NOTICE INVITING TENDER FOR REPLACEMENT OF 5

SCOPE OF WORK
1. The agencies must visit the site for location to install the Air-handling & allied work before
quoting your prices.
2. The work proposed under this tender includes supply,installation,testing & commissioning of
05 Nos double skin airhandling units with mixing box having cap.25000cfm each at terrace.
3. Providing & Fixing at site all main equipments associated with the system as asked under
technical specifications.
4. To execute all incidencal work at site including material supply at site associated with ac
system asked in technical specifications,Nature of such work will be sheet metal duct,chilled
water piping and drain piping etc.incidental civil work,incidental electrical work,cable etc.at
site for all manufactured items at work and also item fabricated at site.
5 Routine testing,pressure testing of complete AHUs at site.
6. Connected civil work such as foundation and other repair work inside AHU Room for
installation of AHU/equipments in all respect.
7. Performance testing at site complete system as per various technical requirement as stipulated
in performance testing clause.
8. Dismentling of existing 05Nos AHU including duct connection,pipe connections,pipe
connection and taking out these from site under rebate item as per schedule of work.
9. Shifting/modification if any in electrical/cubical panel refixing the same alongwith the motor
connection and AHU put in operation etc.
10. Supply,installation,testing & commissioning of allied work like Butterfly valves,balancing
valves,Y-strainer,3-way mixing valve,Airvent etc and all other connected accessories.
11. The existing airhandling units at site i.e at terrace is equipped with 29 Nos units ,out of them
05Nos AHUs proposed for replacement which are in more critical conditions.
12. New chilled waterline with valves & fittings of 05 No.AHUs shall be connected with existing
header ring laid for all 29No AHUs at terrace.
13. The drawings forming part of these specifications provide a feasible scheme for locating the
equipment.The contractor may re-arrange the equipment for improving the layout and meeting
the site conditions.All such changes shall,however be subject to the engineerincharge/consultant approvals.these drawing are not meant to be working drawings,which shall
be prepared by the contractor as reqd.even if the work awarded to be separate agency for
ducting and insulation work,it will be rensponsiblity of contractor to prepare the ducting
drawing and get it approved by the engineer incharge/consultant for ducting work at site.
14. The Airhandling unit alogwith allied work shall be tested as per specification given in tender
documents.
15. All 05 Nos AHUs shall be assembled inside of AHU Rooms.
General Manager(Tech.)
SCHEDULE OF EQUIPMENT PROPOSED
S.No. Description
Unit
Condition of Services
1.0
Air Handling Units 25000CFM(Double Skin)withReturn air/fresh air mixing Box
1.1
Manufacturer Name
--
1.2
Model
--
1.3
Type of unit
--
1.4
Overall Dimension
--
1.5
Unit Base
--
1.6
Drain Pan
--
22Gauge,SS304 Tray insulated
with 13mm closed cell nitril rubber
1.7
Access Door
--
Fan section & Mixing Chamber
2.0
Panel
2.1
Pre-coated G.S.S/Powder coated outer skin
--
0.6mm
2.2
Plain G.S.S/Powder coated inner skin
--
0.6mm
2.3
Thickness of insulated Panel
--
2.4
Frame type
--
2.5
Frame material
--
3.0
Fan & Fan Motor
3.1
Fan type
--
DIDW Backward Curved
3.2
Model
--
BDB900/TM(CLI)
3.3
Operating condition
--
Ducted
3.4
Air Volume
--
25000CFM
3.5
Static Pressure
--
65mmwg
3.6
Fan Total efficiency
--
81%
3.7
Fan static efficiency
--
75%
3.8
Fan speed
--
750-800 rpm
Carrier /ETA/Zeco/edgetech/Waves
Floor mounted
G.S.S channel
25mm,CFC free PUF injected,
density 40kg+ 2kg/cu.m
Moduler
Aluminium extruded
3.9
Noise level
--
Less then 80dba
3.10
Fan to be certified by
--
AMCA
3.11
Make of Fan
--
Kruger/Greenheck
3.12
Type of Motor
--
TEFC(IPP-55)
3.13
Motor
--
D180L 15KW(20H.P)
3.14
4. 0
Make of Motor
Coil Data
--
Crompton/ABB/Havells
4.1
Make
--
4.2
Air Flow Rate
--
25000CFM
4.3
Coil Casing
--
G.I
4.4
Material of Tube
--
Copper
4.5
Tube Thickness
--
0.41mm
4.6
Tube Dia
--
½”(Half inches)
4.7
Coil face area
--
50 – 54 Sqfts
4.8
No. of Coil
--
2Nos
4.9
No.of Raw
--
6 raw deep
4.10
Header material
--
MS
4.11
Test pressure
--
21kg/sqcm
4.12
Fins material
--
Aluminium
4.13
Thickness
--
0.15mm
4.14
No.of fins per inch(FPI)
--
12Nos.
5.0
Type of Filter Section
5.1
Mixing Box
--
To be included
5.2
Volume Control Damper
--
For R/A inlet & F/A inlet
To be included
5.3
Filters
--
Washable synthetic
5.4
Efficiency of Pre-filter
--
90% down to 10 Microns
5.5
Make of filters
--
Spectrum/Thermadyne/Athlete
Carrier/ETA/Zeco/edgetech/Waves
List of Approved `Makes'
S.No.
Items
Acceptable Makes
1.
Air-Handling Units
:
Carrier/ETA/Zeco/edgetech/Waves
2.
DIDW Backward Curved Fan
:
3.
Cooling Coil
:
4.
Electric Motor
:
Crompton/ABB/Havells
5.
Prefilter
:
Spactrum/Thermadyne/Athlete
6.
Chilled Water M.S Pipe
:
Jindal,Hissar/Tata
7.
