Descarga el catálogo comercial - Carrier

48VG ---A
Performancet 16 SEER 2---Stage Packaged Air
Conditioner and Gas Furnace System with PuronR
(R ---410A) Refrigerant
Single and Three Phase
2 to 5 Nominal Tons (Sizes 24---60)
Product Data
heating/cooling size combinations with voltage options to meet
residential and light commercial requirements. Units are
lightweight and install easily on a rooftop or at ground level. The
high tech composite base eliminates rust problems associated with
ground level applications.
Innovative Unit Base Design
On the inside a high--tech composite material will not rust and
incorporates a sloped drain pan which improves drainage and helps
inhibit mold, algae and bacterial growth. On the outside metal base
rails provide added stability as well as easier handling and rigging.
Convertible duct configuration
Unit is designed for use in either downflow or horizontal
applications. Each unit is converted from horizontal to downflow
and includes two horizontal duct covers. Downflow operation is
provided in the field to allow vertical ductwork connections. The
basepan seals on the bottom openings to ensure a positive seal in
the vertical airflow mode.
Efficient operation
A09033
Fig. 1 -- Unit 48VG--A
Single--Packaged Products with Energy--Saving Features and
PuronR refrigerant.
S 15.0 to 16.0 SEER
S 12.0 -- 12.5 EER
S Up to 80.4% AFUE
S Meets Energy Star requirements
S Direct Spark Ignition
S Factory--Installed TXV
S Multi--speed ECM Blower Motor--Standard
S Sound Levels as low as 72dBA
S Two Stage Cooling
S Two Stage Heating (208/230 VAC models)
S Dehumidification Feature
FEATURES/BENEFITS
One--piece heating and cooling units with low sound levels, easy
installation, low maintenance, and dependable performance.
Puron Environmentally Sound Refrigerant is Carrier’s unique
refrigerant designed to help protect the environment. Puron is an
HFC refrigerant which does not contain chlorine that can harm the
ozone layer. Puron refrigerant is in service in millions of systems
proving highly reliable, environmentally sound performance.
Easy Installation
Factory--assembled package is a compact, fully self--contained,
combination gas heating/electric cooling unit that is prewired,
pre--piped, and pre--charged for minimum installation expense.
These units are available in a variety of standard and optional
High--efficiency design offers SEER (Seasonal Energy Efficiency
Ratios) of 15.0 to 16.0, 12.0 to 12.5 EER, and AFUE (Annual
Fuel Utilization Efficiency) ratings as high as 80.4%.
Energy--saving, direct spark ignition saves gas by operating only
when the room thermostat calls for heating. Standard units are
furnished with natural gas controls. A low--cost field installed kit
for propane conversion is available for all units.
48VGN--A units are dedicated Low NOx units designed for
California installations. These models meet the California
maximum oxides of nitrogen (NOx) emissions requirement of 40
nanograms/joule or less as shipped from the factory and MUST be
installed in California Air Quality Management Districts and
wherever a Low NOx rule exists.
Durable, dependable components
Compressors have two stages of cooling and are designed for high
efficiency. Each compressor is hermetically sealed against
contamination to help promote longer life and dependable
operation. Each compressor also has vibration isolation to provide
quieter operation. All compressors have internal high pressure and
overcurrent protection.
Monoport inshot burners produce precise air--to--gas mixture,
which provides for clean and efficient combustion. The large
monoport on the inshot (or injection type) burners seldom, if ever,
requires cleaning. All gas furnace components are accessible in one
compartment.
Turbo--tubulart heat exchangers are constructed of aluminized
steel for corrosion resistance and optimum heat transfer for
improved efficiency. The tubular design permits hot gases to make
multiple passes across the path of the supply air.
In addition, dimples located on the heat exchanger walls force the
hot gases to stay in close contact with the walls, improving heat
transfer.
Stainless steel heat exchanger available as factory installed option.
1
48VG -- A
Multi--speed ECM Blower Motor is standard on all 48VG--A
models.
Direct--drive PSC (Permanent Split Capacitor) condenser--fan
motors are designed to help reduce energy consumption and
provide for cooing operation down to 40_F (4.4_C) outdoor
temperature. Motormasterr II low ambient kit is available as a
field--installed accessory.
Thermostatic Expansion Valve -- A hard shutoff, balance port
TXV maintains a constant superheat at the evaporator exit (cooling
cycle) resulting in higher overall system efficiency.
Refrigerant system is designed to provide dependability. Liquid
filter driers are used to promote clean, unrestricted operation. Each
unit leaves the factory with a full refrigerant charge. Refrigerant
service connections make checking operating pressures easier.
High and Low Pressure Switches provide added reliability for the
compressor.
Indoor and Outdoor coils are computer--designed for optimum
heat transfer and efficiency. The indoor coil is fabricated from
copper tube and aluminum fins and is located inside the unit for
protection against damage. The outdoor coil is internally mounted
on the top tier of the unit.
Low sound ratings ensure a quiet indoor and outdoor
environment with sound ratings as low as 72dBA.
Dehumidification Feature
This unit has independent fan speeds for low stage cooling and
high stage cooling. In addition, 208/230 VAC models have the
field--selectable capability to run an enhanced dehumidification
(’DHUM’) speed on high stage cooling (as low as 320CFM per
ton). Coupled with the improved dehumidification associated with
low stage cooling, the DHUM speed allows for a complete
dehumidification solution independent of cooling stage. 208/230
VAC models also have independent fan speeds for low stage gas
heating and high stage gas heating. The dehumidification control
must open the control circuit on humidity rise above the
dehumidification set point.
NOTE: The enhanced dehumidification feature on high stage
cooling does not support use of an economizer.
Heating
S Reliable direct spark ignition system
S Two--speed PSC inducer motor with ball bearings (208/230 VAC
models)
S Low stage heating delivers 65% of high--stage capacity (208/230
VAC models)
Easy to service cabinets provide easy 3--panel accessibility to
serviceable components during maintenance and installation. The
basepan with integrated drain pan provides easy ground level
installation with mounting pad. A nesting feature ensures a positive
basepan to roof curb seal when the unit is roof mounted. A
convenient 3/4--in. (19.05 mm) wide perimeter flange makes frame
mounting on a rooftop easy.
Standard horizontal metal duct covers with insulation come
with the unit and cover the horizontal duct openings. These can be
left in place if the units are converted to downflow.
Integrated Gas Control (IGC) board provides safe and efficient
control of heating and simplifies trouble--shooting through its
built--in diagnostic function.
Cabinets are constructed of heavyduty, phosphated, zinc--coated
prepainted steel capable of withstanding 500 hours in salt spray.
Interior surfaces of the evaporator/heat exchanger compartment are
insulated with foil--faced insulation, which keeps the conditioned
air from being affected by the outdoor ambient temperature and
provides improved indoor air quality. (Conforms to American
Society of Heating, Refrigeration and Air Conditioning Engineers
62.2.) The sloped drain pan minimizes standing water in the drain.
An external drain is provided.
Louvered grille provides hail and vandalism protection for the
coil.
TABLE OF CONTENTS
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . 3
AHRI Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5---6
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . 8---9
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12---24
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Typical Wiring Schematics . . . . . . . . . . . . . . . . . . . . . 52---61
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 63---64
2
MODEL NUMBER NOMENCLATURE
---
48VG
A
24
040
3
0
--- --Options
GP --- Base unit with tin plated indoor coil hairpins and
Stainless Steel HX (Single Phase Only)
GS --- Stainless Steel HX
TF --- Filter Rack
TP --- Base unit with tin plated indoor coil hairpins (Single
Phase Only)
Type of Unit
48VG --- Two Stage Packaged
Air Conditioner and
Gas Furnace System
See Price Page for full list of factory options.
Only used if ordering an option
Low NOx Indicator
--Standard
N --- Low NOx
Minor Series
Nominal Cooling Capacity
24 --- 2.0 Tons
30 --- 2.5 Tons
36 --- 3.0 Tons
42 --- 3.5 Tons
48 --- 4.0 Tons
60 --- 5.0 Tons
Electrical Supply
3 --- 208/230--- 1--- 60
5 --- 208/230--- 3--- 60
6 --- 460--- 3--- 60
48VG -- A
Major Series
Heat Input Size (Btuh)
040 --- 40,000
060 --- 60,000
090 --- 90,000
115 --- 115,000
130 --- 130,000
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
3
AHRI* CAPACITIES
48VG -- A
Cooling Capacities and Efficiencies
Unit Model
48VG-A
Nominal
Tons
Standard CFM
(High / Low Stage)
24
30
36
42
48
60
2
2-1/2
3
3-1/2
4
5
800 / 600
1000 / 750
1200 / 900
1400 / 1050
1600 / 1200
1750 / 1200
Net Cooling
Capacities - Btuh
(High Stage)
23000
29000
35400
42000
47500
57000
LEGEND
dB--- Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP---Coefficient of Performance
* Air Conditioning, Heating & Refrigeration Institute.
**At “A” conditions---80_F (26.7_C) indoor db/67_F (19.4_C) indoor wb &
95_F (35_C) outdoor db.
{ Rated in accordance with U.S. Government DOE Department of Energy)
test procedures and/or AHRI Standards 210/240.
EER @A**
SEER†
12.0
12.0
12.5
12.5
12.3
12.3
15.0
15.0
16.0
16.0
16.0
16.0
Notes:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80F (26.7_C) db, 67F wb (19.4_C) indoor entering---air
temperature and 95F db (35_C) outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from AHRIdirectory.org.
Heating Capacities and Efficiencies
208/230 VAC Models
UNIT 48VG-- A
HEATING INPUT
(BTUH)
HIGH/LOW
OUTPUT CAPACITY
(BTUH)
HIGH / LOW
TEMPERATURE
RISE
RANGE
HIGH F (C)
TEMPERATURE
RISE
RANGE
LOW F (C)
AFUE (%)
24040
30040
40,000 / 26,000
32,000 / 21,000
20--50 (11--28)
15--45 (8--25)
78
24060
30060
36060
42060
60,000 / 39,000
49,000 / 31,000
25--55 (14--31)
25--55 (14--31)
78.6
36090
42090
48090
60090
90,000 / 58,500
74,000 / 47,000
35--65 (19--36)
35--65 (19--36)
79.2
48115
60115
115,000 / 75,000
93,000 / 61,000
30--60 (17--33)
30--60 (17--33)
80.1
48130
60130
130,000 / 84,500
103,000 / 68,000
35--65 (19--36)
35--65 (19--36)
80.0
LEGEND
AFUE --- Annual Fuel Utilization Efficiency
NOTE: Before purchasing this appliance, read important energy cost and efficiency information available from AHRIdirectory.org.
Heating Capacities and Efficiencies
460V Models
UNIT 48VG-- A
36060
42060
36090
42090
48090
60090
48115
60115
48130
60130
HEATING INPUT
(Btuh)
OUTPUT CAPACITY
(Btuh)
TEMPERATURE RISE
RANGE F (C)
AFUE (%)
60,000
47,000
47,000
25--55
(13.9--30.6)
78.5
78.5
90,000
73,000
35--65
(19.4--36.1)
80.4
115,000
93,000
30--60
(16.7--33.3)
80.3
130,000
103,000
35--65
(19.4--36.1)
78.9
LEGEND
AFUE—Annual Fuel Utilization Efficiency
NOTE: Before purchasing this appliance, read important energy cost and efficiency information available from AHRIdirectory.org.
4
A--Weighted Sound Power Level (dBA)
Model 48VG-A
Sound Ratings
(dBA)
24
30
36
42
48
60
73
77
73
73
72
75
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
125
250
500
1000
2000
4000
8000
60.0
57.5
62.5
60.5
60.0
69.0
62.5
67.0
65.5
63.5
63.5
67.0
68.5
73.5
67.5
68.0
66.0
69.0
68.5
72.0
68.0
68.0
67.0
68.0
64.0
67.0
65.5
66.0
63.5
65.0
60.0
61.0
60.0
60.5
58.5
61.5
53.0
52.5
52.5
53.0
49.5
54.0
NOTE: Tested in accordance with AHRI Standard 270 (not listed in AHRI).
UNIT SIZE
NOMINAL CAPACITY (ton)
SHIPPING WEIGHT** lb.
SHIPPING WEIGHT** (kg)
COMPRESSORS
Quantity
REFRIGERANT (R --- 410A)
Quantity lb.
Quantity (kg)
REFRIGERANT METERING DEVICE
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
OUTDOOR FAN
Nominal CFM
Diameter in.
Diameter (mm)
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
INDOOR BLOWER
Nominal Low Stage Cooling Airflow (Cfm)
Nominal High Stage Cooling Airflow (Cfm)
Size in.
Size (mm.)
Motor HP (RPM)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas (Factory Installed)
Propane Gas
HIGH--PRESSURE SWITCH
(psig) Cut--out Reset (Auto)
LOSS--OF--CHARGE / LOW--PRESSURE
SWITCH (psig) cut--out Reset (auto)
DUCT RETURN--- AIR FILTERS†}
Throwaway Size in.
(mm)
24040
2
352
160
24060
2
352
160
30040
2 ---1/2
359
163
6.4
2.9
6.4
2.9
8.3
3.8
30060
36060
2 ---1/2
3
359
455
163
206
2 ---Stage Scroll
1
8.3
3.8
36090
3
455
206
42060
3 ---1/2
455
206
42090
3 ---1/2
455
206
8.1
3.7
8.1
3.7
8.7
3.9
8.7
3.9
TXV
1..21
13.6
1...21
13.6
2...21
13.6
2...21
13.6
2...21
13.6
2...21
13.6
2...21
13.6
2...21
13.6
2500
24
609.6
1/10 (810)
2500
24
609.6
1/10 (810)
2700
24
609.6
1/5 (810)
2700
24
609.6
1/5 (810)
3000
26
600.4
1/5 (810)
3000
26
600.4
1/5 (810)
3000
26
660.4
1/5 (810
3000
26
660.4
1/5 (810)
3...17
3.7
3...17
3.7
3...17
3.7
3...17
3.7
3...17
4.7
3...17
4.7
3...17
4.7
3...17
4.7
600
800
10x10
254x254
1/2 (1050)
600
800
10x10
254x254
1/2 (1050)
750
1000
10x10
254x254
1/2 (1050)
750
1000
10x10
254x254
1/2 (1050)
900
1200
11x10
279.4x254
3/4 (1000)
900
1200
11x10
279.4x254
3/4 (1000)
1050
1400
11x10
279.4x254
3/4 (1075)
1050
1400
11x10
279.4x254
3/4 (1075)
2...44
2...55
20x20x1
508x508x25
3...44
3...55
2...44
2...55
20x24x1
508x610x25
208/230
VAC Models
3...44
3...44
3...55
3...55
460 VAC
Models
2…38
2…53
650 +/-- 15
420 +/-- 25
50 +/-- 7
95 +/-- 7
3…38
3…53
208/230
VAC Models
3...44
3...55
460 VAC
Models
2…38
2…53
3...38
3...53
24x30x1
610x762x25
*Based on altitude of 0 to 2000 ft (0 ---610 m).
{ Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.
} If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
5
48VG -- A
PHYSICAL DATA
PHYSICAL DATA (CONT)
48VG -- A
UNIT SIZE
NOMINAL CAPACITY (ton)
SHIPPING WEIGHT lb
SHIPPING WEIGHT kg
COMPRESSORS
Quantity
REFRIGERANT (R --- 410A)
Quantity lb
Quantity (kg.)
REFRIGERANT METERING DEVICE
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
OUTDOOR FAN
Nominal Cfm
Diameter in.
Diameter (mm)
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
INDOOR BLOWER
Nominal Low Stage Cooling Airflow (Cfm)
Nominal High Stage Cooling Airflow (Cfm)
Size in.
Size (mm)
Motor HP (RPM)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas (Factory Installed)
Propane Gas
48090
4
500
227
48115
4
500
227
10.8
4.9
10.8
4.9
48130
60090
4
5
500
520
227
236
2 ---Stage Scroll
1
10.8
4.9
60115
5
520
236
60130
5
520
236
12.1
5.5
12.1
5.5
12.1
5.5
TXV
2...21
19.4
2...21
19.4
2...21
19.4
2...21
21.4
2...21
21.4
2...21
21.4
3300
26
660.4
1/5 (810)
3300
26
660.4
1/5 (810)
3300
26
660.4
1/5 (810)
3600
26
660.4
1/5 (810)
3600
26
660.4
1/5 (810)
3600
26
660.4
1/5 (810)
3...17
5.7
3...17
5.7
3...17
5.7
3...17
5.7
3...17
5.7
3...17
5.7
1200
1600
11x10
279.4x254
1.0 (1075)
1200
1600
11x10
279.4x254
1.0 (1075)
1200
1600
11x10
279.4x254
1.0 (1075)
1200
1750
11x10
279.4x254
1.0 (1075)
1200
1750
11x10
279.4x254
1.0 (1075)
1200
1750
11x10
279.4x254
1.0 (1075)
3...38
3...53
3...33
3...51
3...31
3...49
3...38
3...53
3...33
3...51
3...31
3...49
HIGH--PRESSURE SWITCH
650 +/-- 15
(psig) Cut--out Reset (Auto)
420 +/-- 25
LOSS--OF--CHARGE / LOW--PRESSURE
50 +/--7
SWITCH (psig) cut--out Reset (auto)
95 +/-- 7
DUCT RETURN--AIR FILTERS Throwaway†} in.
24x36x1
(mm)
610x914x25
*Based on altitude of 0 to 2000 ft (0 ---610 m).
{ Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.
} If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
6
OPTIONS AND ACCESSORIES
DESCRIPTION
FACTORY
INSTALLED
OPTION
FIELD
INSTALLED
ACCESSORY
Coil Options
Base unit with tin plated indoor coil hairpins
Compressor Start Kit
Compressor Start Kit assists compressor start--- up by
providing additional starting torque on sing phase units
only.
