
SUB-BASEMENT
1.
THIS SCHEDULE APPLIES TO 3-PHASE, 480:480Y/277V AND
480:208Y/120V DRY-TYPE STEP-DOWN TRANSFORMERS ONLY.
2.
ON ONE-LINE DIAGRAMS AND SCHEDULES WHERE FEEDERS AND
CIRCUIT BREAKERS ARE SHOWN AS "XFR", PROVIDE RESPECTIVE
FEEDERS, GROUND CONDUCTORS AND BREAKERS NOTED ABOVE.
PROVIDE SECONDARY BREAKER NOTED ABOVE AS MAIN CIRCUIT
BREAKER INTEGRAL IN DISTRIBUTION, PANEL AND SWITCH
BOARDS, UON.
3. GROUND CONDUCTOR SIZES INDICATED ABOVE SUPERSEDE
GROUND CONDUCTORS SHOWN ON FEEDER SCHEDULE. ROUTE
COPPER GROUNDING CONDUCTOR TO GROUNDING ELECTRODE
PER NEC. PROVIDE BONDING ALSO PER NEC. COMMON LEAD
OF LARGEST REQUIRED SIZE MAY BE EMPLOYED TO SERVE
MULTIPLE TRANSFORMERS.
4. NOT ALL TRANSFORMER SIZES INDICATED IN THIS SCHEDULE
ARE NECESSARILY USED ON THIS PROJECT.
SHEET
E5.1
5. WEIGHTS INDICATED ABOVE ARE APPROXIMATE, ACTUAL VALUES
MAY VARY. CONFIRM WITH SUBMITTAL INFO.
JOB NO.
100% CD'S/ PERMIT SET 7/30/14
02.14.00651
7/30/2014 11:19:53 AM
As indicated
TM
C
L
CENTERLINE OF INNER DOOR
WIDTH AS REQUIRED, MIN 5"
WIDTH AS REQUIRED, MIN 4"
EQUIPMENT GROUND
PRIMARY
PRIMARY
ELECTROSTATIC
SHIELD, WHEN
PRESENT
1/2"
EXHAUST FAN EF-1
TO GROUND BAR AS
INDICATED OR MSGB IF NOT
INDICATED
GROUNDING
CONDUCTOR SIZED
PER TRANSFORMER
SCHEDULE
GROUND
>173% NEUTRAL
120VAC
EXHAUST FAN EF-1
1"
1ST FLOOR-COL. A3
BOND GROUND BAR
MAIN BUS SIZE IF MAIN LUGS ONLY
OR TRIP RATING OF MAIN BREAKER.
3/16"
1"
1/4"
BOND BOX
GROUND
ADJACENT ADDITIONAL PANEL SECTIONS
AS REQUIRED
NOTES:
GENERAL NOTES:
A. DIAGRAM HAS BEEN SIMPLIFIED TO SINGLE PHASE FOR CLARITY.
SIMILAR FOR LUMINAIRES
1.
SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS.
SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS
OF NAMEPLATES FOR DIFFERENT SYSTEMS.
2.
PROVIDE ONE NAMEPLATE FOR EACH PANEL OR MCC SECTION. WHERE SECTION NUMBER TWO AND ABOVE ARE
WITHIN SAME ROOM AND WITHIN 10' OF EACH OTHER USE THE SMALLER SIZE NAMEPLATE.
2.
TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED
TO MATCH EQUIPMENT SPECIFICATIONS.
3.
CENTER ALL TEXT HORIZONTALLY.
4.
TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS.
3.
CENTER ALL TEXT HORIZONTALLY
120VAC
6
PORTLAND STATE
UNIVERSITY
NAMEPLATE MOUNTING LOCATION
120VAC
PHASE
3/16"
3/16"
3/16"
1.
GND
PROVIDE ONE
PER CIRCUIT
1/4"
3/16"
3/16"
CIRCUIT BREAKERS IN DIST. PANELS
GROUND
Client
3/16"
SECTION 2
3/16"
NOTES:
BRANCH
1/4"
USE "BOLD" STYLE TEXT
DIST. PANEL CRPP1A1
DESCRIPTION OF LOAD SERVED
POWER RECEPTACLE
IN STEEL OUTLET BOX
-N-
1/4"
5/8"
LOCATION OF LOAD
STEEL CONDUIT
NEUTRAL
1/4"
WIDTH AS REQUIRED, MIN 5"
TRANSFORMER SECONDARY
LESS THAN 10' LONG
SUBFEED
FED FROM MDS-A
480V, 3P, 3W, 800A, 65KAIC
WIDTH AS REQUIRED, MIN 3.5"
PANEL ENCLOSURE
>173% NEUTRAL
1/4"
GENERAL EQUIPMENT
DIV 16 TO PROVIDE COPPER
GROUND BAR WITH
SEPARATE TERMINATIONS
FOR EACH CONDUCTOR.
