nRM ADCX - Sensor Switch

nRM ADCX
AUTOMATIC DIMMING CONTROL PHOTOCELL
RECESSED MOUNT • LOW VOLTAGE
SPECIFICATIONS
FEATURES
Automatic Daylight Harvesting
Full On/Off Switching Control (optional)
Communicates w/ nLight Network
Remotely Configurable/Upgradeable
Automatic Set-Point Calibration
Push-Button Programmable
Green LED Indicator
PHYSICAL SPECS
SIZE 4.40” (11.18 cm) Square
WEIGHT 6 oz
MOUNTING: Recesses into a 4” x 4”
square junction box
COLOR: White
nLIGHT NETWORK PORTS: 2 RJ-45
ELECTRICAL SPECS
POWER CONSUMPTION: ~ 3 mA
WIRES: None
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
SILICONE FREE
ROHS COMPLIANT
SENSOR OPERATION
The sensor controls the room’s lighting to achieve maximum daylight harvesting
while maintaining a minimum light level referred to as the set-point. When
no daylight is available, the sensor allows the controlled dimmable lighting to
operate at their full bright level. As daylight increases and begins to contribute to
the overall light level of the room, the Automatic Dimming Control (ADC) feature
starts dimming the room proportionally,
eventually reaching the full dim level (or
AMPLE DAYLIGHT
optionally switching off).
As the daylight levels fall, the ADC
feature will again take control of the
lights; reducing the dim level (increasing
the brightness) in order to achieve the
necessary total light level. At the point
when all daylight contribution is gone,
lighting will be back at its full bright level.
DIMMING
OTHER
UL and CUL Listed
Title 24 System Component
5 Year Warranty
Assembled in the U.S.A.
OVERVIEW
OPTIONS
The nLight nRM ADCX Series
LOW TEMP/HIGH HUMIDITY (LT)
photocell sensor provides automatic
• Device electronics are coated for
dimming control for daylight harvesting
corrosion resistance - required for
applications. Ideal for spaces with
cold storage or humid areas.
windows, such as vestibules, corridors,
• Operates down to -40º F/C
classrooms, or offices, the sensor works
by first monitoring daylight conditions in
a room. It then signals networked nLight
control devices to adjust their dimming outputs to obtain maximum energy savings
while ensuring adequate lighting levels are maintained. The nRM ADCX can
control nLight enabled luminaires (e.g. VTLED Family from Lithonia), or nLight
dimming relay packs (e.g. nPP16 D or nSP5 PCD), or auxiliary dimming output
devices (e.g. nIO D). The nRM ADCX sensor can also be used together with
nLight occupancy sensors. Manual override or adjustment of the dimming level is
possible via WallPod dimmers or through the SensorView software.
Set-point
nLIGHT OPERATION
nRM family devices are native nLight
devices meaning they are individually
Lights Full DIM
Lights Full ON
addressable and digitally communicate
to other nLight devices such as Wallpod
AUTO DIMMING CONTROL
switches, relay packs, nLight-enabled
digital luminaires, and occupancy
sensors. All devices are wired using CAT-5e cabling; creating a local nLight
control zone. Once linked to an nLight Gateway, either directly or via an nLight
network backbone, the zone becomes capable of remote status monitoring, time
scheduling, configuration, and control with nLight SensorView software.
ORDERING INFO
MODEL NUMBERS
DESCRIPTION
nRM ADCX
Daylight Harvesting Photocell Recessed Mount
nRM ADCX LT
Daylight Harvesting Photocell Recessed Mount, Low Temp Operation
Revised 12.18.14 © 2014
WIRING (DO NOT WIRE HOT)
T568B pin/pair assignment is recommended for all CAT-5e cables. Sensor power is provided via the CAT-5e connection to an
nLight power pack/supply, nLight-enabled digital luminaire, or nLight Bridge.
Wiring to an nLight Relay Pack
Wiring to an nLight Enabled Luminaire
nRM ADCX
nRM ADCX
BLU (line in)
120 VAC BLK1 (line in)
OR
1
277 VAC1 ORN (line in)
WHT(neutral)
BLU (line out)
nPP16 D
or
nPP16 DS
CAT-5e
0-10 VDC
Ballast or
LED Driver
CAT-5e
VIO (low voltage dim out)
GRY (low voltage common)
GRN
CAT-5e
nLight Enabled
Luminaire
To other nLight
devices (optional)
To other nLight
devices (optional)
DEVICE SETTINGS
Several operational settings for the nRM ADCX are available and configurable through the unit’s push-button and/or
SensorView software, including:
•
Override (Full Dim/Full Bright/Normal)
•
Automatic Set-point Calibration Mode
•
Photocell Broadcasting (Enable/Disable)
•
Blink-back Set-point (in footcandles)
•
Switch Tracking (Enable/Disable)
•
Set-point (0-200 fc)
•
Photocell Broadcasting Channel (1-16)
•
Sunlight Discount Factor (1-8)
•
Switch Tracking Channel (1-16)
•
Occupied Bright Level (0-100%)
•
Photocell On/Off (Enable/Disable)
•
Unoccupied Dim Level (0-100%)
•
WallPod Dimming Adjustment (Temporary, •
Dimming Rate
•
Photocell On/Off (Enable/Disable)
•
Photocell On/Off Transition Time (45 sec - 25 min)
•
Photocell Temporary Override, Permanant)
LED Indicator (Enabled/Disable)
INSTALLATION
• The nRM ADCX is designed to fit inside a 4” square junction
box* (min. box depth 2.125”). The sensor can also be recessed
mounted in a ceiling tile.
• Interconnect unit (via rear RJ-45 ports) with other nLight devices
in lighting zone using CAT-5e cables.
• Once power is received via CAT-5e connection, all devices in
zone will automatically begin functioning together according to
each device’s defaults.
PUSH BUTTON
*Canadian style boxes w/ two screws
per mounting tab require modification.
PROGRAMMING
Refer to included instruction card for default settings and directions on programming the sensor via the push-button.
WARRANTY
5-year limited warranty. Full warranty terms located at:
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Note: Specifications subject to change without notice. Actual performance may differ as a result of end-user environment and application.
Sheet#: TN-118-003
900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.nlightcontrols.com