X
Corporate Thermostats
Thermostats provide control for the system heating and
cooling functions.
X
Crankcase Heater
Crankcase Heater provides anti--- floodback protection for
low--- load cooling applications.
X*
Vertical Economizer with Jade Honeywell W7220 Controller, Honeywell communicating actuator, and dry bulb
sensor. (Contact MicroMetl Customer Service at
1--- 800--- 662--- 4822 to order.)
X
Horizontal Economizer with Jade Honeywell W7220 Controller, Honeywell communicating actuator, and dry bulb
sensor. (Contact MicroMetl Customer Service at
1--- 800--- 662--- 4822 to order.)
X
Economizer
X
Filter Rack
Filter Rack features easy installation, serviceability, and
high--- filtering performance for vertical applications.
Includes 1--- in. filter.
Flat Roof Curbs
Flat Roof Curbs in both 11--- in (279 mm) and 14--- in. (356
mm) sizes are available for roof mounted applications.
X
Flue Discharge Deflector
Directs flue gas exhaust 90 degrees upward from current
discharge.
X
Heat Exchanger
Stainless Steel Heat Exchanger
High Altitude Propane Conversion Kit
High Altitude Propane Conversion Kit is for use at 2001 to
6000 ft. (611--- 1829 m) above sea level. Kit consists of
propane gas orifices that compensate for gas heat operation at high altitude.
X
Low Ambient Kit
Low Ambient Kit (Motormaster II Control) allows the use of
mechanical cooling down to outdoor temperatures as low
as 0°F (--- 18° C) when properly installed.
X
Manual Outside Air Damper
Manual Outside Air Damper includes hood and filter rack
with adjustable damper blade for up to 25% outdoor air.
X
Natural to Propane Gas Conversion Kit
Natural to Propane Gas Conversion Kit allows for conversion from natural gas to propane gas (0--- 2000 ft) (0--- 610
m)
X
Propane to Natural Gas Conversion Kit
Propane to Natural Gas Conversion Kit allows for conversion from propane to natural gas for altitudes of 0--- 2000 ft
(0--- 610 m)
X
Square--- to--- Round Duct Transition Kit
Square--- to--- Round Duct Transition Kit enable 24--- 48 size
units to be fitted to 14 in. (356 mm) round ductwork.
X
Time Guard II
Automatically prevents the compressor from restarting for
at least 4 minutes and 45 seconds after shutdown of the
compressor. Not required when a corporate programmable thermostat is applied or with a RTU--- MP control.
X
*Refer to Price Page for application detail.
7
X
X
X
48VG -- A
ITEM
87.9 39.9 77.6 35.2 84.1 38.2 94.4 42.8
89.7 40.7 79.0 35.8 85.8 38.9 96.5 43.8
48VG -- A
UNIT DIMENSIONS - 48VG--A24--30
A13012
8
97.5
97.5
107.0
110.9
44. 3
44.2
48.5
50.3
86.4
86.5
95.3
98.6
140.2
139.8
153.6
160.2
48VG -- A
56.2
56.3
61.8
64.5
202.8
202.8
223.2
232.3
39.2 123.9
39.2 124.2
43.2 136.1
44.7 142.2
447
447
492
512
63.6
63.4
69.7
72.7
UNIT DIMENSIONS - 48VG--A36--60
A13013
9
ACCESSORY DIMENSIONS
Dashed lines show cross support
location for large basepan units.
B
G
HVAC unit
basepan
HVAC unit
base rails
C
Sealing
Gasket
Roofcurb
A
Anchor screw
H
F
Wood nailer*
Flashing field
supplied
Roofcurb*
Insulation
(field supplied)
Roofing material
field supplied
48VG -- A
E
D
Cant strip
field supplied
SMALL/COMMON CURB
A09413
*Provided with roofcurb
A09090
ROOF CURB DETAIL
B
C
G
SUPPLY
AIR
SMALL
BASE
UNIT
RETURN
AIR
LARGE
BASE
UNIT
H
F A
E
D
UNIT PLACEMENT ON
COMMON CURB
SMALL OR LARGE BASE UNIT
A09415
LARGE CURB
A09094
A09414
UNIT
SIZE
CATALOG
NUMBER
Small
or
Large
CPRFCURB010A00
Large
CPRFCURB011A00
CPRFCURB012A00
CPRFCURB013A00
A
IN.
(mm)
11
(279)
14
(356)
11
(279)
14
(356)
B (small / common
base)
IN. (mm)*
B (large
base)
IN. (mm)*
C
IN.
(mm)
D
IN.
(mm)
E
IN.
(mm)
F
IN.
(mm)
32.4
(822)
10 (254)
14 (356)
16
(406)
47.8
(1214)
H
IN. (mm)
30.6 (778)
2.7 (69)
43.9
(1116)
14 (356)
G
IN. (mm)
46.1 (1170)
42.2 (1072)
* Part Numbers CPRCURB010A00 and CPRCURB011A00 can be used on both small and large basepan units. The cross supports must be located based on
whether the unit is a small basepan or a large basepan.
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.
10
1. Determine cooling and heating requirements at
design conditions:
4. Determine fan speed and power requirements at
design conditions.
Given:
Required Cooling Capacity (TC) . . . . . . . . . . 34,000 Btuh
Sensible Heat Capacity (SHC) . . . . . . . . . . . . 25,000 Btuh
Required Heating Capacity . . . . . . . . . . . . . . . 60,000 Btuh
Condenser Entering Air Temperature . . . . . . . 95F (35C)
Indoor--Air Temperature . 80F (26C)edb 67F (19C)ewb
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . 1200 CFM
External Static Pressure . . . . . . . . . . . . . . . . 0.100 IN. W.C.
Electrical Characteristics . . . . . . . . . . . . . . . . . . . 208--1--60
Before entering the air delivery tables, calculate the total static
pressure required. From the given example, the Wet Coil Pressure
Drop Table, and the Filter Pressure Drop Table:
External Static Pressure
0.100 IN. W.C
Filter
0.07 IN. W.C
Wet Coil Pressure Drop
0.180 IN. W.C
Total Static Pressure
0.287 IN. W.C
Enter the table for Dry Coil Air Delivery—Horizontal and
Downflow Discharge. At .287 IN. W.C. ESP, the closest speed to
1200 CFM is Med--Low (pink wire), which delivers 1262 CFM at
.3 in ESP.
2. Select unit based on required cooling capacity.
Enter Net Cooling Capacities table at condenser entering
temperature of 95F (35C). Unit 036 at 1200 cfm and 67F
(19C) ewb (entering wet bulb) will provide a total capacity of
34,200 Btuh and a SHC of 27,400 Btuh. Calculate SHC correction,
if required, using Note 4 under Cooling Capacities tables.
5. Select unit that corresponds to power source
available.
The Electrical Data Table shows that the unit is designed to operate
at 208--1--60.
3. Select heating capacity of unit to provide design
condition requirement.
In the Heating Capacities and Efficiencies table, note that the unit
036090 (208/230 VAC) will provide 74,000 Btuh with an input of
90,000 Btuh in high stage and will provide 47,000 Btuh of heating
in low stage.
11
48VG -- A
SELECTION PROCEDURE (WITH EXAMPLE)
12
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
19.29
15.50
16.16
12.71
19.25
20.64
22.59
14.57
18.96
19.29
18.61
18.65
19.26
18.60
18.60
19.26
11.42
21.87
12.08
14.13
19.95
22.29
13.61
18.58
15.15
16.78
18.21
20.34
17.82
17.82
1.03
1.06
1.09
1.09
1.09
1.02
1.05
1.08
1.08
1.08
1.01
1.04
1.07
1.07
1.08
75 (23.9)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
See Legend and Notes on Page 24.
675
600
525
CFM
EVAPORATOR
AIR
024 Low Cool
PERFORMANCE DATA
20.61
18.83
17.56
17.75
17.73
20.35
18.58
17.31
17.17
17.14
20.00
18.24
16.98
16.66
16.44
11.39
14.58
13.97
17.75
17.73
10.81
13.66
13.11
17.17
17.14
10.22
12.71
12.24
15.16
16.44
1.20
1.23
1.25
1.25
1.25
1.19
1.22
1.24
1.24
1.24
1.18
1.21
1.23
1.24
1.24
85 (29.4)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
18.64
17.03
15.88
16.22
16.20
18.43
16.82
15.67
15.71
15.68
18.14
16.54
15.39
15.11
15.06
10.12
13.03
12.47
16.22
16.20
9.59
12.20
11.69
15.71
15.68
9.05
11.34
10.90
15.05
15.06
1.39
1.41
1.43
1.42
1.42
1.37
1.40
1.42
1.42
1.42
1.36
1.39
1.41
1.41
1.41
16.69
15.24
14.21
14.68
14.66
16.52
15.06
14.03
14.23
14.21
16.28
14.83
13.80
13.69
13.67
8.88
11.53
11.01
14.68
14.66
8.40
10.77
10.31
14.23
14.21
7.92
10.00
9.59
13.69
13.67
1.58
1.61
1.63
1.62
1.62
1.57
1.60
1.61
1.61
1.61
1.56
1.58
1.60
1.60
1.60
14.74
13.45
12.53
13.13
13.11
14.61
13.31
12.39
12.75
12.73
14.42
13.13
12.20
12.28
12.27
7.68
10.06
9.59
13.13
13.11
7.26
9.39
8.97
12.75
12.73
6.82
8.69
8.32
12.28
12.27
1.80
1.82
1.84
1.83
1.83
1.79
1.81
1.83
1.82
1.82
1.78
1.80
1.82
1.81
1.81
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Total
Total
Total
MBtuh
MBtuh
MBtuh
Syst
Syst
Syst
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
48VG -- A
12.83
11.70
10.89
11.59
11.57
12.73
11.59
10.77
11.27
11.25
12.59
11.44
10.62
10.88
10.86
6.55
8.65
8.21
11.59
11.57
6.17
8.05
7.67
11.27
11.25
5.78
7.44
7.10
10.88
10.86
2.03
2.05
2.07
2.06
2.06
2.02
2.04
2.06
2.05
2.05
2.01
2.03
2.05
2.04
2.04
125 (51.7)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
13
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
25.86
19.95
20.76
16.37
25.97
27.81
30.37
18.77
25.56
25.86
23.30
25.14
25.82
24.94
24.94
25.82
14.76
29.38
15.58
18.20
26.85
29.94
17.56
25.02
19.50
21.58
24.55
27.40
23.89
23.89
1.64
1.62
1.60
1.60
1.60
1.62
1.60
1.58
1.58
1.57
1.60
1.57
1.56
1.55
1.55
75 (23.9)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
See Legend and Notes on Page 24.
900
800
700
CFM
EVAPORATOR
AIR
024 High Cool
PERFORMANCE DATA (CONT)
27.89
25.54
23.86
23.98
23.95
27.52
25.19
23.51
23.20
23.16
27.04
24.72
23.05
22.62
22.22
15.53
19.83
19.03
23.98
23.95
14.76
18.60
17.89
23.20
23.16
13.97
17.34
16.72
20.64
22.22
1.80
1.77
1.75
1.76
1.76
1.78
1.75
1.73
1.73
1.73
1.75
1.73
1.71
1.71
1.70
85 (29.4)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
25.42
23.30
21.77
22.11
22.08
25.12
23.00
21.48
21.41
21.38
24.71
22.61
21.08
20.72
20.54
14.69
18.89
18.11
22.11
22.08
13.94
17.70
17.00
21.41
21.38
13.17
16.48
15.86
19.69
20.54
1.97
1.94
1.92
1.92
1.92
1.95
1.92
1.90
1.90
1.90
1.92
1.89
1.87
1.87
1.87
22.99
21.07
19.70
20.23
20.20
22.74
20.83
19.46
19.62
19.59
22.42
20.50
19.13
18.89
18.86
13.85
17.95
17.18
20.23
20.20
13.12
16.80
16.11
19.62
19.59
12.38
15.61
15.01
18.89
18.86
20.59
18.88
17.66
18.35
18.33
20.40
18.68
17.46
17.83
17.81
20.14
18.42
17.19
17.20
17.17
48VG -- A
2.15
2.12
2.10
2.11
2.11
2.13
2.10
2.08
2.08
2.08
2.10
2.07
2.06
2.05
2.05
13.01
17.01
16.25
18.35
18.33
12.31
15.89
15.22
17.83
17.81
11.59
14.75
14.15
17.20
17.17
2.35
2.32
2.30
2.31
2.31
2.33
2.30
2.28
2.28
2.28
2.30
2.27
2.26
2.26
2.26
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Total
Total
Total
MBtuh
MBtuh
MBtuh
Sys
Sys
Sys
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
18.26
16.76
15.68
16.50
16.48
18.12
16.60
15.51
16.06
16.04
17.91
16.39
15.30
15.52
15.50
12.18
16.07
15.32
16.50
16.48
11.50
15.00
14.34
16.06
16.04
10.81
13.89
13.30
15.52
15.50
2.56
2.54
2.52
2.53
2.53
2.54
2.52
2.50
2.51
2.51
2.52
2.49
2.48
2.48
2.48
125 (51.7)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
14
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
1.42
17.36
14.14
23.33
22.18
17.87
18.62
14.94
24.14
24.18
18.95
19.78
15.67
25.19
27.74
23.33
23.49
23.87
25.72
28.29
24.14
24.18
24.24
26.09
28.69
1.45
16.69
23.36
1.47
1.46
1.47
1.40
1.43
1.45
1.45
1.45
1.38
1.41
1.43
1.43
20.51
22.91
1.43
22.30
Sens
Total
Syst
KW
22.30
Total
75 (23.9)
Capacity
MBtuh
See Legend and Notes on Page 24.
840
750
655
CFM
EVAPORATOR
AIR
030 Low Cool
PERFORMANCE DATA (CONT)
25.62
23.31
21.66
21.82
21.79
25.30
23.00
21.36
21.12
21.08
24.84
22.57
20.94
20.54
20.19
Total
13.42
17.06
16.32
21.82
21.79
12.78
16.04
15.38
21.12
21.08
12.08
14.93
14.35
17.72
20.19
Sens
85 (29.4)
Capacity
MBtuh
1.48
1.50
1.52
1.52
1.52
1.46
1.48
1.50
1.50
1.50
1.44
1.46
1.48
1.48
1.49
22.63
20.60
19.15
19.50
19.48
22.37
20.35
18.90
18.90
18.87
22.00
19.99
18.55
18.23
18.10
11.27
14.43
13.79
19.50
19.48
10.72
13.55
12.98
18.90
18.87
10.11
12.60
12.09
15.01
18.10
1.53
1.55
1.56
1.56
1.56
1.51
1.53
1.55
1.54
1.54
1.49
1.51
1.53
1.53
1.53
19.71
17.95
16.68
17.21
17.18
19.51
17.75
16.48
16.70
16.68
19.22
17.47
16.21
16.05
16.02
9.21
11.90
11.35
17.21
17.18
8.75
11.16
10.67
16.70
16.68
8.24
10.36
9.92
16.05
16.02
1.57
1.59
1.60
1.59
1.59
1.55
1.57
1.58
1.58
1.58
1.54
1.55
1.56
1.57
1.57
16.86
15.36
14.28
14.94
14.92
16.72
15.21
14.12
14.53
14.51
16.51
15.00
13.91
13.99
13.97
7.26
9.47
9.02
14.94
14.92
6.88
8.87
8.46
14.53
14.51
6.47
8.21
7.86
13.99
13.97
1.60
1.61
1.62
1.61
1.61
1.58
1.59
1.61
1.60
1.60
1.57
1.58
1.59
1.59
1.59
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Total
Capacity
Capacity
Capacity
Total
Total
Total
MBtuh
MBtuh
MBtuh
Syst
Syst
Syst
Syst
KW
KW
KW
Total
Sens
Total
Sens
Total
Sens
KW
48VG -- A
14.12
12.87
11.96
12.72
12.71
14.03
12.76
11.84
12.39
12.38
13.88
12.60
11.68
11.97
11.95
5.44
7.16
6.80
12.72
12.71
5.14
6.70
6.38
12.39
12.38
4.82
6.19
5.91
11.97
11.95
1.61
1.62
1.63
1.62
1.62
1.59
1.60
1.61
1.61
1.61
1.58
1.59
1.60
1.60
1.60
125 (51.7)
Capacity
Total
MBtuh
Syst
KW
Total
Sens
15
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
33.13
24.42
25.44
20.21
33.47
35.96
39.41
23.02
32.92
33.13
28.44
32.39
33.07
31.92
31.92
33.07
18.28
38.04
19.27
22.38
34.66
38.82
21.56
32.20
23.93
26.39
31.60
35.39
30.54
30.54
2.12
2.08
2.05
2.05
2.05
2.08
2.04
2.02
2.01
2.01
2.05
2.01
1.98
1.98
1.97
75 (23.9)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
See Legend and Notes on Page 24.
