M MODbreak Moulded Case Circuit Breakers Technical Catalogue An economical and flexible line of MCCBs for general purpose applications POWER DISTRIBUTION AND PROTECTION Moulded Case Circuit Breakers, Chassis, Transfer Switches NHP Electrical Engineering Products Pty Ltd 5th September 2014 1 Sales 1300 NHP NHP Sales 0800 NHP NHP nhp.com.au nhp-nz.com M MODBreak MCCBs CONTENTS MODbreak MCCBs Page Number Product overview 3 pole MCCBs 4 pole MCCBs Internal accessories External accessories MB Chassis MBC Chassis Transfer switches Transfer switch controllers MCCB ratings chart Selectivity and Cascade tables MODcurve Selectivity Software Motor start tables Watts loss Let through and cut off values Temperature ratings Characteristic curves – thermal magnetic MCCBs Characteristic curves – electronic MCCBs Electronic MCCB OCR setting Dimensions MCCBs and accessories Transfer Switches MODbreak OCR Tester MCCB installation details 3 5 6 7 8 - 13 14 - 15 16 - 20 21 22 - 30 31 32 - 35 36 37 - 38 39 39 39 40 41 42 - 45 46 - 54 55 - 58 59 - 60 61 - 67 2 M MODbreak Moulded Case Circuit Breakers MODbreak range overview From 16 A to 1250 A 3 Pole & 4 Pole Choice of 36kA and 50kA breaking capacities. Icu = Ics With Electronic and Thermal Magnetic protection relays MCCBs for motor backup protection MCCBs for distribution systems Manual, rotary handle or motorised versions Wide range of internal and external accessories Chassis options Transfer switch and controllers MB2 MB3 MB4 MODbreak frame sizes and ampere ratings MB2 Rated current Over Current Relay 63 (50A to 63A), 80, 100, 125, 160, 200, 250 A Thermal magnetic Rated current Over Current Relay 320, 400, 500, 630 A Thermal magnetic 40 (16A to 40A), 63, 100, 160, 250 A Electronic MB3 400, 630 A Electronic MB4 800, 1000, 1250 A Electronic Rated current Over Current Relay Thermal Magnetic Over Current Relay Features of Thermal Magnetic OCR MTX1 Electronic Over Current Relay Adjustable overload setting 80% to 100% of ln Adjustable magnetic short circuit setting 6 – 10 ln Push to trip button True RMS sensing Infinite adjustment thermal and magnetic dials Refer ratings chart for additional setting details Features of MTX1 Electronic OCR 3 Overload protection LT with selectable inverse time delay Adjustable Short Time ST characteristic Short circuit (ST) characteristic with selectable time delay LT and ST characteristic can be switched OFF Fixed instantaneous trip DIP switch OCR setting Push to trip button Thermal memory enable / disable Power ON / pick-up LED LED blinks at 85% and rapidly at 120% Ir prior to tripping True RMS sensing Refer ratings chart for additional setting details M MODbreak Moulded Case Circuit Breakers Faster tripping The unique speed contact system accelerates the opening of contacts during short circuit. This ensures faster tripping an ultimate current limiting feature. The result-very low let-through, cut-off current and fault clearing time Mechanical Anti-reclosing This unique feature ensures that under short circuit conditions, the contacts open and latch even before the release gives a trip command to the mechanism. This avoids contact re-closing and bounce Low Watts loss The entire current carrying path is optimally designed to achieve very low watt loss. Silver contacts offer low contact resistance, which help to achieve a low heat connection. Positive Isolation The MCCB toggle indicates the true position of the main switching contacts Double Insulation Internal accessories are housed in insulated casings to ensure a first level of insulation. When the front cover is opened for the fixing of internal accessories, the MCCB is totally insulated ensuring double insulation. Standards Compliance MODbreak complies with AS 60947-2, AS/NZS 3947-6, IEC 60947, and the European CE Mark. Forward or Reverse connection MODbreak MCCBs can be forward or reverse connected to allow reversal of line and load connections. This is especially important for MB and MBC chassis where MODbreak MCCBs are reverse connected on the chassis as standard. Mounting angle ⁰ Vertical and 90 to the left or right 4 M MODbreak Moulded Case Circuit Breakers Features Electronic and thermal magnetic types 3 pole types 36kA and 50kA interrupting capacities Fault interruption ratings Icu = Ics Internal and external accessory range Cascading, Selectivity, motor starting and other data available NHP MODcurve selectivity and Cadblocks available Chassis options for 3 pole MCCB’s up to 630A frame Transfer switches available to 630A frame Quick reference guide MB2 250 MCCB 3 pole MCCB’s Ampere Frame 250AF 250AF 250AF 250AF 630 AF 630 AF 630AF 630AF 800 / 1250AF Trip unit Rating (A) 63 100 125 160 250 63 80 100 125 160 250 40 100 250 40 100 250 320 400 630 320 400 630 400 630 400 630 800 1000 1250 415V kA ICU ICS 36 36 MCCB type Current Adjustment Thermal Magnetic 80-100% 50 50 Thermal Magnetic 80-100% 36 36 Electronic 40-100% 50 50 Electronic 40-100% 36 36 Thermal Magnetic 80-100% 50 50 Thermal Magnetic 80-100% 36 36 Electronic 40-100% 50 50 Electronic 40-100% 50 50 Electronic 40-100% Catalogue Number MB263D3TM MB2100D3TM MB2125D3TM MB2160D3TM MB2250D3TM MB263N3TM MB280N3TM MB2100N3TM MB2125N3TM MB2160N3TM MB2250N3TM MB240D3SE MB2100D3SE MB2250D3SE MB240N3SE MB2100N3SE MB2250N3SE MB3320D3TM MB3400D3TM MB3630D3TM MB3320N3TM MB3400N3TM MB3630N3TM MB3400D3SE MB3630D3SE MB3400N3SE MB3630N3SE MB4800N3SE MB41000N3SE MB41250N3SE Ordering notes: 1. Refer following pages for internal and external accessories, chassis and transfer switch options. 