PT CV SYMBOL COLD WATER IN J62A-JBXP ET JBX250 PT PRV CV PT HOT WATER SUPPLY LINE ¾” 120VAC, 4.2A GAS TANKLESS POWER SUPPLY ET ¾” 120VAC, 1/25 HP PUMP INSTALLED ON BOOSTER INLET CONTROLLED BY SWITCH INSTALLED ON BOOSTER JBX250 185°F T&P RV RV ¾” CONDENSATE TO DRAIN PT RV T&P RV J62A-JBXP 185°F LEGEND DESCRIPTION ELECTRIC BOOSTER HEATER, 6 GAL., 2KW @ 120VAC GAS TANKLESS BOOSTER HEATER, 250,000 BTU/HR PRESSURE REDUCING VALVE CHECK VALVE EXPANSION TANK COMBINATION PRESSURE AND TEMPERATURE GAUGE PRESSURE RELIEF VALVE T&P RELIEF VALVE 120VAC, 18A ELECTRIC BOOSTER AND PUMP POWER SUPPLY PT CV RECIRCULATION LINE 185°F TO FINAL RINSE OF DISH HOT WATER OUT NOTES: MACHINE PRV 1. JBX250, J62A-JBXP, pump, PRV, (4) pressure and temperature gauges, T&P relief valve, and pressure only relief valve supplied by Hubbell. Additional devices and piping supplied by others. 2. Fresh air intake, exhaust venting, and gas supply not shown. 3. The maximum length of piping from the J62A-JBXP to the dish machine is 8 feet and it is recommended that the piping is insulated. MODIFIED RECIRC LOOP TO BYPASS A ELECTRIC BOOTER PRD 9/18/14 4. To maintain proper recirculation the maximum allowable APPROVED DESCRIPTION DATE REV. pressure drop through the piping is 5.2 psi (12 ft H20). The REVISIONS recommended maximum combined length of the 3/4" hot water Stratford, CT 06615 NAME DATE supply and recirculation line is 240 feet (insulated) or (203) 378-2659 DRAWN PRD 3/24/14 64 feet (uninsulated). 1/2" piping is not recommended. The Electric Heater Company CHECKED 3/24/14 WEN III 5. For maximum efficiency it is recommended ENG APPR. PRD 3/24/14 Customer: that the hot water supply and recirculation MFG APPR. WEN III 3/24/14 Description: PROPRIETARY AND CONFIDENTIAL lines be insulated. DIMENSIONS ARE IN INCHES THE INFORMATION CONTAINED IN THIS RECOMMENDED JBX TOLERANCES 6. Pump is a Taco Model 008-SF6, 120 VAC, 60 Hz., DRAWING IS THE SOLE PROPERTY OF RECIRCULATION P&ID (UNLESS OTHERWISE SPECIFIED): THE ELECTRIC HEATER COMPANY. ANY 1/25 HP, stainless steel, flanged with 3/4" NPT REPRODUCTION IN PART OR AS A WHOLE FRACTIONAL ± ¼ SIZE DWG. NO. REV. THE WRITTEN PERMISSION OF ANGULAR: MACH ±½° BEND ±1° flange kit and includes tee to be installed bewteen WITHOUT A JBX-PID-WR THE ELECTRIC HEATER COMPANY IS A TWO PLACE DECIMAL ±0.01 the pump and the electric booster heater. PROHIBITED. THREE PLACE DECIMAL ±0.005 SCALE:1:1 FSCM: 19857 SHEET 1 OF 1
© Copyright 2024 ExpyDoc