1125
1000
875
CFM
EVAPORATOR
AIR
030 High Cool
PERFORMANCE DATA (CONT)
35.75
32.64
30.41
30.38
30.34
35.26
32.18
29.95
29.52
29.32
34.61
31.55
29.34
28.82
28.11
18.94
24.00
23.02
30.38
30.34
18.03
22.57
21.68
26.89
29.32
17.09
21.07
20.29
24.96
28.11
2.29
2.25
2.23
2.23
2.23
2.26
2.22
2.19
2.19
2.19
2.22
2.19
2.16
2.15
2.15
85 (29.4)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
32.16
29.39
27.40
27.67
27.63
31.76
29.00
27.01
26.78
26.74
31.23
28.49
26.51
26.06
25.68
17.68
22.58
21.64
27.67
27.63
16.81
21.20
20.35
26.78
26.74
15.91
19.77
19.02
23.52
25.68
2.49
2.45
2.42
2.43
2.43
2.46
2.42
2.39
2.39
2.39
2.42
2.38
2.36
2.35
2.35
28.60
26.17
24.41
24.94
24.91
28.30
25.86
24.10
24.19
24.16
27.87
25.45
23.69
23.34
23.24
16.42
21.16
20.24
24.94
24.91
15.59
19.84
19.02
24.19
24.16
14.73
18.47
17.75
23.16
23.24
25.11
22.98
21.46
22.21
22.18
24.87
22.74
21.21
21.58
21.55
24.55
22.42
20.88
20.81
20.78
48VG -- A
2.71
2.67
2.64
2.65
2.65
2.67
2.64
2.61
2.61
2.61
2.64
2.60
2.58
2.57
2.57
15.17
19.72
18.84
22.21
22.18
14.37
18.46
17.67
21.58
21.55
13.55
17.16
16.46
20.81
20.78
2.95
2.91
2.89
2.90
2.90
2.92
2.88
2.86
2.87
2.87
2.89
2.85
2.83
2.83
2.83
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Total
Total
Total
MBtuh
MBtuh
MBtuh
Sys
Sys
Sys
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
21.72
19.90
18.57
19.51
19.49
21.55
19.70
18.37
18.99
18.97
21.31
19.45
18.12
18.36
18.33
13.93
18.28
17.42
19.51
19.49
13.17
17.10
16.33
18.99
18.97
12.39
15.86
15.18
18.36
18.33
3.22
3.19
3.17
3.19
3.19
3.19
3.16
3.14
3.15
3.15
3.16
3.13
3.11
3.12
3.12
125 (51.7)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
16
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
28.02
22.71
23.73
18.66
27.84
29.94
32.87
21.37
27.41
28.02
27.07
27.07
27.98
27.03
27.03
27.98
16.77
31.81
17.75
20.73
28.92
32.43
19.92
26.84
22.28
24.60
26.33
29.51
25.86
25.86
1.51
1.54
1.56
1.56
1.56
1.50
1.53
1.55
1.55
1.55
1.48
1.51
1.53
1.54
1.54
75 (23.9)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
See Legend and Notes on Page 24.
1010
900
785
CFM
EVAPORATOR
AIR
036 Low Cool
PERFORMANCE DATA (CONT)
29.50
26.88
24.99
25.41
25.37
29.14
26.52
24.64
24.59
24.55
28.62
26.02
24.16
23.73
23.52
16.57
21.21
20.28
25.41
25.37
15.74
19.89
19.06
24.59
24.55
14.85
18.48
17.75
22.02
23.52
1.62
1.65
1.67
1.66
1.66
1.61
1.63
1.65
1.65
1.65
1.59
1.62
1.64
1.64
1.64
85 (29.4)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
26.21
23.89
22.22
22.83
22.80
25.92
23.59
21.93
22.12
22.09
25.50
23.18
21.53
21.23
21.19
14.55
18.76
17.92
22.83
22.80
13.80
17.58
16.82
22.12
22.09
13.00
16.30
15.63
21.23
21.19
1.73
1.75
1.77
1.76
1.76
1.71
1.74
1.75
1.75
1.75
1.70
1.72
1.74
1.74
1.74
22.99
20.96
19.49
20.28
20.25
22.76
20.72
19.25
19.68
19.65
22.43
20.39
18.93
18.92
18.89
12.60
16.38
15.62
20.28
20.25
11.93
15.32
14.64
19.68
19.65
11.22
14.19
13.59
18.92
18.89
1.83
1.85
1.87
1.86
1.86
1.82
1.84
1.85
1.85
1.85
1.80
1.82
1.84
1.84
1.84
19.84
18.09
16.82
17.75
17.72
19.67
17.90
16.63
17.25
17.23
19.42
17.65
16.37
16.62
16.59
10.73
14.07
13.38
17.75
17.72
10.14
13.15
12.53
17.25
17.23
9.51
12.15
11.61
16.62
16.59
1.93
1.95
1.96
1.95
1.95
1.92
1.94
1.95
1.94
1.94
1.90
1.92
1.94
1.93
1.93
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Total
Total
Total
MBtuh
MBtuh
MBtuh
Syst
Syst
Syst
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
48VG -- A
16.79
15.32
14.28
15.25
15.24
16.67
15.16
14.08
14.86
14.84
16.49
14.97
13.88
14.35
14.33
8.94
11.82
14.28
15.25
15.24
8.43
11.05
10.51
14.86
14.84
7.89
10.19
9.71
14.35
14.33
2.02
2.04
2.05
2.04
2.04
2.01
2.03
2.04
2.03
2.03
2.00
2.02
2.03
2.02
2.02
125 (51.7)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
17
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
38.82
30.63
31.90
25.24
39.08
41.92
45.86
28.86
38.44
38.82
35.72
37.84
38.77
37.44
37.44
38.77
22.80
44.31
24.05
28.03
40.43
45.20
27.02
37.62
30.00
33.14
36.94
41.27
35.86
35.86
2.46
2.41
2.38
2.37
2.37
2.43
2.38
2.34
2.34
2.33
2.39
2.34
2.31
2.30
2.29
75 (23.9)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
See Legend and Notes on Page 24.
1350
1200
1050
CFM
EVAPORATOR
AIR
036 High Cool
PERFORMANCE DATA (CONT)
42.55
38.92
36.30
36.40
36.36
41.98
38.37
35.75
35.28
35.15
41.22
37.63
35.04
34.42
33.72
23.81
30.29
29.05
36.40
36.36
22.65
28.45
27.35
35.09
35.15
21.45
26.55
25.57
31.53
33.72
2.68
2.63
2.59
2.59
2.59
2.64
2.59
2.56
2.56
2.55
2.61
2.56
2.53
2.52
2.51
85 (29.4)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
39.20
35.87
33.49
33.92
33.88
38.71
35.40
33.01
32.85
32.81
38.07
34.79
32.41
31.86
31.52
22.37
28.67
27.48
33.92
33.88
21.25
26.90
25.83
32.85
32.81
20.10
25.07
24.12
29.88
31.52
2.92
2.86
2.83
2.84
2.84
2.88
2.83
2.80
2.80
2.80
2.85
2.80
2.77
2.76
2.76
35.78
32.77
30.61
31.37
31.33
35.39
32.38
30.22
30.43
30.39
34.86
31.86
29.71
29.31
29.26
20.92
27.04
25.88
31.37
31.33
19.85
25.34
24.30
30.43
30.39
18.73
23.58
22.66
29.31
29.26
32.32
29.62
27.68
28.72
28.69
32.00
29.29
27.35
27.92
27.88
31.58
28.87
26.94
26.93
26.89
48VG -- A
3.18
3.13
3.10
3.11
3.11
3.15
3.10
3.07
3.07
3.07
3.11
3.07
3.03
3.03
3.03
19.48
25.40
24.26
28.72
28.69
18.44
23.77
22.75
27.92
27.88
17.37
22.07
21.18
26.93
26.89
3.48
3.43
3.40
3.42
3.42
3.45
3.40
3.37
3.38
3.38
3.41
3.37
3.34
3.34
3.34
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Total
Total
Total
MBtuh
MBtuh
MBtuh
Sys
Sys
Sys
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
28.86
26.47
24.75
26.03
26.00
28.62
26.20
24.48
25.34
25.31
28.28
25.86
24.13
24.51
24.47
18.05
23.74
22.63
26.03
26.00
17.05
22.20
21.21
25.34
25.31
16.02
20.58
19.71
24.51
24.47
3.81
3.77
3.74
3.76
3.76
3.79
3.74
3.71
3.73
3.73
3.75
3.71
3.69
3.69
3.69
125 (51.7)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
18
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
33.62
26.93
28.15
22.25
33.55
36.17
39.84
25.34
33.02
33.62
32.36
32.52
33.57
32.40
32.40
33.57
20.01
38.48
21.17
24.60
34.88
39.26
23.63
32.30
26.44
29.10
31.67
35.63
30.96
30.96
1.92
1.95
1.98
1.98
1.98
1.89
1.93
1.95
1.95
1.95
1.87
1.90
1.92
1.93
1.93
75 (23.9)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
See Legend and Notes on Page 24.
1180
1050
915
CFM
EVAPORATOR
AIR
042 Low Cool
PERFORMANCE DATA (CONT)
36.39
33.07
30.68
31.04
31.00
35.92
32.61
30.24
30.01
29.96
35.25
31.98
29.63
29.07
28.67
19.94
25.40
24.28
31.04
31.00
18.95
23.83
22.82
30.01
29.96
17.89
22.15
21.25
26.30
28.67
1.96
1.99
2.02
2.01
2.01
1.93
1.97
1.99
1.99
2.00
1.91
1.94
1.97
1.97
1.98
85 (29.4)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
32.92
29.92
27.77
28.42
28.38
32.54
29.55
27.41
27.51
27.47
31.99
29.02
26.89
26.44
26.33
17.68
22.69
21.66
28.42
28.38
16.78
21.26
20.34
27.51
27.47
15.82
19.73
18.92
26.27
26.33
1.99
2.03
2.05
2.05
2.05
1.97
2.01
2.03
2.03
2.03
1.95
1.98
2.01
2.01
2.01
29.44
26.76
24.85
25.74
25.70
29.14
26.46
24.54
24.96
24.92
28.70
26.03
24.12
23.97
23.93
15.49
20.04
19.10
25.74
25.70
14.67
18.75
17.91
24.96
24.92
13.81
17.38
16.63
23.97
23.93
2.02
2.05
2.08
2.07
2.07
2.00
2.03
2.06
2.05
2.05
1.98
2.01
2.04
2.04
2.04
25.95
23.60
21.90
23.02
22.99
25.72
23.35
21.65
22.35
22.32
25.38
23.01
21.31
21.51
21.48
13.37
17.46
16.60
23.02
22.99
12.64
16.31
15.55
22.35
22.32
11.87
15.09
14.41
21.51
21.48
2.02
2.06
2.09
2.07
2.07
2.01
2.04
2.07
2.06
2.06
1.99
2.03
2.05
2.05
2.05
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Total
Total
Total
MBtuh
MBtuh
MBtuh
Syst
Syst
Syst
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
48VG -- A
22.49
20.46
18.99
20.27
20.25
22.33
20.26
18.77
19.73
19.70
22.08
20.00
18.51
19.03
19.01
11.34
14.94
18.84
20.27
20.25
10.70
13.96
13.28
19.73
19.70
10.03
12.89
12.28
19.03
19.01
2.01
2.05
2.07
2.05
2.05
1.99
2.03
2.06
2.04
2.04
1.98
2.02
2.04
2.03
2.03
125 (51.7)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
19
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
47.60
35.58
37.00
29.22
47.97
51.31
55.92
33.56
47.25
47.60
41.52
46.52
47.54
45.98
45.98
47.54
26.44
54.17
27.86
32.58
49.63
55.17
31.46
46.30
34.83
38.57
45.47
50.58
44.10
44.10
2.84
2.80
2.77
2.77
2.77
2.79
2.76
2.73
2.73
2.72
2.75
2.71
2.69
2.68
2.67
75 (23.9)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
See Legend and Notes on Page 24.
1575
1400
1225
CFM
EVAPORATOR
AIR
042 High Cool
PERFORMANCE DATA (CONT)
51.07
46.89
43.88
43.95
43.89
50.45
46.29
43.28
42.71
42.52
49.61
45.48
42.48
41.76
40.87
27.57
35.17
33.79
43.95
43.89
26.26
33.07
31.84
42.37
42.52
24.90
30.90
29.82
36.75
40.87
3.12
3.08
3.05
3.05
3.05
3.08
3.04
3.01
3.01
3.01
3.04
3.00
2.97
2.96
2.95
85 (29.4)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
46.25
42.50
39.80
40.27
40.22
45.74
42.00
39.30
39.08
39.03
45.06
41.33
38.64
38.02
37.59
25.93
33.33
31.99
40.27
40.22
24.65
31.30
30.11
39.08
39.03
23.34
29.20
28.16
34.87
37.59
3.45
3.40
3.37
3.38
3.38
3.41
3.36
3.33
3.33
3.33
3.36
3.32
3.28
3.28
3.27
41.47
38.15
35.76
36.59
36.54
41.08
37.75
35.35
35.57
35.52
40.53
37.21
34.81
34.34
34.28
24.28
31.48
30.17
36.59
36.54
23.05
29.52
28.36
35.57
35.52
21.79
27.50
26.49
34.34
34.28
36.77
33.86
31.76
32.90
32.86
36.47
33.55
31.44
32.04
32.01
36.05
33.12
31.02
31.00
30.95
48VG -- A
3.81
3.76
3.72
3.74
3.74
3.76
3.72
3.68
3.69
3.69
3.72
3.67
3.64
3.63
3.63
22.64
29.62
28.34
32.90
32.86
21.45
27.75
26.61
32.04
32.01
20.23
25.80
24.81
31.00
30.95
4.20
4.15
4.12
4.14
4.13
4.16
4.11
4.07
4.08
4.08
4.11
4.06
4.03
4.03
4.03
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Total
Total
Total
MBtuh
MBtuh
MBtuh
Sys
Sys
Sys
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
32.27
29.75
27.94
29.29
29.26
32.06
29.50
27.67
28.59
28.56
31.74
29.18
27.34
27.72
27.68
21.05
27.77
26.51
29.29
29.26
19.90
26.00
24.89
28.59
28.56
18.73
24.14
23.17
27.72
27.68
4.63
4.58
4.55
4.57
4.57
4.59
4.54
4.50
4.52
4.52
4.54
4.49
4.46
4.47
4.47
125 (51.7)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
20
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
37.81
30.32
31.70
25.09
37.81
40.80
44.98
28.96
37.37
37.81
36.82
36.82
37.76
36.76
36.76
37.76
22.88
43.68
24.17
28.19
39.58
44.51
27.06
36.62
30.24
33.38
35.89
40.36
35.18
35.18
2.15
2.19
2.21
2.21
2.21
2.12
2.15
2.18
2.18
2.18
2.08
2.11
2.14
2.14
2.15
75 (23.9)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
See Legend and Notes on Page 24.
1310
1200
1050
CFM
EVAPORATOR
AIR
048 Low Cool
PERFORMANCE DATA (CONT)
41.19
37.39
34.64
35.00
34.95
40.80
37.01
34.28
34.12
34.07
40.10
36.35
33.64
32.99
32.65
22.67
28.84
27.55
35.00
34.95
21.82
27.49
26.30
34.12
34.07
20.63
25.60
24.54
30.42
32.65
2.23
2.26
2.28
2.27
2.27
2.20
2.23
2.25
2.25
2.25
2.16
2.19
2.21
2.21
2.21
85 (29.4)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
37.37
33.93
31.45
32.15
32.10
37.07
33.63
31.15
31.37
31.32
36.50
33.07
30.61
30.13
30.08
20.30
26.03
24.84
32.15
32.10
19.52
24.79
23.69
31.37
31.32
18.44
23.05
22.07
30.13
30.08
2.28
2.31
2.32
2.32
2.32
2.26
2.28
2.30
2.29
2.29
2.22
2.24
2.26
2.26
2.26
33.55
30.46
28.23
29.24
29.20
33.30
30.21
27.99
28.58
28.53
32.85
29.78
27.55
27.49
27.45
18.00
23.28
22.18
29.24
29.20
17.29
22.14
21.13
28.58
28.53
16.30
20.56
19.66
27.49
27.45
2.31
2.33
2.35
2.34
2.34
2.29
2.31
2.32
2.32
2.32
2.26
2.28
2.29
2.29
2.29
29.70
26.96
24.98
26.27
26.23
29.52
26.77
24.79
25.71
25.68
29.17
26.42
24.45
24.80
24.76
15.77
20.59
19.58
26.27
26.23
15.13
19.57
18.64
25.71
25.68
14.23
18.13
17.30
24.80
24.76
2.32
2.33
2.34
2.34
2.34
2.29
2.31
2.32
2.32
2.32
2.26
2.28
2.29
2.29
2.29
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Total
Total
Total
MBtuh
MBtuh
MBtuh
Syst
Syst
Syst
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
48VG -- A
25.85
23.47
21.76
23.26
23.23
25.74
23.32
21.59
22.80
22.77
25.49
23.06
21.33
22.04
22.01
13.64
17.97
21.62
23.26
23.23
13.06
17.07
16.21
22.80
22.77
12.25
15.78
15.03
22.04
22.01
2.28
2.29
2.31
2.30
2.30
2.26
2.28
2.29
2.28
2.28
2.24
2.25
2.26
2.25
2.26
125 (51.7)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
21
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
52.45
39.53
41.19
32.67
52.92
56.86
62.33
37.79
52.30
52.45
46.83
51.47
52.37
51.01
51.01
52.37
29.87
60.49
31.49
36.75
55.12
61.65
35.39
51.23
39.32
43.47
50.28
56.21
48.89
48.89
3.32
3.27
3.24
3.23
3.23
3.27
3.23
3.19
3.18
3.18
3.21
3.16
3.13
3.12
3.11
75 (23.9)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
See Legend and Notes on Page 24.
