Austin Hughes InfraPower Single Phase WSi Switched kWh Outlet

Product
specification drawing
Model : V20US-30A-WSi/CR_530/3B-1
File no.
: PD-V20US-WSi
Release date : 1 Nov 14
Version no. : V5
WSi Outlet kWh Switched Vertical PDU, 100~120Vac
20 outlets : NEMA x 20
OR
V20US-30A-WSi/CR_L530/3B-1
118.11
0.24
1.02
Safety Regulatory :
B
A
47.24
1-4
5-8
Cordset
:
9 - 12
13 - 16
OR
30 Amp
NEMA 5-30P
17 - 20
30 Amp
NEMA L5-30P
3 meter UL 10AWG cable with 30 Amp NEMA 5-30P or L5-30P plug
For 30A Rating PDU, the models which have 20 socket outlets,
Circuit Breaker :
2 x 15A Circuit Breaker
< CIRCUIT A > Socket #1-10 NEMA socket outlets can only output 12A maximum.
Input Rating
30A / 100~120Vac
< CIRCUIT B > Socket #11-20 NEMA socket outlets can only output 12A maximum.
:
Model : V20US-20A-WSi/CR_520/3B-1
OR
Environmental
:
V20US-20A-WSi/CR_L520/3B-1
Safety Regulatory :
20 Amp
NEMA 5-20P
Cordset
:
OR
20 Amp
NEMA L5-20P
3 meter UL 12AWG cable with 20 Amp NEMA 5-20P or L5-20P plug
For 20A Rating PDU, the models which have 20 socket outlets,
Circuit Breaker :
1 x 20A Circuit Breaker
Socket #1-20 NEMA socket outlets can only output 16A maximum.
Input Rating
20A / 100~120Vac
:
Environmental
:
Model : V20US-15A-WSi/CR_515/3B-1
Safety Regulatory :
15 Amp
NEMA 5-15P
Cordset
3 meter UL 14AWG cable with 15 Amp NEMA 5-15P plug
For 15A Rating PDU, the models which have 20 socket outlets,
Circuit Breaker :
:
1 x 15A Circuit Breaker
Socket #1-20 NEMA socket outlets can only output 12A maximum.
Input Rating
15A / 100~120Vac
:
Common Specification :
Description
:
20 outlets NEMA
Receptacles
:
20 outlets NEMA 20A Rated
Meter
:
RMS digital ammeter measuring input load current
Environmental
:
UNIT : inch
Environment Conditions :
Temperature
operating
storage
: 0 to 45 °C
: -25 to 65 °C
Humidity
: 8 to 95% RH, non-condensing
Altitude
operating
storage
: 0 to 2,000 m
: 0 to 15,000 m
PDU Dimension
:
Packing
:
2.76 (W) x 2.56 (D) x 47.24 (H) in.
Net Weight
:
Gross Weight :
WARNING : The individual user should take care to determine prior to use whether this device is
suitable, adequate or safe for the use intended. Since individual applications are subject to great
variation, the manufacturer makes no representation or warranty as to the suitability or fitness of
these devices for any specific application.
The company reserves the right to modify product specifications without prior notice and assumes
no responsibility for any error which may appear in this publication.