a Supply and fixing of 4nos. 6A sockets with 1 no 16A switch fixed on a

TENDER SCHEDULE FOR URUMADLA : ELECTRICAL WORKS
DESCRIPTION
QTY
UNIT
RATE
No.
1
MODULAR SOCKETS:
a Supply and fixing of 4nos. 6A sockets with 1 no 16A switch fixed on
a suitable module metal box and white front plate (Modular type)
including all interconnections as required UPS power (Switch shall
be fixed above the table with suitable modular front plate/box and
sockets shall be fixed below the counters)
9 no
b Supply and fixing of 2nos. 6A sockets with 1 no 6A switch fixed on a
suitable module metal box and white front plate (Modular type)
including all interconnections as required Rawpower (Switch shall be
fixed above the table with suitable modular front plate/box and
sockets shall be fixed below the counters)
c
9 no
Supply and fixing of modular RJ11 telephone sockets with suitable
mounting box (Modular type) including all interconnections as
required (Bm, officers,counter,reception,fo,system room)
7 no
d
Supply and fixing of 3nos. 16A sockets with 1 no 16A switch fixed
on a suitable module metal box and white front plate (Modular
type) including all interconnections as required UPS power(for the
SERVER room)socket for the hub must be fixed as per the location
of HUB inside the server room
e
Supply and fixing of 1nos. 16A socket with 1 no 16A switch fixed on
a 3 module metal box and white front plate (Modular type)
including all interconnections as required for
locker, safe
room,Record room/Stationary roomDBD DocumentExtra room,
f
2
a
Providing 2 meter length of flexible 3core 2.5sqmm multi core
copper cable one end connected to plug top 15A and the other
connected to the SB inside and a suitable hook arranngement as
required for hanging the cable
LIGHT & FAN POINT WIRING
Point wiring with 1.5sqmm 650V grade multistranded PVC insulated
copper wire in MS/PVC PIPE for lights, fans including supply &
fixing of 5 amp modular switch in concealed MS switch box,front
plate, 3 plate ceiling rose, and concealed circuit wiring with 3 Nos
(P,N,E) 2.5sqmm. and all interconnections as required. (New wiring
in banking hall as per counter layout,BM,Co system and Contractor
must reuse the existing Wiring for the same location after extending
the existing points as mentioned in item no 2.b) No new point
wiring for Safe room,Exit,Stationary & Records,ups room ,Locker
room,passage,entrance)(27 points under the scope of land lord)
5 no
4 no
4 no
38 pts
b
c
same as above but for Extending the existing point in the hall as
required for the new layout for counters,hall,cash officer room from
the LDB/PDB
Supply and installation of 6A modular socket with a switch in the
above modular switch boards.
d
Same as item 2a but for call bell points including providing new
buzzer for the Branch Manager cabin as required
3
UPS, RAW POWER & TEL WIRING:
13 pts
10 nos
1 nos
AMOUNT
a
b
c
d
Supply and wiring with 3runs of 2.5 sq.mm 1100 V grade PVC
insulated multi strand copper conductor wires conforming to IS 694
(with latest amendments) in suitable size PVC CONDUIT of 2mm
thick concealed in the above ducts in the floor and supply of all
fixing materials and accessories, interconnections complete as
required for the UPS power sockets in the single window counters
and officer tables.
14 Nos.
Supply and wiring with 3runs of 2.5 sq.mm 1100 V grade PVC
insulated multi strand copper conductor wires conforming to IS 694
(with latest amendments) in suitable size PVC CONDUIT of 2mm
thick concealed in wall/floor and supply of all fixing materials and
accessories, interconnections complete as required for the raw
power primary sockets
6 sets
Same as above but looping with 3runs of 1.5 sq.mm 1100 V grade
PVC insulated multi strand copper conductor wires conforming to IS
694 (with latest amendments) in suitable size PVC CONDUIT from
the raw power secondary sockets
3 sets
Wiring for the wall mounting fans from the nearest switch board
with 1.5sqmm 650V grade multistranded PVC insulated copper wire
in MS/PVC PIPE and all interconnections as required including the
supply and fixing of 6A modular socket 3" below the false ceiling
and 6A switch in the switchboard as required.(BM,System room)
15 nos
e
Cutting the floor to the required depth 2" and width 6" for burying
the conduits for the UPS/raw power socket wiring and plastering
the floor surface.
100 mtr
f
Supplying and laying Medium grade PVC pipe in the above ducts for
the LAN/telephone cabling to the revised layout of counters
150 mtr
g
Supplying and laying 2 pair telphone wire in Modi make PVC casing
capping / pipe for the telephone points as per the revised layout.