2. Refer following pages for Selectivity and Cascade tables. 5 3 pole Price $ 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 M MODbreak Moulded Case Circuit Breakers Features Electronic and thermal magnetic types 4 pole types 36kA and 50kA interrupting capacities Fault interruption ratings Icu = Ics Internal and external accessory range Cascading, Selectivity, motor starting and other data available NHP MODcurve selectivity and Cadblocks available Transfer switches available to 630A frame 250A 4 pole MODbreak MCCB 4 pole MCCB’s Ampere Frame 250AF 250AF 250AF 250AF 630 AF 630 AF 630AF 630AF 800 / 1250AF Trip unit Rating (A) 63 100 125 160 250 63 100 125 160 250 40 100 250 40 100 250 320 400 630 320 400 630 400 630 400 630 800 1000 1250 415V kA ICU ICS MCCB type Current Adjustment 36 36 Thermal Magnetic 80-100% 50 50 Thermal Magnetic 80-100% 36 36 Electronic 40-100% 50 50 Electronic 40-100% 36 36 Thermal Magnetic 80-100% 50 50 Thermal Magnetic 80-100% 36 36 Electronic 40-100% 50 50 Electronic 40-100% 50 50 Electronic 40-100% Catalogue Number MB263D4TM MB2100D4TM MB2125D4TM MB2160D4TM MB2250D4TM MB263N4TM MB2100N4TM MB2125N4TM MB2160N4TM MB2250N4TM MB240D4SE MB2100D4SE MB2250D4SE MB 240N4SE MB2100N4SE MB2250N4SE MB3320D4TM MB3400D4TM MB3630D4TM MB3320N4TM MB3400N4TM MB3630N4TM MB3400D4SE MB3630D4SE MB3400N4SE MB3630N4SE MB4800N4SE MB41000N4SE MB41250N4SE Ordering notes: 1. Refer following pages for internal and external accessories and transfer switch options. 2. Refer following pages for Selectivity and Cascade tables. 6 4 pole Price $ 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 M MODbreak Moulded Case Circuit Breakers Internal Accessories – MODbreak MCCBs Common Internal accessories Common Internal accessories, except UVTs. Field fit by the user. Internal accessories easily clip into an MCCB, and only require a flat or Posidrive screwdriver to first remove the MCCB cover. No live parts are exposed during accessory fitting. Internal accessories come with 600mm wire leads as standard. Accessory types Auxiliary Contacts 1 C/O and 2C/O Auxiliary Contact 2 C/O Trip Alarm Contact Auxiliary & Trip Alarm Contact Shunt Release Under Voltage Release Easy fit clip-in accessories MCCBs with accessory covers removed, showing internal accessories fitted Accessory Electrical Data Shunt Trip 110 - 415VAC 15mA at 250V AC UVT 240V AC 1.4 VA 5A at 250V Auxiliaries/Alarms 3A at 250V (common ratings) 0.5A at 250V 1A at 250V Excitation current Latching current AC Resistive AC Inductive DC Resistive DC Inductive MCCB internal accessory fitting configurations Internal accessory selection catalogue numbers Accessory type Description Shunt Trip Under Voltage Trip Auxiliary & Alarm contacts Suits Catalogue Number 110 – 415V AC, 50/50Hz MB2, 3, 4 MBSHUNTAC110415 240V AC, 50/60Hz 240V AC, 50/60Hz 1 C/O Auxiliary 2 C/O Auxiliary 1 C/O Aux – 1C/O Alarm 1 C/O Alarm MB2, 3 MB4 MB2, 3, 4 MB2, 3, 4 MB2, 3, 4 MB2, 3, 4 MB23UVT240VAC Refer NHP MBAUX1C MBAUX2C MBAUX1CALRC MBALR1C 7 M MODbreak Moulded Case Circuit Breakers External Accessories – MODbreak MCCBs External accessories are field fitted, except for motors which are fitted by NHP. Refer following pages for additional product information. 250A MB2 Accessory type Price $ 320A, 400A, 630A MB3 Price $ 800A, 1250A MB4 Price $ Handle Operators Extension handle and shaft OFF lockable as standard with up to 3 padlocks or hasps, IP54, door interlocking. Additional ON position locking available via field conversion to obtain OFF/ON locking. Lock OFF MB2HANDLESTD 0.00 MB3HANDLESTD 0.00 MB4HANDLESTD 0.00 Direct mount handle Padlockable up to 3 locks, no door interlocking, Lock OFF handle MB2HANDLEDIRECT 0.00 MB3HANDLEDIRECT 0.00 - 0.00 MCCB toggle lock – captive Suits single 5-7 mm padlock MB2CAPLOCK 0.00 MB3CAPLOCK 0.00 MB4CAPLOCK 0.00 Motor operator Includes motor and internal MCCB mounted motor indication flag auxiliary block – must be NHP factory or branch installed 240V AC control, 50-60Hz MB2MOTOR240VAC 0.00 MB3MOTOR240VAC 0.00 - Terminal covers & interpole barriers Terminal covers supplied in sets of 2, IP20 entry insert covers supplied as standard Interpole barriers supplied with new MCCBs as standard for the line side only, 1 per pole. Standard 3P Standard 4P MB2TCSTD3P - 0.00 0.00 MB3TCSTD3P - 0.00 0.00 MB4TCSTD3P MB4TCSTD4P Wide 3P Wide 4P MB2TCWIDE3P MB2TCWIDE4P 0.00 0.00 MB3TCWIDE3P MB3TCWIDE4P 0.00 0.00 - Flush 3P Flush 4P Interpole barrier (set of 3) MB2TCFLUSH3P MB2POLEBARRIER 0.00 0.00 MB3TCFLUSH3P MB3POLE BARRIER 0.00 0.00 MB4POLEBARRIER Attached busbar 3 pole set of 3 4 pole set of 4 MB2ATTBAR3P MB2ATTBAR4P 0.00 0.00 MB3ATTBAR3P MB3ATTBAR4P 0.00 0.00 MB4FCB3P MB4FCB4P Mechanical Interlock Rear mounting, MCCB mounting plate included MB2MECHINT250 - 0.00 MB3MECHINT400 MB3MECHINT630 