Champ® LED Luminaires VMV Series LED Fixtures IF 1662 Installation & Maintenance Information SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE APPLICATION Luminaire construction is designed for use indoors and outdoors in marine and wet locations, where moisture, dirt, corrosion, vibration, and rough usage may be present. Champ® VMV Series Luminaires are suitable for use in the following hazardous (classified) areas as defined by the National Electrical Code (NEC®). 4. Connect supply wires to luminaire wire leads or terminal block per the attached wiring diagrams using methods that comply with all applicable codes. See Figure 2b. Tighten all electrical connections. 5. Close driver housing onto cover module, making sure that all wires are safely inside driver housing. Tighten captive closing screw to 30 in.-lbs. (3.4 N-m). Ensure two (2) bosses on driver housing are in contact with cover module. 6. Turn power on. FIGURE 2a Refer to the luminaire nameplate for specific classification information, maximum ambient temperature suitability, and corresponding operating temperature (T-Code). VMV: VMV3L – 11L NEC/CEC 100-277VAC/100-250VDC Ex nA nR IIC T6 Gc -40°C to +40°C Ex nA nR IIC T5 Gc -40°C to +55°C Ex tb IIIC T72°C Db IP66 -40°C to +40°C Ex tb IIIC T87°C Db IP66 -40°C to +55°C • Class I, Division 2, Groups A, B, C, D • Class II, Groups E, F, G • Class III • Class I, Zone 2 nA nR • Zone 21 tb • Simultaneous Presence • Wet Locations, Type 4X ** ** UL Standards • UL 844 Hazardous (Classified) • UL1598 Luminaires, UL1598A Marine 347-480VAC Ex nA nR IIC T4 Gc -40°C to +55°C Ex tb IIIC T70°C Db IP66 -40°C to +40°C Ex tb IIIC T85°C Db IP66 -40°C to +55°C CSA Standard • CSA C22.2 No. 137 ** IEC/ATEX Standards • • • • • • IEC 60079-0:2011 / EN 60079-0:2012 IEC 60079-15:2010 / EN 60079-15:2010 IEC 60079-31:2008 / EN 60079-31:2009 IEC 60529:2001 / EN 60529:2001 IEC 60598-1:2008 / EN 60598-1:2008 IEC 60598-2:2008 / EN 60598-2:2008 II 3 G Ex nA nR IIC T4 Gc -40°C to +55°C II 2 D Ex tb IIIC T70°C Db IP66 -40°C to +40°C II 2 D Ex tb IIIC T85°C Db IP66 -40°C to +55°C VMVAL, RL, GL, BL 100-277VAC Ex nA nR IIC T5 Gc -40°C to +40°C Ex nA nR IIC T4 Gc -40°C to +55°C Ex tb IIIC T60°C Db IP66 -40°C to +40°C Ex tb IIIC T75°C Db IP66 -40°C to +55°C Fixture Markings • • ** • • II 3 G Ex nA nR IIC T6 Gc -40°C to +40°C II 3 G Ex nA nR IIC T5 Gc -40°C to +55°C II 2 D Ex tb IIIC T72°C Db IP66 -40°C to +40°C II 2 D Ex tb IIIC T87°C Db IP66 -40°C to +55°C IECEx UL 13.0052X DEMKO 13 ATEX 1305741X DEMKO 13 ATEX 1475031X See Table 1 for temperature codes ** ** II 3 G Ex nA nR IIC T5 Gc -40°C to +40°C II 3 G Ex nA nR IIC T4 Gc -40°C to +55°C II 2 D Ex tb IIIC T60°C Db IP66 -40°C to +40°C II 2 D Ex tb IIIC T75°C Db IP66 -40°C to +55°C Input voltage: 100-277 VAC 50/60 Hz 