G.I Drain Pipe
:
Jindal,Hissar/Tata
8.
Butterfly Valve
:
Audco/Advance
9.
Balancing Valve
:
Advance/Sant
10.
Y-Strainer
:
Advance/Sant
11.
Ball valve
:
Zoloto/Leader
12.
SS Pressure Gauge
:
H.Guru/Emrald/Fiebig
13.
Thermometer
:
H.Guru/Emrald/Fiebig
14.
3-Way Mixing Valve
:
Anergy/Honeywell
15.
Auto Airvent
:
Anergy/Honeywell
16.
G.I Sheet
:
Sail/Jindal/Tata
17.
Glass wool Insulation
:
U.P.Twiga/Malanpur
18.
Nitril Rubber Insulation
:
Armacell/Paramount
19.
Aluminium Sheet
:
Balco/Nalco/Hindalco
20.
Fire Damper
:
Servex/Carryaire/Ravistar
Kruger/Greenheck
Carrier/ETA/Zeco/edgetech/Waves
Schedule of Work
Sub - Upgradation of HVAC System at scope complex,7-Lodhi Road,New Delhi-110003.
SH - Replacement of existing 05No AHUs installed at Terrace.
S.No.
1
Deccription of items
Unit Qty Rate Amount
Dismentling of existing AHU's
Dismentling of existing AHU's alongwith fittings
supports etc. locating on terrace at a specified
Space along with all accessories like pipes, valves,
insulation, ducting etc. as per Direction of Engineerincharge.
5
No.
5
Air Handling Units
Rates not to be quoted here
2
No.
S.I.T.C of Double skin floor mounted chilled/Hot
water Air-Handling Units with mixing box complete
with DIDW Backward Curved fan suitable for static
pressure of 65mmwg.& noise level should not
exceed 76 dba at 1mtr with fan total efficiency not
less than 80% ,Fan motor TEFC(IPP-55),15KW
suitable for operation through existing star-delta
starter panel as connection of motor with existing
cable/control cables, Cooling coil 6row deep copper
tube
with
vent/purging
arrangement
,dia
12.5mm,thickness 0.41mm,al.fins12Nos FPI,Filter
plenums with mixing box.drain pan of suitable depth
16G thick,SS304,insulated with closed cell
polyurathene 10mm thick insulation,with necessary
vibration isolation arrangements,fire retardant
flexible connections and all other accessories i/c
supply,return and fresh air dampers ,AHU complete
in working conditions i/c wiring,foundation complete
as per specifications and drawings etc as reqd and
as per direction of engineer - Incharge.
25000 cfm AHU, SP,65mmwg.
3
Controls for AHUs
Supply, fixing,testing & commissioning of controls
complete with wiring etc. three way mixing valve
with linkage and actuator, modulating termperature
controller 80 mm dia etc. as required.
4
No.
5
Rmt
110
No.
10
No.
5
No.
5
Chilled water Piping
80 mm dia.
5.
Supply, fixing, testing and commissioning of
following sizes Butterfly,Balancing valves, Ystrainers in chilled water lines complete with
companion flanges, nuts, bolts, gaskets, supports
etc. duly insulated on chilled water line as per
requirement and specified and as per direction of
Engineer-Incharge.
5.1
Butterfly Valves (PN - 16)
80 mm dia.
5.2
Balancing Valves (PN - 16)
80 mm dia
5.3
Y Shape Strainer (PN - 16)
80 mm dia
5.4
Supply and fixing of Zoloto Make forged Brass Ball
valve o (screwed) with Hex nipple elbow (screwed)
i/c providing and welding the same size socket on
the MS pipe at terace complete as per site
requirement and as per direction of Engineer
incharge
Rates not to be quoted here
Supply, fixing, testing and commissioning of Heavy
class mild steel black steel pipes confirming to IS:
1239
with
all
necessary
fittings,
Bend,reducer,Tee,Flanges,supports and
PUF
insulation having density
36Kg±2Kg/m³with
polythene cover and then 26 gauge aluminium
cladding etc. as required and as per direction of
engineer-incharge.
25 mm dia
5.6
5.7
6
10
No.
10
No.
10
No.
10
mtrs
50
Sqm
340
Sqm
280
SS Pressure gauge 4"dial type with Ball valve
1/2"dia with reqd accessories etc as reqd.
Thermometer dial type with reqd accessories etc as
reqd.
Providing, fixing, testing and commissioning of auto
airvent in chilled water line in AHU room complete
with all accessories settings etc. 10 mm (3/8") dia.
G.I. Drain Piping
Providing, fixing, testing and commissioning of G.I.
drain piping with 19 mm thick nitrile rubber insulation
complete with fittings like elbow,Tee,reducer,socket,
supports as per specification and drawings 50 mm
dia.
50mm dia
7
G.I Sheet Ducting(Rectangular)
Providing, fixing, testing and commissioning of sheet
metal ducting complete with supports, dampers etc.
as per specifications etc as reqd.
22 Gauge
8
Insulation
Providing and fixing of glass wool insulation 50mm
thick having density 32Kg/m³ on ducts using resin
bonded glass wool covered with checken wire mesh
and finished with 26 Ga aluminium cladding etc as
reqd.
Rates not to be quoted here
5.5
No.
9
Dismentling of existing Fire Dampers and Supply &
Fixing of New G.I Fire Dampers made out of
16Gauge G.I Sheet 150mm depth with fusible link
etc as reqd and as per direction of engineerincharge.
Sqm
15
No.
5
Sub-Total
10
Rebate
Rebate,credit/buy-back of old existing AHUs
complete with,fan,fan motor,cooling coil,filters &
other connected accessories etc as reqd and as per
direction of engineer-incharge.
Total
Rates not to be