250 mtr
h
Supplying and fixing a 10 pair krone connector in a suitable box as
required
1 job
4
DISTRIBUTION BOARDS
Supply and installation of following size MCB distribution boards
with following combination of MCBs as required
a
2 +6 way MCB Double door DB for UPS sockets Incomer : 40A DP
MCB &Outgoing : 10/6 A SP MCB 7 Nos. for BM, Counters, Cash
officer.
1
nos
2 + 8 way MCB SINGLE door DB for UPS sockets Incomer : 32A
DP MCB &Outgoing : 16/10/6A SP MCB 10 Nos. for Field officer,
PBD Manager, system room
1
nos
1
nos
b
b
2 + 4 way MCB SINGLE door DB for UPS sockets Incomer : 63A
DP MCB &Outgoing : 32 A DPMCB 4 Nos. for output ups DB
c
e
3 phase 6 way MCB Main DB and Rawpower VTPN Double door DB
Incomer: 100A FP MCCB ,16KA &outgoing : 63A TP MCB-4
nos(LDB/PDB- 1,ATM - 1, Spare-2),63A DP MCB- 3 nos (ups-1,spare2)
3 phase 6 way AC ETPN DB Incomer: 63A FP MCB &outgoing :
20/10/16 A SP MCB's - 18 nos for Raw power and Lighting,AC for
system,BM.
1
nos
1
nos
g
Supply and fixing of 20A DPMCB on a suitable metal box for power
supply to A/C units including all interconnections as required near
the proposed AC locations at 4.5 ft from the floor
level.(Legrand/Siemens/L&T)(Ac for BM, System room, Cash
3
nos
i
Supply and fixing of 63A TPMCB on a suitable metal box for power
supply to Capacitior panel near the cut out including all
interconnections as required .(Legrand/Siemens/L&T)
1
nos
j
Supply, installation , testing and commissioning of 10KVAR APFC
panel with suitable APFC relay, and suitable combination of
capacitors and individual MCB controls
1
nos
Note : All Capacitors shall be Delta connected and rated for 440V
and of APP type The Capacitors shall be provided in the Panel itself
with proper ventilation arrangements.Panel to be installed at
suitable location near the meter side.
6
SITC of 125A on load Change over switch of HPL brand in suitable
enclosure with provision for the service cable termination as
required.
8
SUB-MAIN & AC WIRING
a
Wiring with 2 runs of 6Sq.mm 1100V grade PVC insulated Copper
conducter multistrand wires along with one run of 2.5mm copper
earth wire run in suitable size PVC CONDUIT run concealed on wall/
Ceiling etc as required.(for UPS incoming-2 )
1 nos
30 mtr
b
Wiring with 2 runs of 4Sq.mm 1100V grade PVC insulated Copper
conducter multistrand wires along with one run of 2.5mm copper
earth wire run in suitable size 2 mm thick PVC CONDUIT run
concealed on wall/ Ceiling etc as required. ( 1.5,2 Tr split ac,and
180 mtr
ougoing till ups sub db))
c
Wiring with 4 runs of 4Sq.mm 1100V grade PVC insulated Copper
conducter multistrand wires along with one run of 2.5mm copper
earth wire run in suitable size 2 mm thick PVC CONDUIT run
concealed on wall/ Ceiling etc as required. ( for LDB ,)
60 mtr
d
Wiring with 4 runs of 6 Sq.mm 1100V grade PVC insulated Copper
conducter multistrand wires along with one run of 2.5mm copper
earth wire run in suitable size 2 mm thick PVC CONDUIT run
concealed on wall/ Ceiling etc as required. (From Main panel to Raw
power/ LDB with system and BM ac )
120 mtr
e
Supply and laying of 3.5 core 35 sq.mm 1100V grade PVC
insulated aluminium armoured conducter along with 2 runs of
SWG8 GI earth wire run on wall/ Ceiling etc as required.(from
common termination panel to capacitor ,cos, vdb anf from cos to
VDB at ups room).
50 mtr
f
g
Termination of the above cable as required with suitable glands and
lugs
6 sets
Supplying and laying 3 runs of 2.5Sq.mm 1100V grade PVC
insulated unarmoured multistrand copper conducter cables along
with one run of 12SWG GI earth wire in PVC pipes run on wall/
Ceiling etc as required. (for sign board )
40 mtr
9
FIXTURES/FANS
a
Supply and Installation of Direct/Indirect recess mounted luminaire
Green square ,Philps LED fixture (OR) Equivalent models in other
approved makes with all inter connections and fixing arrangement
as required.