100-250 VDC 347-480 VAC 50/60 Hz Open Hinge FIGURE 1 WARNING To avoid the risk of fire, explosion, or electric shock, this product should be installed, inspected, and maintained by a qualified electrician only, in accordance with all applicable electrical codes. Set Screw WARNING Ground Wires WARNING To avoid electric shock: To avoid explosion: Be certain electrical power is OFF before and during installation and maintenance. Make sure the supply voltage is the same as the luminaire voltage. Luminaire must be supplied by a wiring system with an equipment grounding conductor. Do not install where the marked operating temperatures exceed the ignition temperature of the hazardous atmosphere. To avoid burning hands: Do not operate in ambient temperatures above those indicated on the luminaire nameplate. Make sure lens and housing are cool when performing maintenance. Use proper supply wiring as specified on the luminaire nameplate. All gasket seals must be clean. installation Before opening, electrical power to the luminaire must be turned off. Keep tightly closed when in operation. MOUNTING: 1. Mount the cover module in its support position. • Ceiling and wall mount: mark and drill desired location on mounting surface. Secure with 1/4” (6mm) bolts or lag screws (not provided). To reduce the risk of ignition due to electrostatic discharge, avoid contact with the luminaire while explosive atmosphere is present Clean only with damp cloth. • Pendant, cone, stanchion mount: securely thread onto the appropriate NPT size conduit. Tighten set screw located in the conduit hub. See Figure 1. Wiring • Eaton’s Crouse-Hinds HTL thread lubricant must be added to the conduit threads to prevent water from entering the fixture. 2. Close all unused conduit entries with conduit plugs provided. To prevent galling and to ensure water-tightness, lubricate conduit plugs with Eaton’s Crouse-Hinds HTL lubricant before installing, and secure wrench-tight with at least five (5) full threads engaged (42-52 ft.-lb. for 3/4” plugs, and 58-68 ft.-lb. for 1” plugs). 1. Pull field wiring into cover module. 3. Hang LED luminaire on the cover module hinge hook. See Figure 2a. IF 1662 • 10/14 Copyright © 2014, Eaton’s Crouse-Hinds Business Page 1 FIGURE 2b IF 1662 • 10/14 Copyright © 2014, Eaton’s Crouse-Hinds Business Page 2 Wire Guard Installation Loosen but DO NOT completely remove wire guard screw. If already loosened, move to next step. Set wire guard in place by pushing it over the bottom rim of the fixture which is on the lowest casting until it sits in place above that rim. Ensure that the wire guard is in place around the complete bottom and is not partially in place above the rim. Tighten the screw attached to wire guard until guard is securely attached to bottom casting. The