1750
1600
1400
CFM
EVAPORATOR
AIR
048 High Cool
PERFORMANCE DATA (CONT)
57.41
52.41
48.81
48.85
48.78
56.85
51.86
48.28
47.65
47.56
55.87
50.93
47.37
46.51
45.66
31.06
39.44
37.82
48.85
48.78
29.91
37.62
36.13
47.65
47.56
28.34
35.12
33.80
41.71
45.66
3.62
3.57
3.54
3.54
3.54
3.57
3.53
3.49
3.49
3.48
3.51
3.46
3.43
3.42
3.41
52.50
47.95
44.68
45.21
45.15
52.04
47.50
44.24
44.13
44.07
51.22
46.72
43.48
42.75
42.38
29.43
37.67
36.08
45.21
45.15
28.32
35.90
34.44
44.13
44.07
26.80
33.47
32.17
39.90
42.38
3.95
3.91
3.87
3.88
3.88
3.91
3.86
3.83
3.83
3.83
3.84
3.80
3.77
3.76
3.75
47.61
43.50
40.56
41.52
41.47
47.24
43.13
40.20
40.59
40.53
46.58
42.50
39.57
39.11
39.05
27.80
35.88
34.32
41.52
41.47
26.72
34.16
32.73
40.59
40.53
25.25
31.80
30.53
39.11
39.05
42.73
39.06
36.44
37.79
37.75
42.45
38.77
36.15
37.00
36.95
41.93
38.27
35.65
35.73
35.68
48VG -- A
4.32
4.28
4.24
4.26
4.25
4.28
4.23
4.20
4.20
4.20
4.22
4.17
4.14
4.13
4.13
26.16
34.07
32.53
37.79
37.75
25.11
32.40
30.99
37.00
36.95
23.68
30.11
28.86
35.73
35.68
4.72
4.68
4.65
4.66
4.66
4.68
4.64
4.60
4.62
4.62
4.62
4.58
4.54
4.55
4.55
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
85 (29.4)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Capacity
Total
Total
Total
Total
MBtuh
MBtuh
MBtuh
MBtuh
Sys
Sys
Sys
Sys
Total
Sens
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
KW
37.97
34.73
32.42
34.08
34.04
37.76
34.50
32.18
33.41
33.37
37.37
34.10
31.78
32.34
32.30
24.55
32.25
30.72
34.08
34.04
23.52
30.65
29.26
33.41
33.37
22.12
28.42
27.20
32.34
32.30
5.15
5.12
5.08
5.11
5.11
5.11
5.07
5.04
5.06
5.06
5.06
5.02
4.98
4.99
4.99
125 (51.7)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
22
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
46.03
36.92
38.62
30.56
45.92
49.57
54.62
34.73
45.25
46.03
44.18
44.59
45.96
44.36
44.36
45.96
27.58
52.94
29.08
33.87
47.96
53.90
32.51
44.37
36.25
40.01
43.53
48.88
42.50
42.50
75 (23.9)
Capacity
MBtuh
Total
Sens
See Legend and Notes on Page 24.
1545
1370
1200
CFM
EVAPORATOR
AIR
060 Low Cool
2.69
2.71
2.73
2.73
2.73
2.62
2.65
2.67
2.67
2.67
2.56
2.59
2.61
2.61
2.61
Total
Syst
KW
PERFORMANCE DATA (CONT)
52.62
47.78
44.29
44.84
44.78
52.00
47.18
43.69
43.36
43.29
51.15
46.38
42.92
42.15
41.54
29.14
37.08
35.42
44.84
44.78
27.69
34.77
33.28
43.36
43.29
26.23
32.46
31.12
38.49
41.54
85 (29.4)
Capacity
MBtuh
Total
Sens
2.71
2.73
2.75
2.75
2.75
2.65
2.68
2.69
2.69
2.69
2.60
2.62
2.63
2.64
2.64
50.31
45.71
42.38
43.41
43.35
49.80
45.19
41.88
42.05
41.98
49.07
44.50
41.20
40.55
40.36
27.69
35.51
33.88
43.41
43.35
26.28
33.26
31.80
42.05
41.98
24.86
31.00
29.70
40.24
40.36
2.71
2.72
2.73
2.73
2.73
2.65
2.67
2.68
2.68
2.68
2.60
2.62
2.63
2.63
2.63
47.64
43.29
40.14
41.65
41.59
47.23
42.87
39.71
40.42
40.36
46.63
42.28
39.14
38.94
38.87
26.20
33.88
32.27
41.65
41.59
24.83
31.70
30.26
40.42
40.36
23.45
29.49
28.21
38.94
38.87
2.66
2.67
2.68
2.67
2.67
2.61
2.62
2.63
2.63
2.63
2.57
2.58
2.59
2.59
2.59
44.54
40.48
37.53
39.51
39.46
44.23
40.13
37.17
38.42
38.36
43.75
39.65
36.69
37.09
37.03
24.66
32.18
30.58
39.51
39.46
23.32
30.07
28.64
38.42
38.36
21.98
27.93
26.66
37.09
37.03
2.56
2.57
2.57
2.57
2.57
2.52
2.53
2.53
2.53
2.53
2.48
2.49
2.49
2.49
2.49
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Total
Total
Total
Total
MBtuh
MBtuh
MBtuh
Syst
Syst
Syst
Syst
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
KW
48VG -- A
40.98
37.28
34.57
36.97
36.92
40.79
36.99
34.23
36.03
35.98
40.44
36.60
33.85
34.87
34.82
23.08
30.36
34.35
36.97
36.92
21.77
28.37
26.95
36.03
35.98
20.47
26.30
25.05
34.87
34.82
2.39
2.40
2.41
2.40
2.40
2.36
2.37
2.37
2.37
2.37
2.33
2.33
2.34
2.34
2.34
125 (51.7)
Capacity
Total
MBtuh
Syst
Total
Sens
KW
23
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.8)
62
(16.6)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
62.99
48.75
50.85
39.95
62.73
67.27
73.56
45.99
61.92
62.99
60.84
61.23
62.91
60.99
60.99
62.91
36.12
71.52
38.07
44.77
65.32
72.71
43.11
60.83
47.87
53.13
59.85
66.43
58.66
58.66
4.06
4.02
3.99
3.99
3.99
3.98
3.94
3.91
3.90
3.90
3.90
3.86
3.82
3.82
3.81
75 (23.9)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
See Legend and Notes on Page 24.
2250
2000
1750
CFM
EVAPORATOR
AIR
060 High Cool
PERFORMANCE DATA (CONT)
68.73
62.89
58.69
59.49
59.42
68.00
62.19
57.99
57.75
57.68
67.01
61.22
57.05
56.20
55.57
38.24
49.01
46.95
59.49
59.42
36.40
46.10
44.25
57.75
57.68
34.50
43.05
41.43
51.25
55.57
4.43
4.39
4.35
4.36
4.35
4.35
4.30
4.26
4.26
4.26
4.27
4.22
4.18
4.17
4.17
85 (29.4)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
63.76
58.40
54.54
55.83
55.76
63.17
57.80
53.95
54.29
54.22
62.34
57.00
53.16
52.51
52.33
36.50
47.12
45.08
55.83
55.76
34.70
44.27
42.45
54.29
54.22
32.84
41.30
39.70
52.25
52.33
4.86
4.80
4.76
4.77
4.77
4.78
4.72
4.67
4.68
4.68
4.69
4.63
4.58
4.58
4.58
58.61
53.75
50.24
51.99
51.93
58.16
53.27
49.76
50.64
50.58
57.48
52.61
49.10
48.99
48.92
34.70
45.15
43.14
51.99
51.93
32.94
42.39
40.60
50.64
50.58
31.12
39.48
37.91
48.99
48.92
53.29
48.94
45.80
47.94
47.89
52.95
48.55
45.40
46.80
46.74
52.44
48.03
44.88
45.37
45.32
48VG -- A
5.34
5.27
5.22
5.25
5.25
5.26
5.19
5.13
5.15
5.15
5.17
5.10
5.04
5.05
5.04
32.85
43.08
41.08
47.94
47.89
31.12
40.42
38.65
46.80
46.74
29.35
37.60
36.06
45.37
45.32
5.87
5.80
5.73
5.78
5.78
5.79
5.71
5.65
5.68
5.68
5.70
5.62
5.56
5.57
5.57
CONDENSER ENTERING AIR TEMPERATURES _F (_C)
95 (35)
105 (40.6)
115 (46.1)
Capacity
Capacity
Capacity
Total
Total
Total
MBtuh
MBtuh
MBtuh
Sys
Sys
Sys
Total
Sens
Total
Sens
Total
Sens
KW
KW
KW
47.96
44.15
41.35
43.79
43.74
47.73
43.81
41.00
42.83
42.79
47.35
43.40
40.58
41.63
41.58
31.01
40.88
38.84
43.79
43.74
29.31
38.42
36.66
42.83
42.79
27.57
35.70
34.17
41.63
41.58
6.46
6.38
6.30
6.37
6.37
6.37
6.29
6.22
6.27
6.27
6.29
6.20
6.13
6.16
6.16
125 (51.7)
Capacity
Total
MBtuh
Sys
Total
Sens
KW
24
1.10 x cfm
Sensible capacity (Btuh)
= hewb ---
hlwb
Where: hewb = Enthalpy of air entering evaporator coil
4. The SHC is based on 805 F (26.6_C) edb temperature of air entering
evaporator coil. Below 80_F (26.6_C) edb, subtract (corr factor x cfm) from
SHC.
Above 80_ F (26.6_C) edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 + BF) x (edb --- 80).
5. Integrated capacity is maximum (instantaneous) capacity less the effect
of frost on the outdoor coil and the heat required to defrost it.
4.5 x cfm
total capacity (Btuh)
air leaving evaporator coil (hlwb)
=
Wet---bulb temperature corresponding to enthalpy
= tedb ---
tlwb
tldb
COOLING NOTES:
1. Ratings are net; they account for the effects of the evaporator ---fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
* At 75F (24C) entering dry bulb---Tennessee Valley Authority (TVA) rating conditions; all others at 80F (27C) dry bulb.
LEGEND
BF— Bypass Factor
edb— Entering Dry ---Bulb
Ewb— Entering Wet---Bulb
kW — Total Unit Power Input
SHC— Sensible Heat Capacity (1000 Btuh)
TC — Total Capacity (1000 Btuh) (net)
rh—Relative Humidity
PERFORMANCE DATA (CONT)
48VG -- A
PERFORMANCE DATA (CONT)
GAS ADJUSTMENT
Natural Gas Orifice Sizes and Manifold Pressure
208/230VAC Models
40000
60000
90000
115000
130000
Orifice No. (Qty)
ALTITUDE OF INSTALLATION (FT. [m] ABOVE SEA LEVEL) U.S.A.*
2001 to
0 to 2000
3001 to 4000
4001 to 5000
5001 to 6000
3000*
[0 to 610]
[915 to 1219]
[1220 to 1524]
[1524 to 1829]
[610 to 914]
44 (2)
45 (2)†
48 (2)†
48 (2)†
48 (2)†
Manifold Press. High / Low (in. W.C.)
Orifice No. (Qty)
3.2 /1.4
44 (3)
3.2 /1.4
45 (3)†
3.8 /1.6
48 (3)†
3.5 /1.5
48 (3)†
3.2 /1.4
48 (3)†
Manifold Press. High / Low (in. W.C.)
Orifice No. (Qty)
3.2 /1.4
38 (3)
3.2 /1.4
41 (3)†
3.8 /1.6
41 (3)†
3.5 /1.5
42 (3)†
3.2 /1.4
42 (3)†
Manifold Press. High / Low (in. W.C.)
Orifice No. (Qty)
3.6 /1.6
33 (3)
3.8 /1.6
36 (3)†
3.4 /1.5
36 (3)†
3.4 /1.5
36 (3)†
3.2 /1.4
38 (3)†
Manifold Press. High / Low (in. W.C.)
Orifice No. (Qty)
Manifold Press. High / Low (in. W.C.)
3.8 /1.7
31 (3)
3.8 /1.7
3.8 /1.7
31 (3)
3.2 /1.4
3.6 /1.6
33 (3)†
3.7 /1.6
3.3 /1.4
33 (3)†
3.4 /1.4
3.6 /1.5
34 (3)†
3.3 /1.4
Natural Gas Orifice Sizes and Manifold Pressure
460V
ALTITUDE OF INSTALLATION (FT. ABOVE SEA LEVEL) U.S.A.*
3001 to 4000
4001 to 5000
5001 to 6000
0 to 2000
2001 to 3000*
(915 to 1219
(1220 to 1524
(1524 to 1829
(0--- 610 m)
(611 to 914 m)
m)
m)
m)
Orifice No. (Qty)
38 (2)
41 (2)†
41 (2)†
42 (2)†
42 (2)†
60000
Manifold Press. (in. W.C.)
3.6
3.8
3.4
3.4
3.2
Orifice No. (Qty)
38 (3)
41 (3)†
41 (3)†
42 (3)†
42 (3)†
90000
Manifold Press. (in. W.C.)
3.6
3.8
3.4
3.4
3.2
Orifice No. (Qty)
33 (3)
36 (3)†
36 (3)†
36 (3)†
38 (3)†
115000
Manifold Press. (in. W.C.)
3.8
3.8
3.6
3.3
3.6
Orifice No. (Qty)
31 (3)
31 (3)
33 (3)†
33 (3)†
34 (3)†
130000
Manifold Press. (in. W.C.)
3.8
3.2
3.7
3.4
3.3
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft, use U.S.A. column 2001 to 3000 ft (610 to 914 m).
† Orifices available through your distributor.
Nameplate Input
(Btu/hr)
NOTE: Orifice sizes and manifold pressure settings are based on natural gas with a heating value of 1025 Btu/ft3 and a specific gravity of .6.
Propane Gas Orifice Sizes and Manifold Pressure
208/230VAC Models
Nameplate
Input,
High Stage
(Btu/hr)
40000
60000
90000
115000
130000
ALTITUDE OF INSTALLATION (FT. ABOVE SEA LEVEL) U.S.A.*†
Orifice No. (Qty)
Manifold Press. High / Low (in. W.C.)
Orifice No. (Qty)
Manifold Press. High / Low (in. W.C.)
Orifice No. (Qty)
Manifold Press. High / Low (in. W.C.)
Orifice No. (Qty)
Manifold Press. High / Low (in. W.C.)
Orifice No. (Qty)
Manifold Press. High / Low (in. W.C.)
0 to 2000
[0 to 610]
2001 to 3000*
[610 to 914]
3001 to 4000
[915 to 1219]
4001 to 5000
[1220 to 1524]
5001 to 6000
[1524 to 1829]
55 (2)
10.0/5.0
55 (3)
10.0/5.0
53 (3)
10.0/5.4
51 (3)
10.0/5.4
49 (3)
10.0/5.4
56 (2)
11.0/6.0
56 (3)
11.0/6.0
54 (3)
11.0/6.4
52 (3)
11.0/5.0
50 (3)
11.0/4.8
56 (2)
11.0/5.5
56 (3)
11.0/5.5
54 (3)
11.0/5.9
52 (3)
10.6/4.8
51 (3)
11.0/4.9
56 (2)
11.0/5.0
56 (3)
11.0/5.0
54 (3)
11.0/5.4
53 (3)
11.0/6.1
52 (3)
11.0/5.2
56 (2)
10.7/4.8
56 (3)
10.7/4.8
54 (3)
11.0/5.0
53 (3)
11.0/5.5
52 (3)
11.0/5.0
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft, use U.S.A. column 2001 to 3000 ft (610 to 914 m).
† Use Kit No. CPLPCONV013B00 (0--- 2000 ft [0--- 610 m] above sea level. Use Kit No. CPLPCONV014B00 (2001--- 6000 ft [611--- 1829 m] above sea level.
25
48VG -- A
Nameplate
Input,
High Stage
(Btu/hr)
PERFORMANCE DATA (CONT)
Propane Gas Orifice Sizes and Manifold Pressure
460V
ALTITUDE OF INSTALLATION (FT. ABOVE SEA LEVEL) U.S.A.*
0 to 2000
2001 to 3000*
3001 to 4000
4001 to 5000
5001 to 6000
(0--- 610 m)
(611 to 914 m)
(915 to 1219 m)
(1220 to 1524 m)
(1524 to 1829 m)
Orifice No. (Qty)
53 (2)
54 (2)
54 (2)
54 (2)
54 (2)
60000
Manifold Press. (IN. W.C.)
10.0
11.0
11.0
11.0
11.0
Orifice No. (Qty)
53 (3)
54 (3)
54 (3)
54 (3)
54 (3)
90000
Manifold Press. (IN. W.C.)
10.0
11.0
11.0
11.0
11.0
Orifice No. (Qty)
51 (3)
52 (3)
52 (3)
53 (3)
53 (3)
115000
Manifold Press. (IN. W.C.)
10.0
11.0
10.6
11.0
11.0
Orifice No. (Qty)
49 (3)
50 (3)
51 (3)
52 (3)
52 (3)
130000
Manifold Press. (IN. W.C.)
10.0
11.0
11.0
11.0
11.0
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft (610 ---1372 m), use U.S.A. column 2001 to 3000 ft (611 to 914 m).
†Use Kit No. CPLPCONV013B00 (0 ---2000 ft [0 ---610 m] above sea level). Use Kit No. CPLPCONV014B00 (2001 ---6000 ft [611 ---1829 m] above sea level).
48VG -- A
Nameplate
Input (Btu/hr)
High Altitude Compensation: Natural Gas
208/230VAC Models
Nameplate
Input, High
Stage
(Btu/hr)
Rated Heating Input (Btu/hr), Natural Gas at Installation Altitude Above Sea Level, U.S.A.*
0 to 2000 ft
0 to 610 m
2001 to 3000 ft*
610 to 914 m
3001 to 4000 ft
915 to 1219 m
4001 to 5000 ft
1220 to 1524 m
5001 to 6000 ft
1524 to 1829 m
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
40000
40000
26000
36000
23400
34400
22300
32800
21300
31200
20300
60000
60000
39000
54000
35100
51600
33500
49200
32000
46800
30400
90000
90000
58500
81000
52700
77400
50300
73800
48000
70200
45600
115000
115000
75000
103500
67500
98900
64500
94300
61500
89700
58500
130000
130000
84500
117000
76100
111800
72700
106600
69300
101400
65900
High Altitude Compensation, Natural Gas
460V
Rated Heating Input (Btu/hr), Natural Gas at Installation Altitude Above Sea Level, U.S.A.*
0 to 2000 ft
2001 to 3000 ft*
3001 to 4000 ft
4001 to 5000 ft
5001 to 6000 ft
(0--- 610 m)
(611 to 914 m)
(915 to 1219 m)
(1220 to 1524 m)
(1524 to 1829 m)
60000
60000
54000
51600
49200
46800
90000
90000
81000
77400
73800
70200
115000
115000
103500
98900
94300
89700
130000
130000
117000
111800
106600
101400
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above Sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft (610 ---1372 m), use U.S.A. column 2001 to 3000 ft (611 to 914 m).