7 nos
Supply and Installation of 1X15W downlighter fixtures recess
mounted type LED Philips or Equivalent model with all
interconnections and fixing arrangement as required.
32 nos
Supply and Installation of 1X28W T5 fixtures SURFACE type with all
interconnections (Philips Vector) and fixing arrangement as
required
14 nos
b
d
e
Supply and fixing of exhaust fan of 9" of Almonard / CG as required
3 nos
f
g
h
i
j
Supply and installation of 100w 4/5 step type electronic
regulator in the modular switch boards as required
fan
Supply and fixing of hi flow model 56 inches ceiling fan CG
makewith all connections and anchor fasteners ,fan hooks, down
rods etc as required
Supply and Fixing of wall mounted fans of CG make 400mm Hi flow
model.Bm,System room.
Supply, fixing 1 nos of 16 A switch socket with all modular front
plate and connections for lunch room, Public Space, officer for
cooler
Wiring with 2 runs of 4Sq.mm 1100V grade PVC insulated Copper
conducter multistrand wires along with one run of 2.5mm copper
earth wire run in suitable size 2 mm thick PVC CONDUIT run
concealed on wall/ Ceiling etc as required for above points
10 Earthing:
a Providing Standard Copper Plate Earth Station with 600 X 600 X
3.15mm thick copper plate including construction of brick pedestal,
providing meshed funnel, CI cover completly as per IS 3043-1987
or latest revision including suitable copper strip to be fixed in the
UPS room for distribution.
b
d
4 nos
4 nos
15 nos
8 nos
120 mtr
1 nos
Providing Standard GI pipe Earth Station including construction of
brick pedestal, providing meshed funnel, CI cover completly as per
IS 3043-1987 or latest revision including suitable copper strip to be
fixed in the UPS room for distribution.
1 nos
c Supply and laying of 8SWG Cu insulated Wire in 20mm dia rigid pvc
conduit for ups DB earthing from the existing earth pits in PVC
conduit of suitable size.
60 mtr
Supply and laying of 8SWG gI insulated Wire in 20mm dia rigid pvc
conduit for ups DB earthing from the existing earth pits as required
in PVC conduit of suitable size.
55 mtr
11 Supply fixing of 250A/36kva FP MCCB Enclosure for the meter
input from the pole for the AP TRANSCO all mounted on wooden
board with neutral link of suitable capacities with all connections
and hardware.
1 nos
Total value of Electrical works
APPROVED BRANDS
WIRES
MCCB
TPN SFU
CHANGEOVER SWITCH
CABLES
KITKAT
MS CONDUITS
LT/ RR CABLE/FINOLEX/HAVELLS/POLYCAB
ABB/LT/SIEMENS/GE/MDS/CG
ABB/GE/LT/CG
L&T/HPL/C&S
CCI/UNIVERSAL/POLYCAB/HAVELLS/RALLISON
GECO/ANCHOR/KUNDAN
GUPTA/BHARAT
PVC CONDUITS
PRECISION/SUDHAKAR
METAL CLAD SOCKETS
MDS SLEEK/SIEMENS/HAVELLS
LIGHT FIXTURE
PHILIPS/WIPRO/CG/BAJAJ/GE
CFL FIXTURES
PHILIPS/CG/GE/WIPRO/BAJAJ
CAPACITORS
L&T/ CROMPTON/ NEPTUNE DUCATI/ ASIAN
CEILING/WALL FANS
CROMPTON/ BAJAJ
CABLE GLANDS
SUNIL/HMI/BRACO/COMET
CABLE LUGS
DOWELL/3D
HRC FUSES/BASE
GE/ OR APPROVED MAKE
INDICATING METERS
AE/IMP/MECO/ENERCON
RELAYS
GE/TELEMECANIQUE/PROK DEVICES/
KAPPA/IMP/AE/KALPA
CT'S RESIN-CAST
SELECTOR SWITCHES
L&T/SIEMENS/KAYCEE
INDUSTRIAL EXHAUST FANS
CROMPTON/ GEC/ARMONALD / BAJAJ
CEILING/EXHAUST FANS
PVC CONDUITS
BUS BAR TAPING BOX
M S CONDUITS
CASING / CAPPING
the make of materials considered in the Tender.
CROMPTON / BAJAJ
MODI/SUDHAKAR/VIP/PRECISION/ATUL
SIEMENS/SCHNEIDER/ABB
BHARAT / ZINDAL
CLASSIC/ MODI