screw will be tight enough when the wire guard can no longer easily rotate on the fixture. NOTE: The sheet metal tabs which the screw goes through do not need to be touching for the guard to be securely fastened; the wire guard will be secure without those two tabs touching one another. INSTALLATION CHECKLIST MOUNTING MODULE NOTES: MOUNTING MODULE SERIES CEILING CM2 CM3 Be certain electrical power is OFF before and during installation and maintenance. Luminaire must be supplied by a wiring system with an equipment grounding conductor. Make sure globe or refractor and lamp are cool when performing maintenance. Champ® VMV Series Lighting Fixtures, 13-11L Watt ANGLED BPM2 BPM3 To avoid electric shock: To avoid burning hands: field assembled fixtures PENDANT APM2 APM3 HPM2 5._______ Verify all electrical connections are tightened. WARNING WALL TWM2 TWM3 STANCHION PM5 JM5 - 2: indicates 3/4” NPT thread - 3: indicates 1” NPT thread - 5: indicates 1-1/2” thread - Pendant, angled, ceiling, and stanchion mounts have one (1) conduit entry; ceiling and wall mounts have five (5) conduit entries 1._______ Verify sufficient HTL lubricant is on conduit plugs (recommend approximately 1/8” bead around the first thread of plug) and that all unused conduit entries on the cover module are closed with lubricated plugs. 6._______ Verify all wires are safely and neatly inside driver housing and not on top of wire terminal. Close driver housing onto cover module. VMV*L PVM*L maintenance replacement parts 1. Perform visual, electrical, and mechanical inspections on a regular basis. The environment and frequency of use should determine this. However, it is recommended that checks be made at least once a year. We recommend an Electrical Preventive Maintenance Program as described in the National Fire Protection Association Bulletin NFPA No. 70B: Recommended Practice For Electrical Equipment Maintenance (www.nfpa.org). 2. The lens should be cleaned periodically to ensure continued lighting performance. To clean, wipe the lens with a clean, damp cloth. If this is not sufficient, use a mild soap or a liquid cleaner such as Collinite NCF or Duco #7. Do not use an abrasive, strong alkaline, or acid cleaner. Damage may result. Eaton’s Crouse-Hinds VMV and NVMV Series Champ Luminaires are designed to provide years of reliable lighting performance. However, should the need for replacement parts arise, they are available through your authorized Eaton’s Crouse-Hinds distributor. Assistance may also be obtained through your local Eaton’s Crouse-Hinds representative. 2._______ Verify conduit plugs are installed to at least five (5) full threads into the cover module conduit entries. 7._______ Verify captive closing screw is tightened to 30 in.