Nameplate
Input (Btu/hr)
High Altitude Compensation: Propane Gas
208/230VAC Models
Nameplate
Input, High
Stage
(Btu/hr)
Rated Heating Input (Btu/hr), LP Gas at Installation Altitude Above Sea Level, U.S.A.*
0 to 2000 ft
0 to 610 m
2001 to 3000 ft*
610 to 914 m
3001 to 4000 ft
915 to 1219 m
4001 to 5000 ft
1220 to 1524 m
5001 to 6000 ft
1524 to 1829 m
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
40000
38000
26000
31700
23400
31700
22300
31700
21300
31200
20300
60000
57000
39000
47500
35100
47500
33500
47500
32000
46800
30400
90000
79000
58500
68900
52700
68900
50300
68600
48000
68600
45600
115000
103000
75000
100400
67500
98900
64500
83000
61500
83000
58500
130000
116000
84500
115500
76100
111800
72700
101300
69300
100400
65900
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft (610 ---1372 m), use U.S.A. column 2001 to 3000 ft (611 to 914 m).
26
High Altitude Compensation, Propane Gas
460V
Rated Heating Input (Btu/hr), Propane Gas at Installation Altitude Above Sea Level, U.S.A.*
0 to 2000 ft
2001 to 3000 ft*
3001 to 4000 ft
4001 to 5000 ft
5001 to 6000 ft
(0--- 610 m)
(611 to 914 m)
(915 to 1219 m)
(1220 to 1524 m)
(1524 to 1829 m)
60000
53000
45900
45900
45800
45800
90000
79000
68900
68900
68600
68600
115000
103000
100400
98900
83000
83000
130000
116000
115500
111800
101300
100400
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft (610 ---1372 m), use U.S.A. column 2001 to 3000 ft (611 to 914 m).
48VG -- A
Nameplate Input
(Btu/hr)
27
28
15 - 45oF Low Stage,
20 - 50oF High Stage
48VG(A,N)24040
See notes on page 41.
HEATING RISE
RANGE
UNIT
High
Black
Orange
Med-High2
Pink
Med-Low1
Red
Blue
Low3
Medium4
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
0.1
714
0.08
26
(15)
41
(23)
689
0.08
27
(15)
42
(23)
877
0.12
21
(12)
33
(18)
921
0.14
20
(11)
32
(18)
1291
0.31
15
(8)
23
(13)
NA
NA
489
0.06
38
(21)
NA
597
0.06
31
(17)
49
(27)
779
0.12
24
(13)
37
(21)
829
0.14
23
(13)
35
(20)
1206
0.32
16
(9)
24
(13)
NA
NA
598
0.14
31
(17)
49
(27)
663
0.16
28
(16)
44
(24)
1081
0.34
17
(10)
27
(15)
NA
698
0.13
27
(15)
42
(23)
754
0.15
25
(14)
39
(21)
1142
0.33
16
(9)
25
(14)
888
0.36
21
(12)
33
(18)
951
0.35
20
(11)
31
(17)
NA
371
0.18
NA
485
0.17
39
(22)
582
0.17
32
(18)
50
(28)
1017
0.34
18
(10)
29
(16)
NA
NA
-----
NA
NA
-----
NA
NA
NA
NA
NA
410
0.15
NA
NA
-----
NA
NA
NA
519
0.15
36
(20)
NA
-----
NA
NA
NA
352
0.05
NA
823
0.36
23
(13)
35
(20)
NA
NA
-----
NA
NA
-----
NA
NA
-----
NA
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
------------------------NA
0.2
525
0.07
36
(20)
753
0.37
25
(14)
39
(21)
NA
NA
-----
NA
NA
-----
NA
NA
-----
NA
NA
0.9
-----
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
48VG -- A
668
0.37
28
(16)
44
(24)
NA
NA
-----
NA
NA
-----
NA
NA
-----
NA
NA
1
-----
29
25 - 55oF Low Stage,
25 - 55oF High Stage
48VG(A,N)24060
See notes on page 41.
HEATING RISE
RANGE
UNIT
High
Black
Orange
Med-High4
Pink
Med-Low3
Red
Blue
Low1
Medium2
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
NA
37
(20)
NA
34
(19)
829
0.14
34
(19)
54
(30)
1171
0.30
921
0.14
31
(17)
48
(27)
1229
0.28
38
(21)
1206
0.32
NA
NA
NA
692
0.10
41
(23)
777
0.09
37
(20)
36
(20)
1291
0.31
NA
NA
NA
0.2
597
0.06
48
(27)
0.1
689
0.08
41
(23)
NA
48VG -- A
980
0.32
29
(16)
45
(25)
1017
0.34
28
(16)
44
(24)
NA
1049
0.31
27
(15)
42
(24)
1081
0.34
26
(15)
41
(23)
NA
1105
0.30
26
(14)
40
(22)
1142
0.33
25
(14)
39
(22)
NA
NA
318
0.12
NA
NA
582
0.17
49
(27)
NA
NA
465
0.11
NA
NA
663
0.16
43
(24)
754
0.15
38
(21)
NA
583
0.10
49
(27)
NA
NA
913
0.33
31
(17)
49
(27)
951
0.35
30
(17)
47
(26)
NA
NA
485
0.17
NA
NA
-----
NA
NA
838
0.33
34
(19)
53
(29)
888
0.36
32
(18)
50
(28)
NA
NA
371
0.18
NA
NA
-----
NA
NA
NA
NA
NA
668
0.37
43
(24)
NA
753
0.37
38
(21)
NA
823
0.36
35
(19)
54
(30)
516
0.33
55
(31)
NA
NA
-----
NA
NA
-----
NA
NA
1
-----
679
0.34
42
(23)
NA
NA
-----
NA
NA
-----
NA
NA
0.9
-----
775
0.34
37
(20)
NA
NA
-----
NA
NA
-----
NA
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
489
352
--------0.06
0.05
---------
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
30
15 - 45oF Low Stage,
20 - 50oF High Stage
48VG(A,N)30040
See notes on page 41.
HEATING RISE
RANGE
UNIT
High
Black
Orange
Med-High2
Pink
Med-Low1
Red
Blue
Low3
Medium4
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
NA
670
0.12
28
(16)
43
(24)
698
0.13
27
(15)
42
(23)
1012
0.24
19
(10)
29
(16)
1382
0.50
NA
21
(12)
NA
765
0.12
25
(14)
38
(21)
779
0.12
24
(13)
37
(21)
1069
0.23
18
(10)
27
(15)
1460
0.52
NA
20
(11)
NA
NA
NA
22
(12)
NA
586
0.13
32
(18)
50
(28)
598
0.14
31
(17)
49
(27)
937
0.24
20
(11)
31
(17)
1301
0.48
NA
NA
NA
724
0.26
26
(14)
40
(22)
1003
0.42
19
(10)
29
(16)
NA
786
0.26
24
(13)
37
(21)
1114
0.44
17
(9)
26
(15)
NA
870
0.25
22
(12)
33
(19)
1209
0.46
16
(9)
24
(13)
----NA
410
0.15
519
0.15
36
(20)
NA
NA
-----
NA
NA
NA
NA
NA
299
0.14
NA
NA
NA
466
0.13
40
(22)
NA
NA
626
0.27
30
(17)
47
(26)
890
0.40
21
(12)
33
(18)
NA
NA
-----
NA
NA
-----
NA
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
-------------------------
0.1
714
0.08
26
(15)
41
(23)
831
0.11
23
(13)
35
(19)
877
0.12
21
(12)
33
(18)
1139
0.22
17
(9)
26
(14)
1531
0.53
0.2
525
0.07
36
(20)
NA
629
0.35
30
(17)
46
(26)
NA
NA
381
0.28
NA
NA
-----
NA
NA
-----
NA
NA
1
-----
764
0.37
25
(14)
38
(21)
512
0.27
37
(20)
NA
NA
-----
NA
NA
-----
NA
NA
0.9
-----
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
48VG -- A
31
25 - 55oF Low Stage,
25 - 55oF High Stage
48VG(A,N)30060
See notes on page 41.
HEATING RISE
RANGE
UNIT
High
Black
Orange
Med-High4
Pink
Med-Low1
Red
Blue
Low3
Medium2
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
38
(21)
1460
0.52
NA
30
(17)
NA
29
(16)
1069
0.23
27
(15)
42
(23)
1171
0.30
NA
1012
0.24
28
(16)
44
(24)
1105
0.30
26
(14)
40
(22)
1382
0.50
NA
36
(20)
1531
0.53
NA
765
0.12
37
(21)
831
0.11
34
(19)
54
(30)
1139
0.22
25
(14)
39
(22)
1229
0.28
NA
670
0.12
43
(24)
NA
NA
32
(18)
NA
NA
0.2
692
0.10
41
(23)
0.1
777
0.09
37
(21)
37
(21)
NA
870
0.25
33
(18)
51
(28)
980
0.32
29
(16)
45
(25)
1209
0.46
NA
NA
466
0.13
NA
48VG -- A
34
(19)
NA
937
0.24
30
(17)
47
(26)
1049
0.31
27
(15)
42
(23)
1301
0.48
NA
586
0.13
49
(27)
NA
NA
NA
NA
629
0.35
45
(25)
NA
764
0.37
37
(21)
NA
NA
516
0.33
55
(31)
890
0.40
32
(18)
50
(28)
NA
NA
381
0.28
NA
NA
-----
NA
NA
1
-----
679
0.34
42
(23)
NA
NA
512
0.27
NA
NA
-----
NA
NA
0.9
-----
775
0.34
37
(21)
NA
838
0.33
34
(19)
53
(29)
1003
0.42
28
(16)
44
(24)
NA
913
0.33
31
(17)
49
(27)
1114
0.44
26
(14)
40
(22)
NA
NA
-----
NA
626
0.27
46
(26)
NA
NA
-----
NA
724
0.26
39
(22)
786
0.26
36
(20)
NA
NA
299
0.14
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
583
465
318
------0.10
0.11
0.12
------49
NA
NA
NA
NA
NA
(27)
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
32
25 - 55oF Low Stage,
25 - 55oF High Stage
48VG(A,N)36060
See notes on page 41.
HEATING RISE
RANGE
UNIT
High
Black
Orange
Med-High2
Pink
Med-Low1
Red
Blue
Low3
Medium4
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
NA
37
(21)
1423
0.31
NA
31
(17)
36
(20)
1466
0.30
NA
30
(17)
38
(21)
1198
0.21
NA
NA
864
0.10
33
(18)
52
(29)
1169
0.17
934
0.10
31
(17)
48
(26)
1213
0.16
37
(20)
1251
0.19
NA
NA
NA
0.2
624
0.05
46
(25)
0.1
694
0.05
41
(23)
32
(18)
NA
810
0.11
35
(20)
55
(31)
1110
0.17
26
(14)
40
(22)
1149
0.21
25
(14)
39
(22)
1384
0.33
NA
1016
0.20
28
(16)
44
(24)
1066
0.24
27
(15)
42
(23)
1308
0.35
1065
0.19
27
(15)
42
(23)
1104
0.23
26
(14)
40
(22)
1343
0.34
33
(18)
34
(19)
NA
NA
NA
NA
698
0.13
41
(23)
NA
745
0.12
38
(21)
NA
35
(20)
NA
964
0.21
30
(16)
46
(26)
1017
0.25
28
(16)
44
(24)
1263
0.36
NA
649
0.14
44
(24)
NA
37
(20)
NA
923
0.22
31
(17)
48
(27)
970
0.26
29
(16)
46
(25)
1219
0.37
NA
571
0.14
50
(28)
NA
38
(21)
NA
878
0.23
33
(18)
51
(28)
932
0.27
31
(17)
48
(27)
1183
0.38
NA
525
0.15
54
(30)
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
533
460
383
328
----0.06
0.07
0.07
0.08
----54
NA
NA
NA
NA
NA
(30)
820
0.24
35
(19)
54
(30)
892
0.28
32
(18)
50
(28)
1145
0.40
25
(14)
39
(22)
NA
NA
486
0.16
NA
NA
0.9
-----
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
48VG -- A
839
0.29
34
(19)
53
(29)
1106
0.41
26
(14)
40
(22)
NA
777
0.25
37
(20)
NA
NA
428
0.17
NA
NA
1
-----
33
35 - 65oF Low Stage,
35 - 65oF High Stage
48VG(A,N)36090
See notes on page 41.
HEATING RISE
RANGE
UNIT
High
Black
Orange
Med-High4
Pink
Med-Low1
Red
Blue
Low3
Medium2
WIRE
COLOR
MOTOR
SPEED
0.29
Low Stage Heat Rise
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
oF
BHP
48
(26)
1423
0.31
NA
47
(26)
NA
46
(26)
NA
0.30
46
(26)
1466
0.30
NA
NA
54
(30)
1451
1198
0.21
36
(20)
56
(31)
1415
1251
0.19
49
(27)
NA
49
(27)
1384
0.33
NA
0.31
1149
0.21
37
(21)
59
(33)
1372
NA
52
(29)
NA
52
(29)
1308
0.35
NA
1066
0.24
40
(22)
63
(35)
1287
248.
59
NA
48VG -- A
50
(28)
NA
51
(28)
1343
0.34
NA
0.32
1104
0.23
39
(22)
61
(34)
1327
NA
53
(30)
NA
54
(30)
1263
0.36
NA
0.35
35
(20)
56
(31)
1219
0.37
35
(20)
55
(31)
0.36
NA
37
(20)
58
(32)
1183
0.38
36
(20)
57
(32)
0.37
1168
NA
1212
NA
1249
NA
NA
525
0.15
932
0.27
46
(26)
NA
NA
571
0.14
970
0.26
44
(25)
1017
0.25
42
(23)
NA
NA
649
0.14
NA
NA
698
0.13
62
(34)
NA
NA
745
0.12
58
(32)
NA
810
0.11
53
(29)
NA
864
0.10
50
(28)
NA
NA
NA
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
823
747
669
636
558
513
0.10
0.11
0.12
0.13
0.13
0.14
52
58
64
NA
NA
NA
(29)
(32)
(36)
0.2
971
0.11
44
(25)
0.1
1097
0.12
39
(22)
61
(34)
934
0.10
46
(26)
38
(21)
60
(33)
1145
0.40
38
(21)
59
(33)
0.38
1130
NA
892
0.28
48
(27)
NA
NA
486
0.16
NA
NA
0.9
456
0.15
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
39
(22)
62
(34)
1106
0.41
39
(22)
61
(34)
0.39
1094
NA
839
0.29
51
(28)
NA
NA
428
0.17
NA
NA
1
412
0.16
34
25 - 55oF Low Stage,
25 - 55oF High Stage
48VG(A,N)42060
See notes on page 41.
HEATING RISE
RANGE
UNIT
High
Black
Orange
Med-High2
Pink
Med-Low1
Red
Blue
Low3
Medium4
WIRE
COLOR
MOTOR
SPEED
Low Stage Heat Rise
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
31
(17)
1590
0.43
NA
28
(16)
NA
27
(15)
NA
31
(17)
1633
0.41
NA
0.29
BHP
0.30
38
(21)
1415
oF
NA
37
(20)
1451
1026
0.14
28
(15)
43
(24)
1169
0.17
1076
0.13
27
(15)
41
(23)
1213
0.16
NA
NA
NA
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
0.2
624
0.05
46
(25)
0.1
694
0.05
41
(23)
29
(16)
NA
32
(18)
1552
0.44
NA
0.31
972
0.15
29
(16)
46
(25)
1110
0.17
26
(14)
40
(22)
1372
NA
29
(16)
NA
34
(18)
1518
0.45
NA
0.32
918
0.15
31
(17)
48
(27)
1065
0.19
27
(15)
42
(23)
1327
NA
30
(17)
NA
35
(19)
1483
0.47
NA
872
0.17
33
(18)
51
(28)
1016
0.20
28
(16)
44
(24)
1287
248.
59
NA
31
(17)
NA
36
(20)
1444
0.48
NA
0.35
827
0.18
35
(19)
54
(30)
964
0.21
30
(16)
46
(26)
1249
NA
878
0.23
33
(18)
51
(28)
1168
923
0.22
31
(17)
48
(27)
1212
32
(18)
NA
37
(20)
1406
0.49
NA
32
(18)
NA
38
(21)
1372
0.50
NA
0.37
NA
NA
0.36
714
0.20
40
(22)
NA
771
0.18
37
(21)
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
533
460
383
328
----0.06
0.07
0.07
0.08
----54
NA
NA
NA
NA
NA
(30)
33
(18)
NA
25
(14)
39
(22)
1340
0.51
0.38
820
0.24
35
(19)
54
(30)
1130
NA
666
0.21
43
(24)
NA
NA
0.9
-----
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
48VG -- A
34
(19)
NA
26
(15)
41
(23)
1303
0.53
0.39
1094
NA
777
0.25
37
(20)
NA
611
0.22
47
(26)
NA
NA
1
-----
35
35 - 65oF Low Stage,
35 - 65oF High Stage
48VG(A,N)42090
See notes on page 41.
HEATING RISE
RANGE
UNIT
High4
Black
Orange
Med-High2
Pink
Med-Low1
Red
Blue
Low3
Medium
WIRE
COLOR
MOTOR
SPEED
0.29
BHP
Low Stage Heat Rise
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
oF
54
(30)
1451
NA
42
(24)
41
(23)
48
(26)
1590
0.43
NA
43
(24)
NA
49
(27)
1552
0.44
NA
0.31
1149
0.21
37
(21)
59
(33)
1372
1198
0.21
36
(20)
56
(31)
1415
0.30
NA
45
(25)
NA
52
(29)
1483
0.47
NA
1066
0.24
40
(22)
63
(35)
1287
248.