0.00 0.00 - Electronic MCCB OCR tester MBOCRTESTER 8 0.00 0.00 0.00 0.00 M MODbreak Moulded Case Circuit Breakers External Accessories – MODbreak MCCBs Extension shaft handles Available for MCCBs to 1250A Mounts on front of MCCB without removal of accessory cover Padlock OFF as standard Padlock OFF handle field conversion to padlock ON Suits up to three 5-7mm padlocks or multi lock hasps Door interlock in ON position, selectable for padlock OFF. Side switch selector prevents or allows door opening if padlocked Easy to see ON / OFF / TRIP indication MCCB rating label can be seen with handle installed Push to trip button accessible while handle installed IP 54 degree of protection when door mounted 1.5mm diameter Door Defeat access hole at base of handle Handle kit includes 275mm x 10mm2 shaft, handle, MCCB mechanism OFF Padlocking and use of the door interlock feature Direct mount handles Available for MCCBs to 630A Mounts on MCCB without removal of accessory cover Handles are padlockable OFF as standard Handles can be field converted to lock ON Suits up to three 5-7mm padlocks or multi lock hasps Handles are not door interlocking. Easy to see ON / OFF / TRIP indication MCCB rating label can be seen with handle installed Push to trip button accessible while handle installed IP 54 degree of protection 9 M MODbreak Moulded Case Circuit Breakers External Accessories – MODbreak MCCBs Captive Toggle Padlocking Mechanism Consists of a brushed stainless steel lock attachment, which can be easily customer fitted via 4 hexagonal head mounting screws. Features Suitable for MB2, MB3 and MB4 MCCBs 20A to 1250A. Types: MB2CAPLOCK, MB3CAPLOCK, MB4CAPLOCK. MB2 toggle lock bracket fits within the MCCB’s 45mm DIN cut-out for door or escutcheon mounting. MB3 toggle lock fits within the MCCBs standard 78mm toggle area cut-out. If an MCCB trip occurs, a reset operation can be performed without the need to remove the lock captive attachment. No special spacing required between side by side mounted MCCBs. Captive lock attachment fitted Lock OFF 10 Lock ON M MODbreak Moulded Case Circuit Breakers External Accessories – MODbreak MCCBs Motor Operators Motor operators For 250AF and 630AF MCCBs. ON / OFF & Charged/Discharged indication. Spring charge mechanism. Selector switch for Auto/Manual operation and padlocking. Padlock facility for locking in OFF position (up to 3 padlocks). Resetting time < 250msec & Closing time < 90 msec. High mechanical & electrical endurance. Accessible internal back up fuse for extended motor life. Access to the protection setting on MCCB possible when motor fitted. True indication for ON/OFF & Discharged & charged. MCCB right side internal accessory space occupied when motor fitted. Replaceable 1.6A fuse as standard. OFF/ON terminal wiring is activated by via dry contact closure only. MBMOT motor operators are NHP factory or branch fit. Motors or handles can be fitted to interlocked MCCBs MB MOT Motor operator electrical & mechanical data MB2 Operating voltage (V AC) 240 Operating voltage (%) 85 – 110% Closing time (ms) 60 Opening time (ms) 300 Power consumption (VA) 350 Life / No. of operations 12000 Door cut out (mm x mm) 96 x 96 IP protection, on the front IP30 Operating frequency 2 per min Minimum control impulse time (ms) 300 Motors or handles can be fitted to interlocked MCCBs 11 MB3 240 85 – 110% 90 450 500 10000 96 x 96 IP30 1 per min 450 M MODbreak Moulded Case Circuit Breakers External Accessories – MODbreak MCCBs Mechanical interlocks Allows two MCCBs to be mechanically interlocked using a base plate and rear walking beam interlock, in a side by side configuration. For 250AF and 630AF MCCBs Rear walking beam mechanical interlock supplied on mounting plate Interlock kit plate pole configurations : 3P+3P, 3P+4P, 4P+3P, 4P+4P Mixed frame sizes cannot be interlocked Customer can fit interlock using knockout on rear of MCCB Internal and external accessories to be fitted Mechanically interlocked 4P+3P MCCBs Motor operators available for transfer switching MCCB right side internal accessory pocket occupied when motor fitted Manual Transfer Switches (MTS) using toggles or handles are customer assembled. Basic or Automatic Transfer Switches using motors and external controllers are NHP factory assembled. Refer following pages for information on order Basic (BTS) and Automatic transfer switches (ATS). Mechanical Interlock fitting Fail Safe rear walking beam mechanical interlock Interlock supplied pre-mounted to a metal mounting plate Plate suits MCCB poles: 3P- 3P, 3P- 4P, 4P- 3P and 4P- 4P MCCBs of different frame sizes cannot be interlocked User fit interlock via removal of rear MCCB knockouts Interlocking two MCCBs takes around 5-10 minutes MCCB toggle only operation if required MCCBs accept motors or handles Suitable for mounting MCCBs through an escutcheon or door cut-out 250AF MCCB have a DIN, 47mm size toggle cut-out Motors or handles can be fitted to interlocked MCCBs Knockout at rear of MCCB MCCBs mounted to the front of MCCB plate with actuators inserted knockout at rear of MCCB 12 M MODbreak Moulded Case Circuit Breakers External Accessories – MODbreak MCCBs Terminal