MAIN BREAKER
2.5"
USE RIVOTS ON DIV. 16 PROVIDED ITEMS IN EXTERIOR
LOCATIONS, USE DOUBLE-STICK TAPE ON OWNER FURNISHED
ITEMS (DO NOT DRILL HOLES) AND INTERIOR EQUIPMENT
BOND TO TRANSFORMER
ENCLOSURE
TO SUBFEED PANEL WITH SAME CONNECTIONS
3/16"
3/16"
3/16"
3/16"
1/2"
3/8"
1/2"
BOND TO NEAREST
STRUCTURAL STEEL PER NEC
250 IF REQUIRED BY LOCAL
AUTHORITY HAVING
JURISDICTION
STEEL CONDUIT
DIST. PANEL L1A
1/4"
FED FROM DS1A1
10 HP., 480V, 3∅
2"
1/2"
900 SW Fifth Ave., Suite 1600
Portland, OR 97204-2640
T. 503.227.5280 F. 503.274.7674
NOTE:
NEUTRAL-GROUND
CONNECTION IS MADE WITHIN
THE TRANSFORMER
ENCLOSURE ONLY
K-RATED TRANSFORMER
ENCLOSURE
TO MSGB
Job No.: 02.14.00651
Contact: JJE
www.glumac.com
USE "BOLD" STYLE TEXT
C
L
engineers for a sust ai nable f uture
USE RIVETS NOT DOUBLE-STICK
TAPE FOR EXTERIOR LOCATIONS
EQUIPMENT IDENTIFICATION NAMEPLATES
3
SCALE: NONE
DISTRIBUTION PANEL, MOTOR CONTROL CENTER & BRANCH PANEL
NAMEPLATES
Project
PSU ELEVATOR
RECONNECTION TO
GENERATOR
SCALE: NONE
B. NON-K-RATED (K-1) TRANSFORMER WIRING IS THE SAME EXCEPT NEUTRAL
(GROUNDED SECONDARY CONDUCTOR) IS NOT OVERSIZED.
7
TRANSFORMER/PANEL/OUTLET/LUMINAIRE
WIRING (NON ISOLATED GROUND PANELS)
WIDTH AS REQUIRED, MIN. 6"
WIDTH AS REQUIRED, 6" MIN.
SCALE: NONE
TRANSFORMER TRR-1A1
5/16"
FIRE ALARM SYSTEM FAJB-1
1.25"
1/4"
2.5"
3 / 16 "
1/4"
PRIMARY FED FROM DS1A1
480Y/277V, 3∅, 3W
SECONDARY FEEDS PNL RDP1A1
208Y/120V, 3∅, 4W
75 KVA, K-13 RATED
1/4 "
PNL??-##
1/4"
1/4"
ENGRAVE PANEL NAME AND BRANCH CIRCUIT
NUMBER SERVING ENCLOSURE, OMIT
ENGRAVING IF ENCLOSURE IS NOT POWERED
USE "BOLD" STYLE TEXT. USE WORDS, NOT ABBREVIATIONS,
FOR SYSTEM NAMES AND FUNCTION
1/4"
3/16"
3/16"
3/16"
3/16"
3/16"
3/16"
3/16"
3/16"
1/4"
USE "BOLD" STYLE TEXT
USE RIVOTS NOT DOUBLE-STICK TAPE FOR ALL LOCATIONS
USE RIVETS ON DIV. 16 PROVIDED ITEMS IN EXTERIOR
LOCATIONS, USE DOUBLE-STICK TAPE ON OWNER FURNISHED
ITEMS (DO NOT DRILL HOLES) AND INTERIOR EQUIPMENT
NOTES:
NOTES:
5
1.
REFER TO SPECIFIACTIONS FOR FOR ADDITIONAL INFORMATION AND
COLORS FOR DIFFERENT SYSTEMS.
2.
PROVIDE ONE NAMEPLATE FOR EACH ENCLOSURE OR J-BOX LARGER THAN 4"
3.
CENTER ALL TEXT HORIZONTALLY AND VERTICALLY IF ONLY ONE LINE.
4.
TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED
TO MATCH EQUIPMENT SPECIFICATIONS.
ENCLOSURE INDENTIFICATION NAMEPLATES
2
SCALE: NONE
1.
SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION
AND COLORS OF NAMEPLATES FOR DIFFERENT SYSTEMS.
2.
PROVIDE ONE NAMEPLATE FOR EACH TRANSFORMER.
3.
CENTER ALL TEXT HORIZONTALLY.
4.
TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT
AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS.
TRANSFORMER NAMEPLATE
SCALE: NONE
© 2014 - GLUMAC ALL RIGHTS RESERVED
THESE DRAWINGS ARE THE PROPERTY OF
GLUMAC ARE NOT TO BE
USED OR REPRODUCED IN ANY MANNER,
WITHOUT PRIOR WRITTEN PERMISSION
NAMEPLATE COLOR LEGEND
NAMEPLATE COLOR
1
SERVICE
TEXT
BACKGROUND
480V NORMAL
WHITE
BLACK
322-402
208/120V NORMAL
WHITE
BLACK
322-402
480/277V UPS
WHITE
ORANGE
122-612
Revisions
#
USE "BOLD" STYLE TEXT
ON POWER CONDUITS SHOW
CIRCUIT NUMBERS OF ALL
CIRCUITS IN J-BOX. USE 1"
WIDE KROY OR BROTHERS
LABELING TAPE WITH BLACK 1/2"
HIGH HELVETICA BOLD LETTERING
ON WHITE BACKGROUND.
WIDTH AS REQUIRED, MIN. 8.5"
PANEL, MCC,
ENCLOSURE, ETC.
WHITE
ORANGE
122-612
SECURITY
BLACK
YELLOW
322-704
BMS CONTROLS
GREEN
WHITE
222-324
FIRE ALARM
WHITE
RED
322-602
YELLOW
BLACK
322-407
GROUND CONDUITS
WHITE
GREEN
322-992
480/277V EMERGENCY
WHITE
RED
322-602
208/120V EMERGENCY
WHITE
RED
322-602
480/277V STANDBY
WHITE
BLUE
322-542
208/120V STANDBY
WHITE
480/277V GENERATOR
WHITE
BLUE
GREEN
322-542
122-932
208/120V GENERATOR
WHITE
GREEN
122-932
GENERAL NOTES
15KV MEDIUM VOLTAGE
WHITE
PURPLE
222-582
A.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
CATV/ MATV
WHITE
AQUA
122-942
B.
TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT
AS REQUIRED TO MATCH EQUIPMENT SPECIFICATIONS.
C.
ROWMARK # IS THE COLOR OF THE PLASTIC ENGRAVING
MATERIAL. USE ROWMARK 1/16" ULTRAMATT AND SATIN
STOCK AS NOTED.
4
ENGRAVED
NAMEPLATES
3/16"
ATS-MTLL499
2
3"
PANEL MTES0021
FED FROM: XX
10 HP., 480V, 3∅
RACEWAY AND NAMEPLATE IDENTIFICATION
SCALE: 1/8" = 1'-0"
Date
ROWMARK #
208/120V UPS
TELECOM
Description
STN0012-22,24,26
LIFE SAFETY POWER SYSTEM
FED FROM: (N)SWBD-MTNL3003 (G)SWBD-MTGL304
SERVES: SWBD-MTLL500
2500A, 480Y/277V, 3P, 4-POLE
65 KAIC
3/8"
3/16"
1/4"
3/16"
1/4"
3/16"
1/4"
3/16"
1/4"
3/16"
1/4"
LINE 1
LINE 2
SHEET TITLE:
LINE 3
LINE 4
ELECTRICAL
DETAILS
LINE 5
LINE 6
3/16"
NOTES
1. SEE DRAWINGS FOR ADDITIONAL NAMEPLATE INFORMATION AND COLORS OF
NAMEPLATES FOR DIFFERENT SYSTEMS.
2.
TEXT SHOWN ABOVE IS FOR EXAMPLE ONLY. MODIFY TEXT AS REQUIRED TO
MATCH EQUIPMENT SPECIFICATIONS. REPLACE QUESTION MARKS WITH CORRECT
NUMBERS.
3.
CENTER ALL TEXT HORIZONTALLY
4.
THIS DETAIL APPLIES TO ALL TRANSFER SWITCHES, MANUAL AND AUTOMATIC
5.
DRILL HOLES ON EXTERIOR NAMEPLATES ONLY
1
DRAWN BY: LRH
CHECKED BY: JJE
TRANSFER SWITCH NAMEPLATES
SHEET
E9.1
SCALE: NONE
JOB NO.
100% CD'S/ PERMIT SET 7/30/14
02.14.00651
7/30/2014 11:19:56 AM
1/8" = 1'-0"