59
NA
48VG -- A
44
(25)
NA
51
(28)
1518
0.45
NA
0.32
1104
0.23
39
(22)
61
(34)
1327
NA
872
0.17
49
(27)
47
(26)
NA
54
(30)
1444
0.48
NA
0.35
48
(27)
NA
35
(20)
56
(31)
1406
0.49
0.36
NA
49
(27)
NA
37
(20)
58
(32)
1372
0.50
0.37
1168
NA
1212
NA
1249
NA
714
0.20
60
(33)
932
0.27
46
(26)
NA
771
0.18
56
(31)
970
0.26
44
(25)
1017
0.25
42
(23)
NA
827
0.18
52
(29)
NA
NA
918
0.15
47
(26)
NA
972
0.15
44
(25)
NA
1026
0.14
42
(23)
NA
NA
NA
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
823
747
669
636
558
513
0.10
0.11
0.12
0.13
0.13
0.14
52
58
64
NA
NA
NA
(29)
(32)
(36)
0.2
971
0.11
44
(25)
NA
46
(26)
1633
0.41
NA
NA
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
0.1
1097
0.12
39
(22)
61
(34)
1076
0.13
40
(22)
63
(35)
1251
0.19
50
(28)
NA
38
(21)
60
(33)
1340
0.51
0.38
1130
NA
892
0.28
48
(27)
NA
666
0.21
64
(36)
NA
NA
0.9
456
0.15
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
52
(29)
NA
39
(22)
62
(34)
1303
0.53
0.39
1094
NA
839
0.29
51
(28)
NA
NA
611
0.22
NA
NA
1
412
0.16
36
35 - 65oF Low Stage,
35 - 65oF High Stage
48VG(A,N)48090
See notes on page 41.
HEATING RISE
RANGE
UNIT
High
Black
Orange
Med-High2
Pink
Med-Low1
Red
Blue
Low3
Medium4
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
NA
41
(23)
1837
0.57
NA
37
(20)
40
(22)
1854
0.56
NA
36
(20)
52
(29)
1650
0.44
NA
NA
50
(28)
1686
0.42
38
(21)
NA
42
(23)
1781
0.60
NA
38
(21)
NA
43
(24)
1784
0.59
NA
1121
0.23
38
(21)
60
(33)
1191
0.25
36
(20)
57
(31)
1576
0.46
39
(22)
NA
44
(24)
1720
0.62
NA
1066
0.24
40
(22)
63
(35)
1139
0.26
38
(21)
59
(33)
1544
0.48
1050
0.29
41
(23)
64
(36)
1468
0.51
1091
0.28
39
(22)
62
(34)
1503
0.49
40
(22)
NA
45
(25)
1698
0.63
41
(23)
NA
46
(26)
1655
0.64
NA
NA
NA
NA
974
0.26
44
(25)
1027
0.25
42
(23)
NA
41
(23)
NA
47
(26)
1625
0.66
NA
43
(24)
NA
48
(27)
1578
0.67
NA
NA
44
(24)
NA
50
(28)
1532
0.67
NA
1356
0.55
NA
1393
0.53
NA
1433
0.52
NA
839
0.29
51
(28)
NA
NA
1
-----
895
0.32
48
(27)
NA
887
0.28
48
(27)
NA
NA
0.9
-----
952
0.31
45
(25)
1001
0.30
43
(24)
NA
942
0.27
46
(25)
NA
1177
0.21
36
(20)
57
(32)
1240
0.24
35
(19)
54
(30)
1617
0.45
NA
1229
0.20
35
(19)
55
(30)
1299
0.23
NA
NA
NA
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
703
587
501
449
380
340
0.09
0.09
0.09
0.10
0.11
0.12
61
NA
NA
NA
NA
NA
(34)
0.2
904
0.10
48
(26)
NA
53
(29)
1340
0.22
NA
0.1
1067
0.12
40
(22)
63
(35)
1271
0.19
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
48VG -- A
37
30 - 60oF Low Stage,
30 - 60oF High Stage
48VG(A,N)48115
See notes on page 41.
HEATING RISE
RANGE
UNIT
High4
Black
Orange
Med-High
Pink
Med-Low3
Red
Blue
Low1
Medium2
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
1650
0.44
34
(19)
53
(29)
1837
0.57
30
(17)
47
(26)
1900
0.61
1686
0.42
33
(18)
52
(29)
1854
0.56
30
(17)
47
(26)
1934
0.59
46
(25)
NA
NA
45
(25)
1299
0.23
43
(24)
1340
0.22
42
(23)
NA
NA
NA
NA
0.2
1229
0.20
45
(25)
0.1
1271
0.19
44
(24)
1617
0.45
35
(19)
54
(30)
1781
0.60
31
(17)
49
(27)
1855
0.62
30
(17)
47
(26)
NA
1240
0.24
45
(25)
NA
1544
0.48
36
(20)
56
(31)
1720
0.62
32
(18)
51
(28)
1778
0.65
31
(17)
49
(27)
NA
1139
0.26
49
(27)
NA
48VG -- A
1576
0.46
35
(20)
55
(31)
1784
0.59
31
(17)
49
(27)
1815
0.64
31
(17)
48
(27)
NA
1191
0.25
47
(26)
NA
1503
0.49
37
(21)
58
(32)
1698
0.63
33
(18)
51
(28)
1737
0.67
32
(18)
50
(28)
NA
1091
0.28
51
(28)
NA
1468
0.51
38
(21)
59
(33)
1655
0.64
34
(19)
53
(29)
1695
0.68
33
(18)
51
(28)
NA
1050
0.29
53
(30)
NA
NA
1532
0.67
36
(20)
57
(32)
1528
0.68
37
(20)
57
(32)
NA
1578
0.67
35
(20)
55
(31)
1606
0.70
35
(19)
54
(30)
NA
1625
0.66
34
(19)
53
(30)
1656
0.70
34
(19)
52
(29)
NA
NA
895
0.32
NA
NA
1
839
0.29
1356
0.55
41
(23)
NA
952
0.31
59
(33)
NA
NA
0.9
887
0.28
1393
0.53
40
(22)
1433
0.52
39
(22)
NA
1001
0.30
56
(31)
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
1177
1121
1066
1027
974
942
0.21
0.23
0.24
0.25
0.26
0.27
47
50
52
54
57
59
(26)
(28)
(29)
(30)
(32)
(33)
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
38
35 - 65oF Low Stage,
35 - 65oF High Stage
48VG(A,N)48130
See notes on page 41.
HEATING RISE
RANGE
UNIT
High4
Black
Orange
Med-High
Pink
Med-Low3
Red
Blue
Low1
Medium2
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
1650
0.44
38
(21)
58
(32)
1837
0.57
NA
52
(29)
1900
0.61
1686
0.42
37
(21)
57
(32)
1854
0.56
NA
52
(29)
1934
0.59
50
(28)
NA
NA
50
(28)
1299
0.23
48
(27)
1340
0.22
47
(26)
NA
NA
NA
NA
0.2
1229
0.20
51
(28)
0.1
1271
0.19
49
(27)
52
(29)
NA
1617
0.45
39
(22)
59
(33)
1781
0.60
35
(20)
54
(30)
1855
0.62
NA
1240
0.24
51
(28)
NA
1576
0.46
40
(22)
61
(34)
1784
0.59
35
(20)
54
(30)
1815
0.64
35
(19)
53
(29)
NA
1191
0.25
53
(29)
NA
1544
0.48
41
(23)
62
(35)
1720
0.62
36
(20)
56
(31)
1778
0.65
35
(20)
54
(30)
NA
1139
0.26
55
(31)
NA
1503
0.49
42
(23)
64
(35)
1698
0.63
37
(20)
56
(31)
1737
0.67
36
(20)
55
(31)
NA
1091
0.28
57
(32)
NA
1468
0.51
43
(24)
65(3
6)
1655
0.64
38
(21)
58
(32)
1695
0.68
37
(21)
57
(31)
NA
1050
0.29
60
(33)
NA
NA
1532
0.67
41
(23)
63
(35)
1528
0.68
41
(23)
63
(35)
NA
1578
0.67
40
(22)
61
(34)
1606
0.70
39
(22)
60
(33)
NA
1625
0.66
39
(21)
59
(33)
1656
0.70
38
(21)
58
(32)
NA
NA
895
0.32
NA
NA
1
839
0.29
1356
0.55
46
(26)
NA
NA
952
0.31
NA
NA
0.9
887
0.28
1393
0.53
45
(25)
1433
0.52
44
(24)
NA
1001
0.30
63
(35)
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
1177
1121
1066
1027
974
942
0.21
0.23
0.24
0.25
0.26
0.27
53
56
59
61
64
NA
(30)
(31)
(33)
(34)
(36)
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
48VG -- A
39
35 - 65oF Low Stage,
35 - 65oF High Stage
48VG(A,N)60090
See notes on page 41.
HEATING RISE
RANGE
UNIT
High
Black
Orange
Med-High2
Pink
Med-Low1
Red
Blue
Low3
Medium4
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
NA
37
(20)
1990
0.63
NA
NA
36
(20)
2020
0.62
NA
NA
52
(29)
1844
0.52
NA
NA
50
(28)
1878
0.50
NA
NA
37
(21)
1956
0.66
NA
36
(20)
35
(20)
48VG -- A
NA
39
(22)
1872
0.69
NA
1066
0.24
40
(22)
63
(35)
1139
0.26
38
(21)
59
(33)
1731
0.56
NA
38
(21)
1912
0.67
NA
1121
0.23
38
(21)
60
(33)
1191
0.25
36
(20)
57
(31)
1762
0.54
1050
0.29
41
(23)
64
(36)
1655
0.59
1091
0.28
39
(22)
62
(34)
1693
0.57
37
(20)
NA
40
(22)
1842
0.70
37
(21)
NA
41
(23)
1802
0.71
NA
NA
NA
NA
974
0.26
44
(25)
1027
0.25
42
(23)
NA
38
(21)
NA
42
(23)
1760
0.73
NA
39
(22)
NA
43
(24)
1719
0.74
NA
NA
41
(23)
NA
44
(24)
1643
0.72
NA
1532
0.63
NA
1570
0.64
NA
1616
0.60
NA
839
0.29
51
(28)
NA
NA
1
-----
895
0.32
48
(27)
NA
887
0.28
48
(27)
NA
NA
0.9
-----
952
0.31
45
(25)
1001
0.30
43
(24)
NA
942
0.27
46
(25)
NA
1177
0.21
36
(20)
57
(32)
1240
0.24
35
(19)
54
(30)
1805
0.53
NA
1229
0.20
35
(19)
55
(30)
1299
0.23
NA
NA
NA
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
703
587
501
449
380
340
0.09
0.09
0.09
0.10
0.11
0.12
61
NA
NA
NA
NA
NA
(34)
0.2
904
0.10
48
(26)
NA
53
(29)
1340
0.22
NA
0.1
1067
0.12
40
(22)
63
(35)
1271
0.19
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
40
30 - 60oF Low Stage,
30 - 60oF High Stage
48VG(A,N)60115
See notes on page 41.
HEATING RISE
RANGE
UNIT
High4
Black
Orange
Med-High2
Pink
Med-Low3
Red
Blue
Low1
Medium
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
1650
0.44
34
(19)
53
(29)
1844
0.52
30
(17)
47
(26)
1900
0.61
1686
0.42
33
(18)
52
(29)
1878
0.50
30
(17)
46
(26)
1934
0.59
46
(25)
NA
NA
45
(25)
1299
0.23
43
(24)
1340
0.22
42
(23)
NA
NA
NA
NA
0.2
1229
0.20
45
(25)
0.1
1271
0.19
44
(24)
1617
0.45
35
(19)
54
(30)
1805
0.53
31
(17)
48
(27)
1855
0.62
30
(17)
47
(26)
NA
1240
0.24
45
(25)
NA
1576
0.46
35
(20)
55
(31)
1762
0.54
32
(18)
49
(27)
1815
0.64
31
(17)
48
(27)
NA
1191
0.25
47
(26)
NA
1544
0.48
36
(20)
56
(31)
1731
0.56
32
(18)
50
(28)
1778
0.65
31
(17)
49
(27)
NA
1139
0.26
49
(27)
NA
1503
0.49
37
(21)
58
(32)
1693
0.57
33
(18)
51
(29)
1737
0.67
32
(18)
50
(28)
NA
1091
0.28
51
(28)
NA
1468
0.51
38
(21)
59
(33)
1655
0.59
34
(19)
53
(29)
1695
0.68
33
(18)
51
(28)
NA
1050
0.29
53
(30)
NA
NA
1532
0.63
36
(20)
57
(32)
1528
0.68
37
(20)
57
(32)
NA
1570
0.64
36
(20)
55
(31)
1606
0.70
35
(19)
54
(30)
NA
1616
0.60
35
(19)
54
(30)
1656
0.70
34
(19)
52
(29)
NA
NA
895
0.32
NA
NA
1
839
0.29
1356
0.55
41
(23)
NA
952
0.31
59
(33)
NA
NA
0.9
887
0.28
1393
0.53
40
(22)
1433
0.52
39
(22)
NA
1001
0.30
56
(31)
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
1177
1121
1066
1027
974
942
0.21
0.23
0.24
0.25
0.26
0.27
47
50
52
54
57
59
(26)
(28)
(29)
(30)
(32)
(33)
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
48VG -- A
41
35 - 65oF Low Stage,
35 - 65oF High Stage
48VG(A,N)60130
High4
Black
Orange
Med-High2
Pink
Med-Low3
Red
Blue
Low1
Medium
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
CFM
BHP
Low Stage Heat Rise oF
(oC)
High Stage Heat Rise oF
(oC)
Notes:
1 Factory-shipped low stage cooling speed
2 Factory-shipped high stage cooling speed
3 Factory-shipped low stage gas heating speed
4 Factory-shipped high stage gas heating speed
Allowable High Stage Enhanced Dehumidification Cooling Speed
”NA” = Not allowed for particular heating speed
HEATING RISE
RANGE
UNIT
1650
0.44
38
(21)
58
(32)
1844
0.52
1686
0.42
37
(21)
57
(32)
1878
0.50
NA
50
(28)
NA
50
(28)
52
(29)
1900
0.61
NA
NA
NA
1299
0.23
48
(27)
1340
0.22
47
(26)
51
(28)
1934
0.59
NA
NA
NA
0.2
1229
0.20
51
(28)
0.1
1271
0.19
49
(27)
52
(29)
NA
1617
0.45
39
(22)
59
(33)
1805
0.53
35
(19)
53
(30)
1855
0.62
NA
1240
0.24
51
(28)
NA
1544
0.48
41
(23)
62
(35)
1731
0.56
36
(20)
55
(31)
1778
0.65
35
(20)
54
(30)
NA
1139
0.26
55
(31)
NA
48VG -- A
1576
0.46
40
(22)
61
(34)
1762
0.54
36
(20)
54
(30)
1815
0.64
35
(19)
53
(29)
NA
1191
0.25
53
(29)
NA
1503
0.49
42
(23)
64
(35)
1693
0.57
37
(21)
57
(31)
1737
0.67
36
(20)
55
(31)
NA
1091
0.28
57
(32)
NA
1468
0.51
43
(24)
65
(36)
1655
0.59
38
(21)
58
(32)
1695
0.68
37
(21)
57
(31)
NA
1050
0.29
60
(33)
NA
NA
1532
0.63
41
(23)
63
(35)
1528
0.68
41
(23)
63
(35)
NA
1570
0.64
40
(22)
61
(34)
1606
0.70
39
(22)
60
(33)
NA
1616
0.60
39
(22)
59
(33)
1656
0.70
38
(21)
58
(32)
NA
NA
895
0.32
NA
NA
1
839
0.29
1356
0.55
46
(26)
NA
NA
952
0.31
NA
NA
0.9
887
0.28
1393
0.53
45
(25)
1433
0.52
44
(24)
NA
1001
0.30
63
(35)
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
1177
1121
1066
1027
974
942
0.21
0.23
0.24
0.25
0.26
0.27
53
56
59
61
64
NA
(30)
(31)
(33)
(34)
(36)
DRY COIL AIR DELIVERY* -- HORIZONTAL AND DOWNFLOW DISCHARGE - UNIT 48VG--A 208/230 VAC MODELS (CONT)
42
See notes on page 46.
