T24-DM1 / T24-DM2 LCD Temperature Controller Overview of functions LCD temperature controller T24-DM1 / T24-DM2 provides the foundation for modern single room concepts Features LCD with white backlight Proportional output(s) DC 0-10V or 2-10V Adjustable P-band and I-time, setpoint range. Display selection Unoccupancy mode Memory retention after power failure 2-pipe(T24-DM1) or 4-pipe(T24-DM2) system External sensor TG-M10000 and TG-M10002 (optional) Technical Data T24-DM1 / T24-DM2 Nominal Voltage Power Consumption AC 24V 50/60 Hz (+/-15%, AC 20.4V ... 27.6V) 1VA @ AC 24V Ouptut(s) Built-in Sensor External Sensor (optional) Temperature Range DC 0-10V or 2-10V by jumper setting NTC thermistor , 10k ohm @ 25°C Probe type, TG-M10000; Duct type, TG-M10002 Display : 0 to 40°C Set point : 5 to 40°C, 0.5K increment Mode ON / STANDBY Cooling / Heating (**Auto change-over between cooling & heating ) **Deadband Proportional Band Integral Time Display Offset Temperature Differential Lower Set Point Limit [LSP] Upper Set Point Limit [USP] **Adjustable 1K to 5K between cool & heat (Factory setting 3K) Adjustable 1 to 10K (Factory setting 5K) Adjustable 0 to 300 seconds (Factory setting 60 seconds) Display temperature adjust: -2,-1,0,1,2 (Factory setting 0) 1K Adjustable 5-35°C (Factory setting 5°C) Adjustable 9-40°C (Factory setting 40°C) Unoccupancy Set Point Range Cooling 5°C to 36°C (Factory setting 26°C) Heating 9°C to 40°C (Factory setting 16°C) Unoccupancy contact input Connection Voltage-free dry contact only 2 Screw terminals, max. 1.0mm or AWG #18 Ambient Humidity Body Material Max. 90% r.h. , non-condensing Self-extinguishing, Molded ABS Weight Dimensions (L x H x D) Mounting Degree of Protection Agency Approval 120g 86 x 86 x 28.5 (mm) Wall mounted, holes separated 60mm vertically, 2x screws provided IP 30 CE mark compliant to EMC Directive **Only available on T24-DM2 Installation and Dimensions 86 mm Subject to technical change V1.3 01062010 To be opened by accredited servicing agents only Electronic control - Type 2.B action (micro-disconnection operation) Separate collection for electrical and electronic equipment 60 mm 86 mm 28.5mm 1 T24-DM1 / T24-DM2 LCD Temperature Controller Setup Menu 1. Enter setup menu Switch the unit to ‘standby’ mode, press and hold “ holding “ - ” for 10s until “ S-F ” appears. ”, then press“ - ” , hold “ - ” and release “ ”, keep 2. Select sub-menu “ S-F ” or “ S-P ” After entering setup menu and “ S-F ” appears, press “ + “ or “ - ” to select “ S-F ” or “ S-P ”, confirm by “ 3. Select function under sub-menu Under sub-menu, press “ 4. Adjust the parameters Press “ + ” or “ - ” to adjust the parameters values. 5. Save changes & go back to sub-menu Press and hold “ 6. Exit setup menu Time out Under sub-menu, press “ ” to exit. If there is no key operation within 30 seconds, new setting will not be stored and exit automatically. Sub-Menu S-F Firmware version Temperature display Selection for un-occupancy mode Display selection S t uA c Restore factory setting rF Sub-Menu S-P Proportional band Integral time Upper set point limit Lower set point limit Un-occupancy set point range-cool Un-occupancy set point range-heat Display offset **Deadband A I U L C H n d ”. ” key momentarily to select the functions sequentially. ” , then press“ + ” , hold “ + ” and release “ ”, keep holding “ + ” for 1s. Display only o Display in C To select uA1 or uA2 cAt = display ambient temperature cSP = display setpoint value rFC = current setting; rFS = restore factory setting [Factory setting rFC] To select value from 1 to 10K To set the value from 0 to 30 (1=10s) o To set the value from 9 to 40 C o To set the value from 5 to 36 C o To set the value from 5 to 40 C o To set the value from 5 to 36 C To set the value to -2,-1,0,1, or 2 To set the value from 1 to 5K [Factory setting 5K] [Factory setting 6] o [Factory setting 40 C] o [Factory setting 5 C] o [Factory setting 26 C] o [Factory setting 16 C] [Factory setting 0] [Factory setting 3K] o [Factory setting C only] [Factory setting uA1] [Factory setting cAt] **Only available on T24-DM2 Jumper Setting JP 1 Opened Closed For external sensor For built-in sensor [Factory setting] JP 2 Opened Closed For DC 0-10V ouput For DC 2-10V ouput [Factory setting] JP2 JP1 Wiring Diagrams GND OCU C om A C 24V A C 24V T24-DM2 T24-DM1 Terminals for sensor SR1 C om External sensor Occupancy contact 1 1 2 2 Valve Actuator Cool Valve Actuator 0-10V 2 3 3 0-10V 2 3 3 4 5 F eedback 1 4 5 F eedback 1 5 3 0-10V 2 5 *2 & 4 are internally shorted *2 & 4 are internally shorted 5 1 F eedback Heat Valve Actuator Subject to technical change V1.3 01062010 Notes 22 or 24 AWG twisted shielded pair double insulated cable is recommended as sensor cable and its length must not exceed 25m. Do not bundle and run power cable and sensor cable in the same conduit. When using external sensor, run the cable away from any electric motor or power cable. Remove JP1 whenever using external sensor. Un-occupancy contact closure activates un-occupancy mode. To be opened by accredited servicing agents only Electronic control - Type 2.B action (micro-disconnection operation) Separate collection for electrical and electronic equipment 2 T24-DM1 / T24-DM2 LCD Temperature Controller Error code Error codes will be displayed on LCD display unit with below errors. E-1 E-2 E-3 EEPROM read/write error Temperature sensor open circuit Temperature sensor short circuit *If jumper JP1 is opened and external sensor is used, E-2 means the external sensor may have been disconnected from terminals SR1 and GND. Check the external sensor’s connectivity and resistance value. Setup Menu - description Menu Main S- F System Function Selection Sub MCU firmware (software) revision level Appears once only after entering the setup mode t Temperature unit Fixed at ºC, not changeable. Appears once only after entering the setup mode. uA Activation selection for unoccupancy mode uA1 = unoccupancy mode can only be activated when thermostat is in operating mode (factory setting) uA2 = unoccupancy mode can be activated when thermostat is in either standby mode or operating mode Display selection cAt = display ambient temperature (factory setting) cSP = display setpoint value rFC = Retain current settings (factory setting) rFS = Restore factory settings rF Restoration of factory settings A Proportional Band To set proportional band from 1 to 10K, in 1K increments (factory setting 5K) I Integral time for PI control U Upper occupancy set point limit setting To set integral time from 0 (0s) to 30 (300s) in numeric 1 (10s) increments. [factory setting 6 (60s)]. Setting 0 means integral time being turned off. To set upper occupancy set point limit, adjustable between current lower set point limit value and 40°C (factory setting 40°C). The program is set such that there is always a minimum separation of 4 degrees maintained between the upper occupancy set point limit value and the lower set point limit value. L Lower occupancy set point limit setting To set lower occupancy set point limit, adjustable between current upper set point limit value and 5°C (factory setting 5°C). The program is set such that there is always a minimum separation of 4 degrees maintained between the upper occupancy set point limit value and the lower set point limit value. C Unoccupancy cooling set point setting To set unoccupancy cooling set point, adjustable between current unoccupancy heating set point value and 40°C (factory setting 26°C). The program is set such that there is always a minimum separation of 4 degrees maintained between the unoccupancy cooling set point value and the unoccupancy heating set point value. H Unoccupancy heating set point setting To set unoccupancy heating set point, adjustable between current unoccupancy cooling set point value and 5°C (factory setting 16°C). The program is set such that there is always a minimum separation of 4 degrees maintained between the unoccupancy cooling set point value and the unoccupancy heating set point value. n Offset adjustment of temperature indication (field recalibration of measured temperature) n 2 = temperature indication plus 2 degrees n 1 = temperature indication plus 1 degree n 0 = no offset (factory setting) n-1 = temperature indication minus 1 degree n-2 = temperature indication minus 2 degrees Deadband adjustment for dual-output models only Auto change-over Cooling Heating On To set auto cool/heat changeover deadband value from 1 to 5K. [factory setting 3K (± 1.5K of set point value)]: when ambient temperature is 1.5K above set point value, controller will go into cooling mode or when ambient temperature is1.5K below set point value, controller will go into heating mode. **d Subject to technical change V1.3 01062010 Description S c S- P System Operating Parameter Setting Function Off Set point 1.5K 1.5K **only available on T24-DM2 To be opened by accredited servicing agents only Electronic control - Type 2.B action (micro-disconnection operation) Separate collection for electrical and electronic equipment 3
© Copyright 2024 ExpyDoc