-lbs. (3.4 N-m) and two (2) bosses on driver housing are in contact with cover module. Eaton’s Crouse-Hinds Sales Service Department, 1201 Wolf Street, Syracuse, New York 13208, Phone (315) 477-7000. 3. Visually check for undue heating evidenced by discoloration of wires or other components, damaged parts, or leakage evidenced by water or corrosion in the interior. Replace all worn, damaged, or malfunctioning components, and clean gasket seals before putting the luminaire back into service. 3._______ Verify installed conduit plugs are torqued to 42-52 ft.-lbs. for 3/4” plugs and 58-68 ft.-lbs. for 1” plug. 4. Electrically check to make sure that all connections are clean and tight. 5. Mechanically check that all parts are properly assembled. 6. If the lens is removed from the fixture, the lens gasket must be replaced to maintain restricted breathing ratings. Driver Option Ambient Supply Wire Class II, Div. 1 Simultaneous Rating Class I, Div. 2/ Zone 2 AEx nA nR; Ex nA nR Zone 21 AEx tb IIC; Class III, Div. 1; Class II, Div. 1, Groups E, F, G UNV1 VDC 40°C 75°C T5 T3C T6 T72°C UNV1 VDC 55°C 90°C T4A T3B T5 T87°C UNV34 40°C 75°C T5 T3C T4 T70°C UNV34 55°C 90°C T4A T3A T4 T85°C RL, GL, BL, AL 40°C 75°C T6 T4A T5 T60°C RL, GL, BL, AL 55°C 90°C T6 T4A T4 T75°C 4._______ Verify supply wires are connected to luminaire wire leads (or terminal block) per wiring diagrams. Table 1 All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Crouse-Hinds “Terms and Conditions of Sale,” and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith. IF 1662 • 10/14 Copyright © 2014, Eaton’s Crouse-Hinds Business Page 3 Eaton’s Crouse-Hinds Business 1201 Wolf Street, Syracuse, New York 13208 Copyright © 2014 IF 1662 Revision 3 Revised 10/14 Supercedes 08/13 Champ LED 照明 VMVシリーズLED照明器具 取扱説明書 IF 1662 【こちらの取扱説明書は大切に保存してください。】 使用方法 インされています。 Champ VMV シリーズ照明器具は米国電気規程(NEC)に定義、区分され た危険地域の使用に適しています。 4. すべての適用可能なコードに対応する方法で、下記 配線図に従って照明器具リード線あるいはターミナ ル・ブロックに供給ワイヤーを接続してください。 図2b参照。電気的な接続をすべてきつく締めてくだ さい。 5. すべてのワイヤーが電源内部で安全であることを確 かめて、カバー部材上に電源を閉じてください。30 in.-lbsへの捕虜閉鎖ねじを締めてください。(3.4 N-m) 電源器材上にある2 bossがカバー部材に接し ていることを確認してください。 6. 電源をオンにしてください。 図2a 照明器具ネームプレートにある具体的な区分情報、最大周囲温度の適 合性、付随する動作温度(T-code)をご参照ください。 また船舶や湿地場所、振動のある場所、屋内外で使用できるようデザ VMV: VMV3L – 11L NEC/CEC 100-277VAC/100-250VDC Ex nA nR IIC T6 Gc -40°C to +40°C Ex nA nR IIC T5 Gc -40°C to +55°C Ex tb IIIC T72°C Db IP66 -40°C to +40°C Ex tb IIIC T87°C Db IP66 -40°C to +55°C • Class I, Division 2, Groups A, B, C, D • Class II, Groups E, F, G • Class III • Class I, Zone 2 nA nR • Zone 21 tb • Simultaneous Presence • Wet Locations, Type 4X ** ** UL Standards • UL 844 Hazardous (Classified) • UL1598 Luminaires, UL1598A Marine 347-480VAC Ex nA nR IIC T4 Gc -40°C to +55°C Ex tb IIIC T70°C Db IP66 -40°C to +40°C Ex tb IIIC T85°C Db IP66 -40°C to +55°C