35 - 65oF
25 - 55oF
48VG(A,N)36060
48VG(A,N)36090
HEATING RISE
RANGE
UNIT
WIRE
COLOR
Blue
Pink
Red
Orange
Black
Blue
Pink
Red
Orange
Black
MOTOR
SPEED
Low1
Med-Low
Medium3
Med-High2
High
Low1
Med-Low
Medium
Med-High2
High3
BHP
0.29
47
(26)
BHP
Heat Rise oF
(oC)
48
(27)
0.30
50
(28)
0.31
NA
51
(28)
0.32
1065
0.19
64
(35)
1104
0.23
62
(34)
1327
NA
1110
0.17
61
(34)
1149
0.21
59
(33)
1372
NA
1169
0.17
58
(32)
1198
0.21
57
(32)
1415
NA
918
0.15
NA
NA
NA
NA
1212
NA
1249
54
(30)
0.35
970
0.26
1017
0.25
1066
0.24
64
(35)
1287
248.5
9
53
(29)
56
(31)
0.36
NA
NA
NA
923
0.22
NA
771
0.18
964
0.21
NA
827
0.18
1016
0.20
NA
872
0.17
NA
58
(32)
0.37
1168
NA
932
0.27
NA
878
0.23
NA
714
0.20
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
810
745
698
649
571
525
0.11
0.12
0.13
0.14
0.14
0.15
55
NA
NA
NA
NA
NA
(30)
972
918
872
827
771
714
0.15
0.15
0.17
0.18
0.18
0.20
46
48
51
54
NA
NA
(25)
(27)
(28)
(30)
1110 1065
1016
964
923
878
0.17
0.19
0.20
0.21
0.22
0.23
40
42
44
46
48
51
(22)
(23)
(24)
(26)
(27)
(28)
1149 1104
1066
1017
970
932
0.21
0.23
0.24
0.25
0.26
0.27
39
40
42
44
46
48
(21)
(22)
(23)
(24)
(25)
(26)
1372 1327
1287
1249 1212
1168
248.5
0.31
0.32
0.35
0.36
0.37
9
32
33
35
36
37
38
(18)
(19)
(19)
(20)
(20)
(21)
810
745
698
649
571
525
0.11
0.12
0.13
0.14
0.14
0.15
972
0.15
NA
1026
0.14
NA
1076
0.13
63
(35)
1213
0.16
56
(31)
1251
0.19
54
(30)
1451
31
(17)
864
0.10
0.30
0.2
864
0.10
51
(29)
1026
0.14
43
(24)
1169
0.17
38
(21)
1198
0.21
37
(21)
1415
Heat Rise
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
31
(17)
934
0.10
0.29
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
oF
0.1
934
0.10
48
(26)
1076
0.13
41
(23)
1213
0.16
37
(20)
1251
0.19
36
(20)
1451
DRY COIL AIR DELIVERY -- HORIZONTAL AND DOWNFLOW DISCHARGE - 48VG--A 460 VAC MODELS
48VG -- A
60
(33)
0.38
1130
NA
892
0.28
NA
820
0.24
NA
666
0.21
NA
39
(22)
486
0.16
0.38
62
(35)
0.39
1094
NA
839
0.29
NA
777
0.25
NA
611
0.22
NA
41
(23)
428
0.17
0.39
839
0.29
53
(29)
1094
NA
NA
777
0.25
611
0.22
666
0.21
NA
NA
NA
820
0.24
54
(30)
892
0.28
50
(28)
1130
1
428
0.17
0.9
486
0.16
43
See notes on page 46.
48VG(A,N)42090
48VG(A,N)42060
35 - 65oF
25 - 55oF
Orange
Black
High3
Blue
Low1
Med-High2
Black
High
Red
Orange
Med-High2
Medium
Red
Medium3
Pink
Pink
Med-Low
Med-Low
Blue
Low1
Heat Rise
(oC)
CFM
BHP
Heat Rise oF
(oC)
47
(26)
1633
0.41
42
(23)
0.29
BHP
48
(27)
1590
0.43
43
(24)
50
(28)
1552
0.44
44
(24)
0.31
1110
0.17
61
(34)
1149
0.21
59
(33)
1372
1169
0.17
58
(32)
1198
0.21
57
(32)
1415
0.30
NA
NA
oF
1552
0.44
29
(16)
972
0.15
1590
0.43
28
(16)
1026
0.14
1633
0.41
27
(15)
1076
0.13
63
(35)
1213
0.16
56
(31)
1251
0.19
54
(30)
1451
32
(18)
0.31
31
(17)
0.30
972
0.15
46
(25)
1110
0.17
40
(22)
1149
0.21
39
(21)
1372
31
(17)
0.29
BHP
1026
0.14
43
(24)
1169
0.17
38
(21)
1198
0.21
37
(21)
1415
High Stage
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise
oF(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
1076
0.13
41
(23)
1213
0.16
37
(20)
1251
0.19
36
(20)
1451
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
51
(28)
1518
0.45
45
(25)
0.32
1065
0.19
64
(35)
1104
0.23
62
(34)
1327
NA
1518
0.45
29
(16)
918
0.15
33
(19)
0.32
918
0.15
48
(27)
1065
0.19
42
(23)
1104
0.23
40
(22)
1327
48VG -- A
54
(30)
1444
0.48
47
(26)
0.35
56
(31)
1406
0.49
48
(27)
0.36
NA
58
(32)
1372
0.50
50
(28)
0.37
1168
NA
1212
NA
NA
1249
1017
0.25
1066
0.24
64
(35)
1287
248.5
9
53
(29)
1483
0.47
46
(25)
NA
878
0.23
NA
1372
0.50
32(18
)
714
0.20
38
(21)
0.37
932
0.27
NA
NA
923
0.22
NA
1406
0.49
32
(18)
771
0.18
37
(20)
0.36
NA
NA
878
0.23
51
(28)
932
0.27
48
(26)
1168
NA
923
0.22
48
(27)
970
0.26
46
(25)
1212
60
(33)
1340
0.51
51
(28)
0.38
1130
NA
892
0.28
NA
820
0.24
NA
1340
0.51
33
(18)
666
0.21
39
(22)
0.38
820
0.24
54
(30)
892
0.28
50
(28)
1130
666
0.21
714
0.20
771
0.18
970
0.26
964
0.21
NA
1444
0.48
31
(17)
827
0.18
36
(20)
0.35
827
0.18
54
(30)
964
0.21
46
(26)
1017
0.25
44
(24)
1249
1016
0.20
NA
1483
0.47
30
(17)
872
0.17
35
(19)
872
0.17
51
(28)
1016
0.20
44
(24)
1066
0.24
42
(23)
1287
248.5
9
DRY COIL AIR DELIVERY -- HORIZONTAL AND DOWNFLOW DISCHARGE - 48VG--A 460 VAC MODELS
62
(35)
1303
0.53
52
(29)
0.39
1094
NA
839
0.29
NA
777
0.25
NA
1303
0.53
34
(19)
611
0.22
41
(23)
0.39
839
0.29
53
(29)
1094
NA
777
0.25
NA
611
0.22
44
See notes on page 46.
30 - 60oF
35 - 65oF
48VG(A,N)48090
48VG(A,N)48115
HEATING RISE
RANGE
UNIT
Blue
Low1
Red
Orange
Black
Medium2
Med-High
High3
Pink
Black
High
Med-Low
Orange
Med-High
Pink
Med-Low3
Red
Blue
Low1
Medium2
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
1341
0.26
NA
1617
0.45
53
(30)
1781
0.60
48
(27)
2065
0.75
42
(23)
NA
1229
0.20
NA
1389
0.26
NA
1650
0.44
52
(29)
1837
0.57
47
(26)
2088
0.74
41
(23)
NA
1271
0.19
NA
1445
0.24
60
(33)
1686
0.42
51
(28)
1854
0.56
47
(26)
2131
0.72
40
(22)
NA
0.2
1229
0.20
55
(31)
1389
0.26
49
(27)
1650
0.44
41
(23)
1837
0.57
37
(21)
2088
0.74
0.1
1271
0.19
54
(30)
1445
0.24
47
(26)
1686
0.42
40
(22)
1854
0.56
37
(20)
2131
0.72
1576
0.46
55
(30)
1784
0.59
48
(27)
2013
0.77
43
(24)
NA
1281
0.28
NA
1544
0.48
56
(31)
1720
0.62
50
(28)
1982
0.79
44
(24)
NA
1236
0.29
NA
1503
0.49
57
(32)
1698
0.63
51
(28)
1941
0.8
45
(25)
NA
1189
0.3
NA
1468
0.51
59
(33)
1655
0.64
52
(29)
1888
0.81
46
(25)
NA
1139
0.32
NA
1433
0.52
60
(33)
1625
0.66
53
(29)
1860
0.81
46
(26)
NA
1072
0.33
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
1177 1121
1066
1027
974
942
0.21
0.23
0.24
0.25
0.26
0.27
58
61
64
NA
NA
NA
(32)
(34)
(35)
1341 1281
1236
1189 1139
1072
0.26
0.28
0.29
0.3
0.32
0.33
51
53
55
57
60
63
(28)
(29)
(31)
(32)
(33)
(35)
1617 1576
1544
1503 1468
1433
0.45
0.46
0.48
0.49
0.51
0.52
42
43
44
45
46
47
(23)
(24)
(24)
(25)
(26)
(26)
1781 1784
1720
1698 1655
1625
0.60
0.59
0.62
0.63
0.64
0.66
38
38
40
40
41
42
(21)
(21)
(22)
(22)
(23)
(23)
2065 2013
1982
1941 1888
1860
0.75
0.77
0.79
0.8
0.81
0.81
35
36
37
NA
NA
NA
(19)
(20)
(20)
1177 1121
1066
1027
974
942
0.21
0.23
0.24
0.25
0.26
0.27
DRY COIL AIR DELIVERY -- HORIZONTAL AND DOWNFLOW DISCHARGE - 48VG--A 460 VAC MODELS
48VG -- A
NA
1532
0.67
56
(31)
1751
0.75
49
(27)
NA
1356
0.55
NA
982
0.35
NA
1578
0.67
55
(30)
1785
0.79
48
(27)
1393
0.53
NA
1027
0.34
NA
NA
1356
0.55
50
(28)
1532
0.67
44
(25)
1751
0.75
39
(22)
839
0.29
982
0.35
1027
0.34
NA
NA
NA
1393
0.53
49
(27)
1578
0.67
43
(24)
1785
0.79
38
(21)
887
0.28
1
839
0.29
0.9
887
0.28
45
See notes on page 46.
35 - 65oF
35 - 65oF
48VG(A,N)48130
48VG(A,N)60090
HEATING RISE
RANGE
UNIT
Blue
Low1
Red
Orange
Black
Medium2
Med-High
High
Pink
Black
High3
Med-Low3
Orange
Med-High
Pink
Med-Low
Red
Blue
Low1
Medium2
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
NA
2088
0.74
NA
NA
NA
1650
0.44
58
(32)
1837
0.57
52
(29)
2088
0.74
46
(26)
1229
0.20
55
(31)
1389
0.26
49
(27)
1844
0.52
37
(20)
1990
0.63
NA
1686
0.42
57
(32)
1854
0.56
52
(29)
2131
0.72
45
(25)
1271
0.19
54
(30)
1445
0.24
47
(26)
1878
0.50
36
(20)
2020
0.62
NA
NA
1389
0.26
1445
0.24
2131
0.72
1341
0.26
NA
NA
NA
1617
0.45
60
(33)
1781
0.60
54
(30)
2065
0.75
47
(26)
1177
0.21
58
(32)
1341
0.26
51
(28)
1805
0.53
38
(21)
1956
0.66
35
(19)
2065
0.75
NA
0.2
1229
0.20
0.1
1271
0.19
NA
1576
0.46
61
(34)
1784
0.59
54
(30)
2013
0.77
48
(27)
1121
0.23
61
(34)
1281
0.28
53
(29)
1762
0.54
39
(21)
1912
0.67
36
(20)
2013
0.77
NA
1281
0.28
NA
1139
0.32
60
(33)
1655
0.59
41
(23)
1802
0.71
38
(21)
1888
0.81
36
(20)
1189
0.3
57
(32)
1693
0.57
40
(22)
1842
0.70
37
(21)
1941
0.8
35
(19)
1072
0.33
63
(35)
1616
0.60
42
(23)
1760
0.73
39
(21)
1860
0.81
37
(20)
NA
NA
NA
982
0.35
NA
1532
0.63
44
(25)
1643
0.72
41
(23)
1751
0.75
39
(22)
NA
1570
0.64
43
(24)
1719
0.74
40
(22)
1785
0.79
38
(21)
NA
1532
0.67
63
(35)
1751
0.75
55
(31)
839
0.29
NA
1356
0.55
NA
982
0.35
NA
1
839
0.29
1027
0.34
NA
1578
0.67
61
(34)
1785
0.79
54
(30)
887
0.28
NA
NA
1625
0.66
59
(33)
1860
0.81
52
(29)
942
0.27
NA
1393
0.53
NA
1027
0.34
NA
0.9
887
0.28
1433
0.52
NA
1072
0.33
NA
1655
0.64
58
(32)
1888
0.81
51
(28)
974
0.26
1468
0.51
NA
1139
0.32
NA
1503
0.49
64
(36)
1698
0.63
57
(32)
1941
0.8
50
(28)
1027
0.25
NA
1189
0.3
NA
48VG -- A
NA
1544
0.48
62
(35)
1720
0.62
56
(31)
1982
0.79
49
(27)
1066
0.24
64
(35)
1236
0.29
55
(31)
1731
0.56
39
(22)
1872
0.69
36
(20)
1982
0.79
NA
1236
0.29
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
1177 1121
1066
1027
974
942
0.21
0.23
0.24
0.25
0.26
0.27
DRY COIL AIR DELIVERY -- HORIZONTAL AND DOWNFLOW DISCHARGE - 48VG--A 460 VAC MODELS
46
Notes:
1 Factory-shipped low stage cooling speed
2 Factory-shipped high stage cooling speed
3 Factory-shipped low gas heating speed
”NA” = Not allowed for particular heating speed
35 - 65oF
30 - 60oF
48VG(A,N)60115
48VG(A,N)60130
HEATING RISE
RANGE
UNIT
Blue
Low1
Red
Orange
Black
Medium2
Med-High
High3
Pink
Black
High3
Med-Low
Orange
Med-High
Pink
Med-Low
Red
Blue
Low1
Medium2
WIRE
COLOR
MOTOR
SPEED
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
CFM
BHP
Heat Rise oF
(oC)
NA
1389
0.26
NA
1844
0.52
52
(29)
1990
0.63
48
(27)
2088
0.74
46
(26)
NA
1445
0.24
NA
1878
0.50
51
(28)
2020
0.62
48
(26)
2131
0.72
45
(25)
1805
0.53
53
(30)
1956
0.66
49
(27)
2065
0.75
47
(26)
NA
1341
0.26
NA
NA
1762
0.54
55
(30)
1912
0.67
50
(28)
2013
0.77
48
(27)
NA
1281
0.28
NA
1762
0.54
49
(27)
1912
0.67
45
(25)
2013
0.77
43
(24)
1121
0.23
NA
1805
0.53
48
(27)
1956
0.66
44
(24)
2065
0.75
42
(23)
1177
0.21
NA
NA
1844
0.52
47
(26)
1990
0.63
43
(24)
2088
0.74
41
(23)
1229
0.20
1389
0.26
1445
0.24
60
(33)
1878
0.50
46
(26)
2020
0.62
43
(24)
2131
0.72
40
(22)
1271
0.19
NA
1281
0.28
NA
NA
1731
0.56
56
(31)
1872
0.69
51
(29)
1982
0.79
49
(27)
NA
1236
0.29
NA
1731
0.56
50
(28)
1872
0.69
46
(26)
1982
0.79
44
(24)
1066
0.24
NA
1236
0.29
NA
1693
0.57
57
(32)
1842
0.70
52
(29)
1941
0.8
50
(28)
NA
1189
0.3
NA
1693
0.57
51
(28)
1842
0.70
47
(26)
1941
0.8
44
(25)
1027
0.25
NA
1189
0.3
NA
1655
0.59
58
(32)
1802
0.71
53
(30)
1888
0.81
51
(28)
NA
1139
0.32
NA
1655
0.59
52
(29)
1802
0.71
48
(27)
1888
0.81
46
(25)
974
0.26
NA
1139
0.32
NA
1616
0.60
60
(33)
1760
0.73
55
(30)
1860
0.81
52
(29)
NA
1072
0.33
NA
1616
0.60
53
(30)
1760
0.73
49
(27)
1860
0.81
46
(26)
942
0.27
NA
1072
0.33
NA
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.3
0.4
0.5
0.6
0.7
0.8
1177 1121
1066
1027
974
942
0.21
0.23
0.24
0.25
0.26
0.27
1341
0.26
0.2
1229
0.20
0.1
1271
0.19
DRY COIL AIR DELIVERY -- HORIZONTAL AND DOWNFLOW DISCHARGE - 48VG--A 460 VAC MODELS
48VG -- A
1570
0.64
61
(34)
1719
0.74
56
(31)
1785
0.79
54
(30)
NA
1027
0.34
NA
1570
0.64
55
(31)
1719
0.74
50
(28)
1785
0.79
48
(27)
887
0.28
NA
1027
0.34
NA
0.9
887
0.28
1532
0.63
63
(35)
1643
0.72
59
(33)
1751
0.75
55
(31)
NA
982
0.35
NA
1532
0.63
56
(31)
1643
0.72
52
(29)
1751
0.75
49
(27)
839
0.29
NA
982
0.35
NA
1
839
0.29
47
600
0.03
700
0.04
800
0.04
900
0.05
0.05
0.06
--
--
0.04
700
1000
0.06
0.06
0.06
0.05
--
--
0.05
800
1500-2200 CFM
16x24x1+18x24x1
(406x610x25+457x356x25)
600-1400 CFM
12x20x1+12x20x1
(305x508x25+305x508x25)
1200-1800 CFM
16x24x1+14x24x1
(406x610x25+356x610x25)
FILTER SIZE IN. (MM)
--
--
3.0
3.5,
4.0
5.0
--
600
2.0,
2.5,
COOLING
TONS
--
--
--
700
--
--
0.08
800
Economizer with 1--in. Filter Pressure Drop (IN. W.C.)
UNIT
SIZE
24
30
36
42
48
60
--
--
3.0
3.5,
4.0
5.0
0.03
600
2.0,
2.5,
COOLING
TONS
Wet Coil Pressure Drop (IN. W.C.)
1500-2200 CFM
16x24x1+18x24x1
(406x610x25+457x356x25)
600-1400 CFM
12x20x1+12x20x1
(305x508x25+305x508x25)
1200-1800 CFM
16x24x1+14x24x1
(406x610x25+356x610x25)
FILTER SIZE IN. (MM)
Filter Pressure Drop Table (IN. W.C.)