cover options Available for MCCBs 250AF to 1250A Wide, standard, flush terminal covers Wide covers physically longer for larger cables or busbars 3 and 4 pole covers Covers come complete with IP20 end cover knock outs Increases IP Form for switchboard construction Rigid rubber interpole barriers supplied with MCCBs as standard Covers designed for chassis mounted MCCB Hole per pole for electrical probe testing. Front IP covers & interpole barriers are supplied with new MCCBs as standard Standard cover Flush cover 13 IP20 finger touch protection using MB terminal covers Wide cover M MB800 MCCB Chassis MODbreak MB chassis assemblies are designed to suit MODbreak Moulded Case Circuit Breakers. The busbars are fully dipped and type tested, and are suitable for 250AF MCCB’s rated 63A to 250A. (50A to 250A) MB 18 way Chassis for 250AF MCCB’s MB 12 way chassis showing MCCBs mounted, including flush terminal covers MB2TCFLUSH3P on the user connection side. The same covers can also be fitted to the Tee Off connection side for IP20 touch protection Poles MCCBs on each side Total MCCBs on chassis Chassis pan Height (mm) Pan Width Catalogue Number 6 12 18 24 30 36 42 48 60 72 1 2 3 4 5 6 7 8 10 12 2 4 6 8 10 12 14 16 20 24 105 210 315 420 525 632 737 840 1050 1260 370 370 370 370 370 370 370 370 370 370 MB80006U MB80012U MB80018U MB80024U MB80030U MB80036U MB80042U MB80048U MB80060U MB80072U NOTES: 1. Height dimensions are for pan size only. For cut-out details and other dimensions refer to following page. 2. An MB chassis metal pan width is 370mm. With MCCBs mounted on both sides the total width is 380mm. With flush terminal covers added to the MCCB load side, the total width is 405mm. 3. Terminals extend 53.5mm beyond the dimensions shown above, top and bottom. Chassis technical details: Chassis type Amps kA Suit MCCB MB 800 800 800 36 kA for 1 second 40 kA for 0.5 second MB250 14 MCCB dimensions H W D 163 105 96 M MB800 MCCB Chassis Dimensions mm: MB chassis with MB2TCFLUSH3P cover shown fitted to chassis Tee Off side of MCCB 15 M MBC MCCB High Current Chassis Features: Suits 250AF and 630AF MCCBs with trip unit ranging 50A to 630A. Double sided chassis types for 3 pole MCCBs 1250 A, 1600 A or 2200 A rated main bars. 11 enclosure sizes to suit application height space. Front connect tags supplied as standard. Complies with AS/NZS 3439, AS/NZS 3000 – 2007. Form of separation can be up to 4bih. AS/NZS 3439.1: 2000 (Annex ZF). Circuit breakers are reverse fed as standard. Assembled to order from stocked parts by NHP Chassis Box Selection (no Tee offs fitted, specify from next page) Chassis Size 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 Main bar rating (A) Icw kA for 1 sec 1250A 65 2 x 10x20mm bars 1600A 65 2 x 10x30mm bars 2200A 2 x 10x50mm bars 65 MCCB unit space (mm) 15 U 18 U 21 U 24 U 27 U 30 U 33 U 36 U 39 U 42 U 45 U 15 U 18 U 21 U 24 U 27 U 30 U 33 U 36 U 39 U 42 U 45 U 15 U 18 U 21 U 24 U 27 U 30 U 33 U 36 U 39 U 42 U 45 U Overall height (mm) 610 718 826 932 1030 1150 1258 1366 1474 1582 1690 610 718 826 932 1030 1150 1258 1366 1474 1582 1690 610 718 826 932 1030 1150 1258 1366 1474 1582 1690 Notes: Height excludes extended and attached busbar. Overall chassis depth when MCCB’s are fitted is 269 mm. Refer next page for chassis Tee Off ordering details. For detailed dimensions, escutcheon/door cut-outs, and ordering form, refer following pages. 16 Catalogue Number MBC12153 MBC12183 MBC12213 MBC12243 MBC12273 MBC12303 MBC12333 MBC12363 MBC12393 MBC12423 MBC12453 MBC16153 MBC16183 MBC16213 MBC16243 MBC16273 MBC16303 MBC16333 MBC16363 MBC16393 MBC16423 MBC16453 MBC22153 MBC22183 MBC22213 MBC22243 MBC22273 MBC22303 MBC22333 MBC22363 MBC22393 MBC22423 MBC22453 Price $ 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 M MBC MCCB High Current Chassis TEE OFF’s MBC Chassis and Tee Offs are NHP FACTORY ASSEMBLED Frame MB2 250 Narrow MB3 400-630 Narrow MB3 400-630 Wide MCCB Amp Frame (A) 250 400-630 400-630 MCCB width (U = units) 3U 4U 6U Double sided Cat. No. MBCDN2503 MBCDN6303 MBCDW6303 Price $ 0.00 0.000.00 0.00 Ordering notes 1. Add Tee Offs as required to the chassis enclosure to complete the components list required. 2. 1 x double sided tee off kit will accommodate 2 MCCBs, 1 on each side of the chassis. 3. For ordering MBC Chassis an ordering layout form is to be used. 4. Add the price of the tee offs required to the price of the chassis to calculate a list price. 5. MB3 400 / 630A MCCB’s fitted with a same width narrow cover = 4 units in width 6. MB3 400 / 630A MCCB’s fitted with a “wide” width cover = 6 units in width 7. Bottom or top extended main bar are optional. 8. For MCCB terminal cover selection use refer MCCB accessories. 9. Only circuit breakers of the same width can be mounted opposite each other. Component selection example: Main chassis components: Chassis Chassis box 1600 A, less tee offs 630 A tee off set wide cover 400 A tee off set narrow cover 250 A tee off set 250 A tee off set components MBC16183 MBCDW6303 MBCDN6303 MBCDN2503 MBCDN2503 Quantity 1 1 1 1 1 Terminal covers are ordered as required for the MCCB line and load terminals. Flush covers are used for the chassis tee off side. Testing: The MBC (HC) chassis has been unconditionally type tested (no MCCBs fitted) by NHP, with an Icw short time rating of 65 kA for 1 second. 