RS Flip--Flop, R Dominant RSR Symbol RSR Set Reset -- S -- R B1 D Application Remarks B1 Q QN --- Binary Variable Inverse Binary Variable Block Diagram Utilization as static binary value memory. S Method of Operation Q The binary output Q is set to 1, when S is 1. R The binary output Q is set to 0, when R is 1. The value of Q is not changed, when both inputs are 0. When both inputs are 1, then Q is set to 0, since the reset input R dominates. The output QN always holds the inverse value of Q. Truth Table Binary Command S R 0 0 1 1 Output State Q Q does not change Q=0 Q=1 Q=0 0 1 0 1 Binary Values for the Commands Set/Reset Technical Data Processing time: Siemens AG Item No.: 465 980.7105.23 SIMADYN D ¡ Standard Function Modules P32 05.96 3 ms 5--1