CSA Standard • CSA C22.2 No. 137 ** IEC/ATEX Standards • • • • • • IEC 60079-0:2011 / EN 60079-0:2012 IEC 60079-15:2010 / EN 60079-15:2010 IEC 60079-31:2008 / EN 60079-31:2009 IEC 60529:2001 / EN 60529:2001 IEC 60598-1:2008 / EN 60598-1:2008 IEC 60598-2:2008 / EN 60598-2:2008 II 3 G Ex nA nR IIC T4 Gc -40°C to +55°C II 2 D Ex tb IIIC T70°C Db IP66 -40°C to +40°C II 2 D Ex tb IIIC T85°C Db IP66 -40°C to +55°C VMVAL, RL, GL, BL 100-277VAC Ex nA nR IIC T5 Gc -40°C to +40°C Ex nA nR IIC T4 Gc -40°C to +55°C Ex tb IIIC T60°C Db IP66 -40°C to +40°C Ex tb IIIC T75°C Db IP66 -40°C to +55°C Fixture Markings • • ** • • II 3 G Ex nA nR IIC T6 Gc -40°C to +40°C II 3 G Ex nA nR IIC T5 Gc -40°C to +55°C II 2 D Ex tb IIIC T72°C Db IP66 -40°C to +40°C II 2 D Ex tb IIIC T87°C Db IP66 -40°C to +55°C IECEx UL 13.0052X DEMKO 13 ATEX 1305741X DEMKO 13 ATEX 1475031X See Table 1 for temperature codes ** ** II 3 G Ex nA nR IIC T5 Gc -40°C to +40°C II 3 G Ex nA nR IIC T4 Gc -40°C to +55°C II 2 D Ex tb IIIC T60°C Db IP66 -40°C to +40°C II 2 D Ex tb IIIC T75°C Db IP66 -40°C to +55°C Input voltage: 100-277 VAC 50/60 Hz 100-250 VDC 347-480 VAC 50/60 Hz Open Hinge 図1 注意 Set Screw 発火、爆発、感電の危険性を防ぐため、この製品は全ての適切な電 気コードに従って資格のある電気技術者によってのみ取付、調査、 管理すること。 注意 Ground Wires 注意 感電を防ぐには: 爆発を防ぐには: 取付、メンテナンスの前、もしくは最中は必ず電源をオフにする こと。 照明器具は器材の接地線と共に配線システムに従って供給するこ と。 火傷を防ぐには: レンズや保護部分の温度が低くなっていることを確認し作業を行 うこと。 設置方法 固定: 供給電圧が照明器具の電圧と同じであることを確かめること。 作業温度が危険な状態にある大気の発火温度を超過する場合、取り 付けを行わないこと。 照明器具ネームプレートに明記された温度以上の周囲温度の中で作 動しないこと。 照明器具ネームプレート上で指定されている適切な供給配線を使 用すること。 ガスケット・シールはすべて清潔であること。 施工開始前に、照明器具の電源を必ずオフにすること。施工時はし っかりと閉じておくこと。 1.カバー部品を固定位置へ取り付ける。 • 天井および壁への取付:取付部分に印をつけ、必要な箇所へ 穴を開ける。1/4” (6mm)ボルトもしくはラグスクリューが好 ましい(本製品には含まれていません)。 • つり下がった部分、円錐、支柱への取付:適したNPTサイズの 電線管上へ安全に装着する。電線管ハブのネジをしっかりと 締め装着する。図1参照。 • 備品への防水の為、電線管へは潤滑性Eaton’s Crouse-Hinds HTLを使用すること。 静電気による発火危険を減らすため、爆発性の大気がある場合、 照明器具との接触を避けること。湿った布でのみ取り除くことが 可能。 配線 1. カバー部材へフィールド配線を引いてください。 2. 導管プラグを備えた全ての使用していない電線管エントリーを 閉じてください。 摩擦防止と水密性を保証するため、施工前に Eaton’s Crouse-Hinds HTLで備えた導管プラグを潤滑にしてくだ さい。少なくとも5本のねじれた導線と使用中の導線 を安全にする 必要があります。(42-52 ft.-lb. for 3/4” plugs, and 58-68 ft.-lb. for 1” plugs). 3. カバー部材留め金にLED照明器具を取り付けてください。図2a参 照。 IF 1662 • 10/14 Copyright © 2014, Eaton’s Crouse-Hinds Business Page 3 図2b IF 1662 • 10/14 Copyright © 2014, Eaton’s Crouse-Hinds Business Page 2 ワイヤーガード設置方法 付属のねじを完全に取り除かないように電気保護線を緩ませてくだ さい。 もし既に緩んでいる場合、次の手順へ移ってください。 一番下のキャスティングに保護部分が安全に取り付けられるまで電気 保護線に取り付けら れたねじをきつく締めてください。電気保護線が器材上で簡単に回転 しない場合、ねじは十分にしっかりと固定されています。 電気保護線を一番下のキャスティングにある器材底面の枠上に押しな がら配置してください。 電気保護線が最下層にあること、完全に枠上にあることを確認して ください。 注意: ねじが通り抜ける板金タブは安全に固定されている保護部分と接続し ている必要はありません; 2つのつまみが互いに触れなくても電気保 護線の安全性は保たれています。 field assembled fixtures MOUNTING MODULE NOTES: MOUNTING MODULE SERIES ANGLED BPM2 BPM3 感電を防ぐには: 取り付けとメンテナンスの事前、もしくは最中は電源がオフになっ ていることを確実にすること。