17 M MBC High Current Chassis Order Form Customer: Account No: Deliver to: Order No: Quantity: Price: Contact: $ / Req'd Delivery: UNIT S / CHASSIS SPECIFICATION 1 2 3 POLES 4 MCCB 5 Config. X X 3 Pole - only Double Sided - only 6 Top Entry only 7 Chassis Supply Connection 8 9 Bottom Entry only Top and Bottom Entry No Extended Bar - Connect via MCCB 10 11 RATING 65kA for 1 sec 12 13 1250 Amp 2 -10 x 20 mm main bars 1600 Amp 2 -10 x 30 mm main bars 2200 Amp 2 -10 x 50 mm main bars 14 Size 1 15 Qty Size 3 Units Total Type x 3 = 250A MB2 Narrow Terminal Cover x 5 = 250A MB2 Wide Terminal Cover 19 x 4 = 400A MB3 Narrow Terminal Cover 20 x 6 = 400A MB3 Wide Terminal Cover x 4 = 630A MB3 Narrow Terminal Cover x 6 = 630A MB3 Wide Terminal Cover 17 Size 2 3 POLE TEE OFFS - DOUBLE SIDED 610 mm 16 18 718 mm 21 826 mm 22 23 Size 4 24 934 mm Total units 25 * 37.5mm gap each side of MB2 using wide covers (total 75mm) 26 Size 5 27 1042 mm * 37.5mm gap each side of MB3 using wide covers (total 75mm) 28 29 Size 6 30 1150 mm NOTES 31 32 Size 7 33 1258 mm 34 35 Size 8 36 1366 mm 37 38 Size 9 39 1474 mm * Pan Width = 440 mm including mounting channel 41 Size 10 * Chassis are supplied crated and without MCCB's fitted * Circuit breakers to be fitted reverse fed by customer 40 42 1582 mm * Depth = 269 mm from rear to escutcheon * 1 Unit = 36 mm 43 44 Size 11 45 1690 mm TORQUE SETTINGS MCCB LINE SIDE BOLTS 250 AMPS M6 7Nm 400 - 630 AMPS M8 14Nm MAIN BAR CONNECTIONS M10 44Nm Document version 11/02/13 CUSTOMER REFERENCE DRAWINGS In tern al Use O n ly NHP Branch MOUNTING, CUT OUT AND CONNECTION DETAILS Chassis Reference Drawing MD I00581200 Rev 0 NHP Contact MBCD250 Narrow Tee Off Dwg Set MD L005080 Rev 2 Sales Order MBCDN630 Narrow Tee Off Dwg Set MD L005083 Rev 2 Works Order MBCDW630 Wide Tee Off Dwg Set Rev 2 Requested Ex works Date: MD L005086 18 / / M MBC MCCB High Current Chassis Example photo, showing an MBC chassis with MCCBs using direct mount handles, and with terminal covers installed. The terminal covers are fitted to the tee off side and user connection side of the MCCBs. The top two MCCBs are fitted with WIDE terminal covers, and the others with same width standard covers. The tee off side of the MCCBs have flush terminal covers fitted which cover the MCCB terminal area, as well as the exposed tee off chassis connection points. Isolator option for Chassis Where a user wishes to use a load break switch to isolate the chassis, NHP can supply a Socomec 1600A load break switch, plus busbar connection kit which consists of a set of bars. MBC double sided chassis showing MCCBs with direct mount handles and terminal covers fitted. Refer accessories pages for cover and other accessories selection. MBC double sided chassis showing Socomec SLB16003P isolator using a link kit as shown. A clear polycarbonate cover for the link kit is also available (not shown). Link kits are available for chassis with 1250A And 1600A main bars. 2200A main bar kits are not available at this time. Additional details are available on request. Catalogue numbers of link kit parts: Link kit Link kit cover HCCONNTAG16003P HCSLB1600C 19 M MBC MCCB High Current Chassis Reference dimensions MBC Chassis cut-out details Notes 1. 2. 3. 1600A Chassis shown above with 2 off 30mm x 10mm busbars per phase. Other busbar options: 1250A busbars, 2 off 20mm x 10mm per phase 2200A busbars, 2 off 50mm x 10mm per phase Cut out dimensions are centred on the MCCB toggles. 20 M MODbreak MCCB Transfer Switches Basic Transfer Switches MODbreak transfer switches are available from 20A to 630A, and consist of mechanically and electrically interlocked circuit breakers, with motors fitted. The transfer switches come pre-wired on a metal panel. Automatic Transfer Switches Basic Transfer Switches can be coupled with either TemLogic TL101CIP electronic or TLP2 relay timer changeover controllers to enable Automatic Transfer Switching (ATS). The changeover controller automatically commences a change over to a standby power supply in the event of power failure. Manual Transfer Switches MODbreak Manual Transfer Switches are available from 20A to 630A, and consist of rear walking beam mechanically interlocked circuit breakers on a metal mounting plate. Manual transfer switches are assembled by the user, using interlock kits and MCCBs that are ordered from the MCCB and accessories pages in this catalogue. Basic Transfer Switches (BTS) Features: Poles: 3P+3P or 4P+4P MCCB configurations. Pre-assembled on a mounting plate Rear walking beam interlock used Pre-wired with electrical interlocking 240V AC control motor operated MCCBs Ordering: MB transfer switches are manufactured to order. Contact NHP for availability. TM = Thermal Magnetic, E = Electronic Trip Unit. BTS = Basic Transfer with motors BTS selection chart and Catalogue numbers MCCB’s used Ampere Range MB263N_TM MB263N_TM MB263N_TM MB263N_TM MB263N_TM MB240N_SE MB2100N_SE MB2250N_SE MB3320N_TM MB3400N_TM MB3630N_TM MB3400N_SE MB3630N_SE 