--
--
0.09
--
--
0.10
--
0.05
0.07
1100
--
0.09
0.11
1100
0.08
0.10
0.06
0.04
0.07
0.09
0.05
900
1200
1000
--
0.04
0.06
1000
1100
--
--
0.06
900
--
0.07
0.08
--
0.08
0.08
--
0.09
0.11
1200
0.11
0.11
0.07
0.06
0.08
0.10
0.06
0.09
0.10
0.07
0.09
0.11
0.01
1700
0.06
0.09
--
1600
--
0.10
0.13
--
0.12
0.14
0.15
0.13
--
0.18
0.17
--
1700
0.11
0.12
0.08
1800
0.08
0.10
--
1700
48VG -- A
0.17
0.15
--
STANDARD CFM (SCFM)
1300
1400
1500
1600
0.14
0.08
0.09
1600
0.04
0.09
--
STANDARD CFM (SCFM)
1300
1400
1500
STANDARD CFM (SCFM)
1300
1400
1500
--
0.06
0.07
1200
0.20
0.17
--
1800
0.10
0.11
--
1800
0.21
0.19
--
1900
0.13
0.09
1900
0.11
0.12
--
1900
0.22
0.21
--
2000
0.14
0.10
2000
0.13
0.12
--
2000
0.23
--
--
2100
0.12
2100
0.14
--
--
2100
0.23
--
--
2200
0.13
2200
0.15
--
--
2200
TYPICAL PIPING AND WIRING
ROOF-MOUNTING
CURB
ROOF
RETURN-AIR
FLEXIBLE DUCT
48VG -- A
SUPPLY-AIR
FLEXIBLE DUCT
CEILING
CONCENTRIC DIFFUSER BOX
(FIELD-SUPPLIED)
A09233
INDOOR
THERMOSTAT
RETURN
AIR
FROM
POWER
SOURCE
TOP COVER
DISCONNECT
PER NEC*
FROM
GAS LINE
*NEC - NATIONAL ELECTRICAL CODE
A09234
48
Condensate trap — A 2--in. (50.8 mm) condensate trap must be
field supplied.
Ductwork — Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit with
flanges.
To convert a unit to downflow discharge — Units are equipped
with factory--installed inserts in the down--flow openings. Removal
of the inserts is similar to removing an electrical knock--out. Use
the duct cover to seal the horizontal discharge openings in the unit.
Units installed in horizontal discharge orientation do not require
duct covers.
Airflow — Units are draw--thru in the cooling mode and
blow--thru in the heating mode.
Maximum cooling airflow — To minimize the possibility of
condensate blow--off from the evaporator, airflow through the units
should not exceed 450 cfm per ton.
Minimum cooling airflow — Minimum cooling airflow is 350
cfm per ton.
Minimum ambient cooling operation temperature — All
standard units have a minimum ambient operating temperature of
40_F (4_C). With accessory low ambient temperature kit, units can
operate at temperatures down to 0_F (--17_C).
Minimum temperature — Air entering the heat exchanger in
heating mode must be a minimum of 55_F (13_C) continuous and
a maximum of 80_F (27_C) continuous.
48VG -- A
APPLICATION DATA
49
ELECTRICAL DATA
48VG -- A
UNIT
NOMINAL
VOLTAGE
RANGE
COMPRESSOR
OFM
IFM
IDM
MIN
MAX
RLA
LRA
FLA
FLA
FLA
POWER SUPPLY
MCA
MOCP
48VG(--- ,N)A2404030
48VG(--- ,N)A2406030
208/230-1-60
197
253
11.7
58.3
0.7
4.1
.21
19.4
30
48VG(--- ,N)A3004030
48VG(--- ,N)A3006030
208/230-1-60
197
253
13.1
73.0
1.2
4.1
.21
21.7
30
48VG(--- ,N)A3004050
48VG(--- ,N)A3006050
208/230-3-60
197
253
8.7
58.0
1.2
4.1
.21
16.2
20
48VG(--- ,N)A3606030
48VG(--- ,N)A3609030
208/230-1-60
197
253
15.3
83.0
1.2
6.0
.21
26.3
40
48VG(--- ,N)A3606050
48VG(--- ,N)A3609050
208/230-3-60
197
253
11.6
73.0
1.2
6.0
.21
21.7
30
460-3-60
414
506
5.7
38.0
0.53
3.2
10.8
15
48VG(--- ,N)A4206030
48VG(--- ,N)A4209030
208/230-1-60
197
253
17.9
96.0
1.2
6.0
.21
29.6
45
48VG(--- ,N)A4206050
48VG(--- ,N)A4209050
208/230-3-60
197
253
14.2
88.0
1.2
6.0
.21
25.0
35
460-3-60
414
506
6.2
44.0
0.53
3.2
11.5
15
35.3
50
26.3
40
12.5
15
44.8
60
29.1
40
14.0
20
48VG(--- ,N)A3606060
48VG(--- ,N)A3609060
48VG(--- ,N)A4206060
48VG(--- ,N)A4209060
48VG(--- ,N)A4809030
48VG(--- ,N)A4811530
.65
.33
.65
.33
.21
208/230-1-60
197
253
21.2
104.0
1.2
7.6
.50
48VG(--- ,N)A4813030
.50
48VG(--- ,N)A4809050
.21
48VG(--- ,N)A4811550
208/230-3-60
197
253
14.0
83.1
1.2
7.6
.50
48VG(--- ,N)A4813050
.50
48VG(--- ,N)A4809060
.33
48VG(--- ,N)A4811560
460-3-60
414
506
6.4
41.0
0.53
4.0
.65
48VG(--- ,N)A4813060
.30
48VG(--- ,N)A6009030
.21
48VG(--- ,N)A6011530
208/230-1-60
197
253
28.8
152.9
1.2
7.6
.50
48VG(--- ,N)A6013030
.50
48VG(--- ,N)A6009050
.21
48VG(--- ,N)A6011550
208/230-3-60
197
253
16.2
110.0
1.2
7.6
.50
48VG(--- ,N)A6013050
.50
48VG(--- ,N)A6009060
.33
48VG(--- ,N)A6011560
460-3-60
414
506
7.6
52.0
48VG(--- ,N)A6013060
.053
4.0
.65
.30
50
ELECTRICAL DATA (CONT)
LEGEND
48VG -- A
FLA - Full Load Amps
IDM - Inducer Motor
IFM - Indoor Fan Motor
LRA -Locked Rotor Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Over Current Protection
OFM - Outdoor Fan Motor
RLA - Rated Load Amps
51
48VG -- A
CONNECTION WIRING SCHEMATIC GAS INPUTS 40, 60 ,90 KBTU/HR 208/230--1--60
A13018
52
48VG -- A
LADDER WIRING SCHEMATIC GAS INPUTS 40, 60 90 KBTU/HR 208/230--1--60
A13019
53
48VG -- A
CONNECTION WIRING SCHEMATIC GAS INPUTS 115, 130 KBTU/HR 208/230--1--60
A13020
54
48VG -- A
LADDER WIRING SCHEMATIC GAS INPUTS 115, 130 KBTU/HR 208/230--1--60
A13021
55
48VG -- A
CONNECTION WIRING SCHEMATIC GAS INPUTS 40, 60, 90 KBTU/HR 208/230--3--60
A13022
56
48VG -- A
LADDER WIRING SCHEMATIC GAS INPUTS 40, 60, 90 KBTU/HR 208/230--3--60
A13023
57
48VG -- A
CONNECTION WIRING SCHEMATIC GAS INPUTS 115, 130 208/230--3--60
A13024
58
48VG -- A
LADDER WIRING SCHEMATIC GAS INPUTS 115, 130 208/230--3--60
A13025
59
48VG -- A
CONNECTION WIRING SCHEMATIC 460--3--60
A13026
60
48VG -- A
LADDER WIRING DIAGRAM 460--3--60
A13027
61
CONTROLS
48VG -- A
Operating sequence
208/230 VAC Models:
On a call for low stage heating, terminal W1 on the thermostat is
energized. On a call for high stage heating both terminals W1 and
W2 are energized. Regardless of the stage of the heating call, the
induced--draft motor is turned on to high speed for a 15 sec
pre--purge time. After the pre--purge, when the pressure switch
senses that sufficient combustion air is being moved by the
induced--draft motor, the ignition sequence begins. The IGC will
energize the sparker and the low stage gas valve solenoid. Upon
sensing flame, the IGC will check the heating call. If W2 is not
energized, the IGC will drop the induced--draft motor to low speed
and maintain the gas valve on low stage. If W2 is energized, the
IGC will maintain the induced--draft motor on high speed and
energize the high stage gas valve solenoid. Thirty sec after flame is
sensed the IGC will turn on the evaporator fan motor. If W2 is not
energized, the evaporator fan motor will run on low heat speed. If
W2 is energized, the evaporator fan motor will run on high heat
speed. After the call for heat is satisfied, the IGC will run the
evaporator fan motor an additional field--selectable time of 90, 120,
150, or 180 sec before shutting the evaporator fan motor off.
460 VAC Models:
On a call for heating, terminal W of the thermostat is energized,
starting the induced--draft motor. When the pressure switch senses
that the induced--draft motor is moving sufficient combustion air,
the ignition sequence begins. This function is performed by the
integrated gas unit controller (IGC). The indoor (evaporator)--fan
motor is energized 45 sec after flame is established. When the
thermostat is satisfied and W is de--energized, the burners stop
firing and the indoor (evaporator) fan motor shuts off after a
45--sec time--off delay. Please note that the IGC has the capability
to automatically reduce the indoor fan motor on delay and increase
the indoor fan motor off delay in the event of high duct static
and/or partially--clogged filter.
Cooling — When the system thermostat calls for cooling, 24 V is
supplied to the “Y1/Y” and “G” terminals of the thermostat. This
completes the circuit to the contactor coil (C) and indoor
(evaporator) fan relay (IFR). The normally open contacts of
energized C close and complete the circuit through compressor
motor (COMP) to outdoor (condenser) fan motor (OFM). Both
motors start instantly. The set of normally open contacts of
energized IFR close and complete the circuit through IFM. The
IFM starts instantly.
On the loss of the thermostat call for cooling, 24 V is removed
from both the “Y1/Y” and “G” terminals (provided the fan switch
is in the “AUTO” position) de--energizing the compressor
contactor and opening the contacts supplying power to
compressor/OFM. After a 60--second delay, the IFM shuts off. If
the thermostat fan selector switch is in the “ON” position, the IFM
will run continuously.
NOTE: On units with a Time Guard II device: Once the
compressor has started and then stopped, it cannot be restarted
again until 5 minutes have elapsed.
62
Packaged Gas Heating/Electric Cooling Units
Constant Volume Application
HVAC Guide Specifications
Size Range:
2 to 5 Tons, Nominal Cooling
40,000 to 130,000 Btuh,
Nominal Heating Input
Model Number: 48VG--A
Part 1 — General
SYSTEM DESCRIPTION
Outdoor rooftop or ground mounted air conditioner and gas
furnace system utilizing a two--stage scroll compressor for cooling duty. Unit shall discharge supply air vertically or horizontally
as shown on contract drawings. Outdoor fan/coil section shall
have a draw--thru design with vertical discharge for minimum
sound levels.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with AHRI Standards
210/240 and 270.
B. Unit shall be designed in accordance with UL Standard 1995
and ANSI Z 21.47.
C. Unit shall be manufactured in a facility registered to ISO 9001
manufacturing quality standard.
D. Unit shall be UL listed and c--UL certified as a total package
for safety requirements.
E. Roof curb shall be designed to conform to NRCA Standards.
F. Insulation and adhesives shall meet NFPA 90.1 requirements
for flame spread and smoke generation.
G. Cabinet insulation shall meet ASHRAE Standard 62.2.
DELIVERY, STORAGE AND HANDLING
Unit shall be stored and handled per manufacturer’s
recommendations.
Part 2 — Products
EQUIPMENT
A. General:
Factory--assembled, single--piece, heating and cooling unit.
Contained within the enclosure shall be all factory wiring, piping,
controls, refrigerant charge with R--410A refrigerant, and special
features required prior to field start--up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of phosphated,
zinc--coated, pre--painted steel capable of with--standing 500
hours in salt spray.
2. Normal service shall be through 3 removable cabinet
panels.
3. The unit shall be constructed on a rust proof unit base that
has an externally trapped, integrated sloped drain.
4. Evaporator fan compartment top surface shall be insulated
with a minimum 1/2--in. (12.7 mm) thick, flexible
fiberglass insulation, coated on the air side and retained by
adhesive and mechanical means. The evaporator wall
sections will be insulated with a minimum semi--rigid foil-faced board capable of being wiped clean. Aluminum foil-faced fiberglass insulation shall be used in the entire indoor
air cavity section.
5. Unit shall have a field--supplied condensate trap.
C. Fans:
1. The evaporator fan shall be a multi--speed, direct--drive, as
shown on equipment drawings.
2. Fan wheel shall be made from steel, be double--inlet type
with forward curved blades with corrosion resistant finish.
Fan wheel shall be dynamically balanced.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
63
3. Condenser fan shall be direct drive propeller type with aluminum blades riveted to corrosion resistant steel spiders, be
dynamically balanced, and discharge air vertically.
Compressor:
1. Fully hermetic compressors with factory--installed vibration
isolation.
2. Two--stage scroll compressors shall be standard on all units.
Coils:
Evaporator and condenser coils shall have aluminum plate fins
mechanically bonded to seamless copper tubes with all joints
brazed. Tube sheet openings shall be belled to prevent tube
wear.
Heating Section:
1. Induced--draft combustion type with energy saving direct
spark ignition system and redundant main gas valve.
2. Induced--draft motors shall provide adequate airflow for
combustion.
3. The heat exchangers shall be constructed of aluminized steel
for corrosion resistance.
4. Burners shall be of the in--shot type constructed of
aluminum coated steel.
5. All gas piping and electric power shall enter the unit cabinet
at a single location.
Refrigerant Components:
Refrigerant expansion device shall be of the TXV
(thermostatic expansion valve) type.
Filters:
Filter section shall consist of field--installed, throwaway, 1--in.
(25 mm) thick fiberglass filters of commercially available
sizes.
Controls and Safeties:
1. Unit controls shall be complete with a self--contained low
voltage control circuit.
2. Compressors shall incorporate a solid--state compressor
protector that provides reset capability.
Operating Characteristics:
1. Unit shall be capable of starting and running at 125_F
(51_C) ambient outdoor temperature per maximum load
criteria of AHRI Standard 210.
2. Compressor with standard controls shall be capable of operation down to 40_F (4_C) ambient outdoor temperature.
3. Units shall be provided with fan time delay to prevent cold
air delivery before the heat exchanger warms up.
4. Unit shall be provided with 90--second fan time delay after
the thermostat is satisfied.
Electrical Requirements:
All unit power wiring shall enter the unit cabinet at a single
location.
Motors:
1. Compressor motors shall be of the refrigerant--cooled type
with line--break thermal and current overload protection.
2. All fan motors shall have permanently lubricated bearings,
and inherent, automatic reset, thermal overload protection.
3. Condenser fan motor shall be totally enclosed.
4. Evaporator Fan Motor to be multi--speed ECM blower motor.
Compressor Protection:
Solid--state control shall protect compressor by preventing
“short cycling.”
48VG -- A
GUIDE SPECIFICATIONS
48VG -- A
GUIDE SPECIFICATIONS (CONT)
N. Low NOx:
Shall provide NOx reduction to values below 40 nanograms/
joule to meet California’s and other localities’ emission requirements as shipped from factory.
O. Special Option/Kits Available:
1. Coil Options
Base unit with tin plated indoor coil hairpins available as a
factory installed option.
2. Compressor Start Kit (single phase units only):
Shall provide additional starting torque for single--phase
compressors.
3. Corporate Thermostat:
To provide for one--stage heating and cooling in addition
manual or automatic changeover and indoor fan control.
4. Crankcase Heater Kit:
Shall provide anti--floodback protection for low--load cooling applications.
5. Economizer for two--stage operation:
(Horizontal and Vertical with Jade Honeywell W7220 controller, Honeywell communicating actuator, and dry bulb
sensor. (Contact MicroMetl Customer Service at
1--800--662--4822 to order.)
NOTE: The enhanced dehumidification feature on high
stage cooling does not support use of an economizer.
a. Economizer controls capable of providing free cooling
using outside air.
b. Equipped with low leakage dampers not to exceed 3%
leakage, at 1.0 IN. W.C. pressure differential.
c. Spring return motor shuts off outdoor damper on power
failure.
6. Filter Rack Option or Kit:
Shall provide filter mounting for downflow applications.
Offered as an accessory or as a factory installed option.
Copyright 2013 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
7. Flat Roof Curb Kit:
Curbs shall have seal strip and a wood nailer for flashing
and shall be installed per manufacturer’s instructions.
8. Flue Discharge Deflector Kit
Directs flue gas exhaust; 90 degrees upward from current
discharge.
9. Heat Exchanger Option
Stainless Steel Heat Exchanger available as a factory
installed option.
10. High Altitude Propane Conversion Kit:
Shall consist of all required hardware to convert to propane
gas heat operation at 2001 to 6000 ft (611 to 1829 m) above
sea level.
11. Low Ambient Package Kit:
Shall consist of a solid--state control and condenser coil
temperature sensor for controlling condenser--fan motor operation, which shall allow unit to operate down to 0_F
(--18_C) outdoor ambient temperature when properly
installed.
12. Manual Outdoor Air Damper Kit:
Package shall consist of damper, birdscreen, and rainhood
which can be preset to admit outdoor air for year--round
ventilation.
13. Natural--to--Propane Conversion Kit:
Shall be complete with all required hardware to convert to
propane gas operation at 10.0 IN. W.C. manifold pressure.
14. Propane--to--Natural Conversion Kit
Shall be complete with all hardware to convert to natural
gas at standard altitude (0 to 2000 ft [0 to 610 m] above sea
level).
15. Square--To--Round Duct Transitions Kit (24--48 models):
Shall have the ability to convert the supply and return openings from rectangular to round.
Edition Date: 03/13
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
64
Catalog No: 48VG ---01PD
Replaces: NEW