照明器具は接地線器材と一緒に電線 システムによって供給すること。 火傷を防ぐには: メンテナンスを行う際、グローブや屈折レンズ、ランプの温度が低 くなっていることを確実にすること。 取り付け時の確認項目 Champ® VMV Series Lighting Fixtures, 13-11L Watt PENDANT APM2 APM3 HPM2 5._______ 全ての電気接続がきつく締まっていることを確認してく ださい。 注意 CEILING CM2 CM3 WALL TWM2 TWM3 STANCHION PM5 JM5 - 2: indicates 3/4” NPT thread - 3: indicates 1” NPT thread - 5: indicates 1-1/2” thread - Pendant, angled, ceiling, and stanchion mounts have one (1) conduit entry; ceiling and wall mounts have five (5) conduit entries 1._______ 導管プラグにHTL潤滑剤が十分に塗布されていることを確認 してください(プラグ初めのねじ切り部分に約1/8” 程度のHTL 潤滑剤の添付をお勧めします)。またカバー部材にある全ての 未使用の電線管は潤滑したプラグで閉じていることを確認して ください。 6._______ 全ての導線が安全、きちんと電源器材内部にあり、ワイヤ ー端子上にないことを確認してください。電源器材をカバー部 材へ締めてください。 VMV*L PVM*L 2._______ 導管プラグが少なくとも5ヶは固定されていることを確 認する。 メンテナンス 交換部品 1.視覚的、電気的、機械的な検査を定期的に行ってください。使用環 境と使用頻度により検査を行うものとしますが、最低でも一年間に 一回の検査をお勧めいたします。 Eaton’s Crouse-Hinds VMVとVMVおよびNVMVシリーズであるChamp照明 器具一式は、数年に渡り信頼できる照明パフォーマンスを提供するた めデザインされています。しかしながら、万が一、交換部品の必要性 があれば、指定のEaton’s Crouse-Hindsの代理店を通じてお問い合わ せをすることが可能です。 全米防火協会NFPA、No.70Bに記述されている電気防止管理プログラム を推奨し、 電気機器メンテナンス (www.nfpa.org) の実践を推薦します。 2.レンズは恒常的な点灯を保証するため定期的に掃除を行ってくださ い。きれいな湿った布でお手入れをし、清潔に保ってください。十 分でない場合、Collinite NCFかDuco #7のような、マイルドな石鹸 あるいは液体のクリーナーを使用してください。研磨剤、もしくは 強いアルカリ性か酸性のクリーナーを使用しないでください。ダメ ージを与える可能性があります。 7._______付属の閉鎖ねじが30 in.-lbsの強度ににきつくしめられて いることを確認してください。また、電源の2 (2) bossがカバ ー部材に接していることを確認してください。 また、お客様のお近くのEaton’s Crouse-Hinds営業所からアシスタン スを得ることも可能です。 Eaton’s Crouse-Hinds 営業部 1201 Wolf Street, Syracuse, New York 13208, TEL (315) 477-7000 3._______ 導管プラグが3/4”のプラグには42-52 ft.-lbs、1”のプ ラグには58-68 ft.-lbsのトルクで締められていることを確認 します。 3.電線やその他部品の変色、破損、もしくは水漏れ、内部腐食により 不適切な結果の出た加熱部分は視覚的に確認してください。全ての 使用済み、または破損、不具合の部品を交換し、照明器具を戻す前 にガスケットシールを清潔にしてください。 4.全ての接続が清潔でしっかりと締まり、電気的に問題がないか確認 を行ってください。 5.全ての部品がきちんと組み立てられ、機械的に問題がないか確認を 行ってください。 6.レンズが器材から取り除かれる場合、制限呼吸を維持するためレン ズガスケットを交換してください。 4._______ 配線図ごとに、供給されたワイヤーが照明器具リード線(あ るいはターミナルブロック)に接続していることを確認します。 Driver Option Ambient Supply Wire Class II, Div. 1 Simultaneous Rating Class I, Div. 2/ Zone 2 AEx nA nR; Ex nA nR Zone 21 AEx tb IIC; Class III, Div. 1; Class II, Div. 1, Groups E, F, G UNV1 VDC 40°C 75°C T5 T3C T6 T72°C UNV1 VDC 55°C 90°C T4A T3B T5 T87°C UNV34 40°C 75°C T5 T3C T4 T70°C UNV34 55°C 90°C T4A T3A T4 T85°C RL, GL, BL, AL 40°C 75°C T6 T4A T5 T60°C RL, GL, BL, AL 55°C 90°C T6 T4A T4 T75°C Table 1 この取扱い説明書に明記されたステートメント、技術、および推奨情報は信頼できる情報もしくはテストに基づいています。しかし その正確さもしくは完全性は保証されるものではありません。Crouse-Hindsにおける“安全性における取引条件”に従い、この製品 の使用状況は弊社管理外となり、購入者は使用目的に沿って製品の適応性を十分に確認する必要があり、またこの使用に関するすべ ての危険性、責任を理解して使用するものとする。 IF 1662 • 10/14 Copyright © 2014, Eaton’s Crouse-Hinds Business Page 3 Eaton’s Crouse-Hinds Business 1201 Wolf Street, Syracuse, New York 13208 Copyright © 2014 IF 1662 Revision 3 Revised 10/14 Supercedes 08/13
© Copyright 2024 ExpyDoc