50.4-63 80-100 100-125 128-160 200-250 16-40 40-100 100-250 256-320 320-400 504-630 160-400 252-630 Fault I/C 415V kA Icu/Ics OCR Type 3P Outline Dims. (mm) H W D 50 TM 305 209 235 50 E 336 237 241 50 TM 550 433 341 50 E 550 433 341 21 3 Pole BTS Cat No. Price $ 4 Pole BTS Cat No. Price $ MBTSTM6333 MBTSTM10033 MBTSTM12533 MBTSTM16033 MBTSTM25033 MBTSE4033 MBTSE10033 MBTSE25033 MBTSTM32033 MBTSTM40033 MBTSTM63033 MBTSE40033 MBTSE63033 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 MBTSTM6344 MBTSTM10044 MBTSTM12544 MBTSTM16044 MBTSTM25044 MBTSE4044 MBTSE10044 MBTSE25044 MBTSTM32044 MBTSTM40044 MBTSTM63044 MBTSE40044 MBTSE63044 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 M MODbreak Transfer Switch Controller Type: TL101CIP The TemLogic 2 TL101 automatic transfer switch (ATS) controller will control & supervise the primary & secondary power of an installation and initiate transferring of the mains to a backup source in the event of main source interruption. The utility changeover, from one power source to the other can be fully automatic or manually operated. The logic controller includes the necessary functions to monitor energy distribution systems and generating sets, and MODbreak transfer switch. Automatic transfer takes place when predefined conditions entered by the user take place such as: Power failure of one power source Power supply voltage/frequency etc. not falling within programmed limits The need to use the most economical power source The TL101CIP is programmed from the front panel with visual led indication. Alternatively, the circuit breakers can be manually controlled using the function keys on the front face of the controller. The list below details typical applications: Utility-utility, utility to generator or generator to generator changeover Generator management with automatic test and rotation emergency Three phase, two phase or single-phase voltage controls L-L voltage and/or L-N voltage control Controls of minimum voltage, maximum voltage, phase loss, asymmetry, minimum frequency, maximum frequency, with independent enable and delay Technical Features Flush mount 144 x 144 mm housing Plug in removable connections Phase to phase voltage measure inputs: 80-800VAC Voltage transformer programming TRMS voltage measure Frequency measurement 45-65Hz Control function: phase sequence, phase loss, max/min voltage, asymmetry, max/min frequency Two displays for voltage/frequency viewing 8 digital programming inputs 7 relay programmable outputs RS232 interface Description Catalogue Number Price $ Controller with interface panel TL101CIP 0.00 22 M MODbreak Transfer Switch Controller Type: TLP2 Timer / Relay logic controller The basic timer / relay logic controller includes the following standard features: Voltage and phase sequence sensing relay Time delay normal to emergency Time delay emergency to normal Common power supply relays Normal supply phase sequence relay 4 supply fuses Control wiring terminals A 4 position mode selector switch is provided loose (Manual / Automatic / Test / Off) Description Catalogue Number Controller for MODbreak Transfer Switches TLP2 23 Price $ M MODbreak Wiring Diagrams MB MOT Motor Operators MB MOT Motor Operator for MB2 and MB3 MCCBs Transfer Switch with remote electrical control - non automatic switching 24 M MODbreak Automatic Transfer switch TL101CIP Controller Wiring, components and dimensions 25 M MODbreak Automatic Transfer switch TL101CIP Controller Wiring, components and dimensions 26 M MODbreak Automatic Transfer switch TL101CIP Controller Wiring, components and dimensions 27 M MODbreak Automatic Transfer switch TLP2 Controller Wiring, components and dimensions 28 M MODbreak Automatic Transfer switch TLP2 Controller Wiring, components and dimensions 29 M MODbreak Automatic Transfer switch TLP2 Controller Wiring, components and dimensions 30 M MODbreak MCCB ratings chart MCCB Ampere Frames (AF) MCCB Types Poles 250 A 400A MB2 D 630A MB3 N D 3 or 4 800/1000/1250 MB3 N 3 or 4 D MB4 N 3 or 4 OCR (Over Current Relay) data Current Ratings of OCRs (A) OCR types 63, 80, 100, 125, 160, 200, 250 320, 400 630 A Thermal Magnetic & Electronic Thermal Magnetic & Electronic Thermal Magnetic & Electronic Thermal magnetic dial adjustment range 0.8 to 1.0 x In and 6 – 10 x Im MTX1 Electronic OCR data OCR adjustments Adjustment range (LT) Adjustment of LT time delay Ir LT Thermal memory Adjustment range (ST) Ir Short time setting time delay Fixed Instantaneous OCR setting AS/NZS 60947.2 IEC-60947-2 MCCB data Impulse withstand Voltage (kV) Rated Operational Voltage (V) (max) Rated Insulation Voltage (V) Standard and approvals 230 / 240 V AC 400 / 415 V AC 500 V AC Icu 550 V AC kA 600 V AC 690 V AC 250VDC (3P in series) 500VDC (3P in series) L/ R<15ms Ics as % lcu Mechanical Life span Electrical @1.0 In Operating Frequency (Hz) Total Opening Time Finger-proof Terminals Ambient Temperature Storage Temperature Mounting Positions 3 Pole Dimensions (W x D x H) 4 Pole Weight (kg) (3/4 Pole) Accessories Auxiliary Contact Trip Alarm Contact Internal Auxiliary & Trip Alarm Contact Shunt Release Under Voltage Release Extension handle Direct mount handle Handle mechanism padlock attachment Captive toggle padlock attachment Trapped key interlock 4 extension hdle Mechanical Interlock Motor operator for remote operation External Transfer switch controller Spreader bars for MCCB terminals Terminal covers - same width as MCCB Terminal covers - wide width Terminal covers - flush Interpole barriers – c/w with MCCB Chassis rated 800A for 250AF Chassis (high current) up to 630AF 0.8 to 1.0 x In and 6 – 10 x Im 0.8 to 1.0 x In and 6 – 10 x Im N 3 or 4 800, 1000, 1250 Electronic - via DIP switches 0.4 to 1.0 in steps of 0.05 or OFF 10s at 6 Ir or 3s at 6 Ir and 10s at 7.2 Ir or 3s at 7.2 Ir Enable / Disable (θ = ON or 0 = OFF) 1.5, 2.5, 4, 5.5, 6.5, 8 x Ir 100ms / Instantaneous or OFF 10 x In 10 x In 8 690 750 AS/NZS / IEC / CE 65 85 36 50 25 36 18 25 16 18 10 15 15 25 5 10 100% 100% 25000 10000 8 8 690 690 750 750 AS/NZS / IEC / CE AS/NZS / IEC / CE 65 85 65 85 36 50 36 50 25 36 25 36 15 20 15 20 12 18 12 18 8 15 8 10 15 25 15 25 5 10 5 10 100% 100% 100% 100% 15000 15000 4000 4000 50 / 60 <10 msec Via use of MB terminal covers -5°C to + 55°C - 35°C to + 70°C Vertical and 90° to the left and right 140 x 111.5 x 266 140 x 111.5 x 266 183.5 x 111.5 x 266 183.5 x 111.5 x 266 5.5 / 7.2 6 / 7/.8 105 x 96 x 179 140 x 95 x 179 2.5 / 3.3 1C/O or 2C/O 1C/O 1C/O + 1C/O 110 - 415V 50/60Hz, 110 - 220V DC 220 - 240 V 50 Hz √ √ √ √ X √ √ √ √ √ √ √ √ √ √ √ √ √ X √ √ √ √ √ √ √ √ √ √ √ 31 √ √ √ √ X √ √ √ √ √ √ √ √ √ √ 8 690 750 AS/NZS / IEC /CE 85 50 25 20 16 10 100% 8000 750 <20 msec 210 x 143 x 370 278 x 143 x 370 13 / 16 √ X √ √ X X X √ √ √ X X √ X X M MCCB to MCB Selectivity and Cascading Upstream THERMAL MAGNETIC MCCB, either 36kA or 50kA Downstream Thermal magnetic MCBs, MOD6 or DIN-T series 415V AC system voltage MB2 NTM MB3 NTM 250AF MCCB Thermal Magnetic, 50kA Downstream MOD6 6kA MCB's & RCBO's DIN-T 6kA MCB's & RCBO's DIN-T 10kA MCB's & RCBO's DIN-TH 10kA MCB's DIN-T 15kA MCB's Current Rating MB263N_TM 63A ≤32 25 / 25 25 / 25 25 / 25 25 / 25 MOD6 6kA MCB's & RCBO's DIN-T 6kA MCB's & RCBO's DIN-T 10kA MCB's & RCBO's DIN-TH 10kA MCB's DIN-T 15kA MCB's Notes: MB2100N_TM MB2125N_TM MB2160N_TM MB2250N_TM 100A 125A 160A 250A MB3320N_TM 320A MB3400N_TM 400A 25 / 25 -- / -- -- / -- 40 -- / 25 25 / 25 25 / 25 25 / 25 25 / 25 -- / -- -- / -- 50-63 -- / 25 -- / 25 25 / 25 25 / 25 25 / 25 -- / -- -- / -- ≤32 25 / 30 25 / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / -- 40 -- / 30 25 / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / -- 50-63 -- / 30 -- / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / -- ≤32 30 / 36 30 / 36 30 / 36 30 / 36 30 / 36 30 / 30 30 / 30 40 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 50-63 -- / 30 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 80 -- / -- -- / -- -- / 25 15 / 25 15 / 25 10 / 10 10 / 10 100 -- / -- -- / -- -- / -- 15 / 25 15 / 25 10 / 10 10 / 10 125 -- / -- -- / -- -- / -- -- / -- 15 / 25 10 / 10 10 / 10 ≤32 30 / 36 30 / 36 30 / 36 30 / 36 30 / 36 30 / 30 30 / 30 40 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 50-63 -- / 30 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 MB2 DTM Upstream Downstream 400AF MCCB Thermal Magnetic, 50kA MB3 DTM 250AF MCCB Thermal Magnetic, 36kA Current Rating MB263D_TM 63A ≤32 25 / 25 25 / 25 25 / 25 25 / 25 40 -- / 25 25 / 25 25 / 25 25 / 25 400AF MCCB Thermal Magnetic, MB2100D_TM MB2125D_TM MB2160D_TM MB2250D_TM 100A 125A 160A 250A 36kA MB3320D_TM 320A MB3400D_TM 400A 25 / 25 -- / -- -- / -- 25 / 25 -- / -- -- / -- 50-63 -- / 25 -- / 25 25 / 25 25 / 25 25 / 25 -- / -- -- / -- ≤32 25 / 30 25 / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / --- / -- 40 -- / 30 25 / 30 25 / 30 25 / 30 25 / 30 -- / -- 50-63 -- / 30 -- / 30 25 / 30 25 / 30 25 / 30 -- / -- -- / -- ≤32 30 / 36 30 / 36 30 / 36 30 / 36 30 / 36 30 / 30 30 / 30 40 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 50-63 -- / 30 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 80 -- / -- -- / -- -- / 25 15 / 25 15 / 25 10 / 10 10 / 10 100 -- / -- -- / -- -- / -- 15 / 25 15 / 25 10 / 10 10 / 10 125 -- / -- -- / -- -- / -- -- / -- 15 / 25 10 / 10 10 / 10 ≤32 30 / 36 30 / 36 30 / 36 30 / 36 30 / 36 30 / 30 30 / 30 40 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 50-63 -- / 30 -- / 30 30 / 30 30 / 30 30 / 30 30 / 30 30 / 30 The first number is the Selectivity kA rating / the second is the Cascade kA rating. Example: Selectivity 25 / 30 Cascade -- or --/-- Indicates no Selectivity or Cascade. Selectivity: The power contacts of the Upstream MCCB do not latch open when a fault is cleared by the downstream MCB. Cascading: The upstream MCCB assists the downstream MCB in clearing a higher level fault than the MCBs normal breaking capacity. 32 M MCCB to MCB Selectivity and Cascading Upstream ELECTRONIC MCCB either 36kA or 50kA Downstream Thermal magnetic MCBs, MOD6 or DIN-T series 415V AC system voltage MB2 NSE Upstream Downstream MOD6 6kA MCB's & RCBO's DIN-T 6kA MCB's & RCBO's DIN-T 10kA MCB's & RCBO's DIN-TH 10kA MCB's DIN-T 15kA MCB's MOD6 6kA MCB's & RCBO's DIN-T 6kA MCB's & RCBO's DIN-T 10kA MCB's & RCBO's DIN-TH 10kA MCB's DIN-T 15kA MCB's Notes: 400AF MCCB Electronic OCR, 50kA Current Rating MB240N_SE 40A MB2100N_SE 100A MB2250N_SE 160A MB2250N_SE 250A MB3400N_SE 400A ≤32 20 / 25 20 / 25 20 / 25 20 / 25 -- / -- 40 -- / 25 20 / 25 20 / 25 20 / 25 -- / -- 50-63 -- / 25 -- / 25 20 / 25 20 / 25 -- / -- ≤32 20 / 30 20 / 30 20 / 30 20 / 30 -- / -- 40 -- / 30 20 / 30 20 / 30 20 / 30 -- / -- 50-63 -- / 30 -- / 30 20 / 30 20 / 30 -- / -- ≤32 20 / 36 20 / 36 20 / 36 20 / 36 20 / 30 40 -- / 30 20 / 30 20 / 30 20 / 30 20 / 30 50-63 -- / 30 -- / 30 20 / 30 20 / 30 20 / 30 80 -- / -- -- / -- 10 / 15 10 / 15 10 / 10 100 -- / -- -- / -- 10 / 15 10 / 15 10 / 10 125 -- / -- -- / -- -- / -- 10 / 15 10 / 10 ≤32 20 / 36 20 / 36 20 / 36 20 / 36 20 / 30 40 -- / 30 20 / 30 20 / 30 20 / 30 20 / 30 50-63 -- / 30 -- / 30 20 / 30 20 / 30 20 / 30 MB2 DSE Upstream Downstream MB3 NSE 250AF MCCB Electronic OCR, 50kA MB3 DSE 250AF MCCB Electronic OCR, 36kA 400AF MCCB Electronic OCR, Current Rating MB240D_SE 40A MB2100D_SE 100A MB2250D_SE 160A MB2250D_SE 250A MB3400D_SE 400A ≤32 20 / 25 20 / 25 20 / 25 20 / 25 -- / -- 40 -- / 25 20 / 25 20 / 25 20 / 25 -- / -- 50-63 -- / 25 -- / 25 20 / 25 20 / 25 -- / -- ≤32 20 / 30 20 / 30 20 / 30 20 / 30 -- / -- 40 -- / 30 20 / 30 20 / 30 20 / 30 -- / -- 50-63 -- / 30 -- / 30 20 / 30 20 / 30 -- / -- ≤32 20 / 36 20 / 36 20 / 36 20 / 36 20 / 30 40 -- / 30 20 / 30 20 / 30 20 / 30 20 / 30 50-63 -- / 30 -- / 30 20 / 30 20 / 30 20 / 30 80 -- / -- -- / -- 10 / 15 10 / 15 10 / 10 100 -- / -- -- / -- 10 / 15 10 / 15 10 / 10 125 -- / -- -- / -- -- / -- 10 / 15 10 / 10 ≤32 20 / 36 20 / 36 20 / 36 20 / 36 20 / 30 40 -- / 30 20 / 30 20 / 30 20 / 30 20 / 30 50-63 -- / 30 -- / 30 20 / 30 20 / 30 20 / 30 The first number is the Selectivity kA rating / the second is the Cascade kA rating. Example: Selectivity 20 / 30 Cascade -- or --/-- Indicates no Selectivity or Cascade. Selectivity: The power contacts of the Upstream MCCB do not latch open when a fault is cleared by the downstream MCB. Cascading: An upstream MCCB assists a downstream MCB to clear a higher fault than the MCB’s breaking capacity. 33 36kA M MCCB to MCCB Selectivity and Cascade 36kA upstream ELECTRONIC MCCB Downstream Thermal magnetic or Electronic MCCBs 415V AC system voltage Upstream MCCB Downstream MCCB MB240D_SE MB240N_SE MB263D_TM MB263N_TM MB2100D_SE MB2100N_SE MB2100D_TM MB2100N_TM MB2100D_SE MB2100N_SE MB2100D_TM MB2100N_TM MB2100D_SE MB2100N_SE MB2125D_TM MB2125N_TM MB2125D_SE MB2125N_SE MB2160D_TM MB2160N_TM MB2160D_SE MB2160N_SE MB2250D_TM MB2250N_TM MB2250D_SE MB2250N_SE MB2250D_TM MB2250N_TM MB2250D_SE MB2250N_SE MB3320D_TM MB3320N_TM MB3400D_SE MB3400N_SE MB3630D_TM MB3630N_TM MB3630D_SE MB3630N_SE Notes: MB3 DSE MB4 DSE MCCB Electronic MTX1.0 OCR, 36kA MCCB Electronic MTX1.0 OCR, 36kA Current Rating MB3400D_SE 400 A MB3630D_SE 630 A MB4800D_SE 800 A MB41000D_SE 1000 A MB41250D_SE 1250 A 40 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36 63 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36 80 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36 100 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36 125 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36 160 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36 200 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36 250 A 20 / 36 20 / 36 36 / 36 36 / 36 36 / 36 400 A -- -- 36 / 36 36 / 36 36 / 36 630 A -- -- 36 / 36 36 / 36 36 / 36 The first number is the Selectivity kA rating / the second is the Cascade kA rating. Example: Selectivity 20 / 36 Cascade “--“ Indicates no Selectivity or Cascade. Selectivity: The Upstream MCCB power contacts do not latch open a fault is cleared by the downstream MCCB. Cascading: An upstream MCCB assists a downstream MCCB to clear a higher fault than the MCCB’s breaking capacity. 34 M MCCB to MCCB Selectivity and Cascade 50kA upstream ELECTRONIC MCCB Downstream Thermal magnetic or Electronic MCCBs 415V AC system voltage Upstream MCCB Downstream MCCB MB240D_SE MB240N_SE MB263D_TM MB263N_TM MB2100D_SE MB2100N_SE MB2100D_TM MB2100N_TM MB2100D_SE MB2100N_SE MB2100D_TM MB2100N_TM MB2100D_SE MB2100N_SE MB2125D_TM MB2125N_TM MB2125D_SE MB2125N_SE MB2160D_TM MB2160N_TM MB2160D_SE MB2160N_SE MB2250D_TM MB2250N_TM MB2250D_SE MB2250N_SE MB2250D_TM MB2250N_TM MB2250D_SE MB2250N_SE MB3320D_TM MB3320N_TM MB3400D_SE MB3400N_SE MB3630D_TM MB3630N_TM MB3630D_SE MB3630N_SE Notes: MB3 NSE MB4 NSE MCCB Electronic MTX1.0 OCR, 50kA MCCB Electronic MTX1.0 OCR, 50kA Current Rating MB3400N_SE 400 A MB3630N_SE 630 A MB4800N_SE 800 A MB41000N_SE 1000 A MB41250N_SE 1250 A 40 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50 63 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50 80 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50 100 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50 125 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50 160 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50 200 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50 250 A 20 / 50 20 / 50 36 / 50 36 / 50 36 / 50 400 A -- -- 36 / 50 36 / 50 36 / 50 630 A -- -- 36 / 50 36 / 50 36 / 50 The first number is the Selectivity kA rating / the second is the Cascade kA rating. Example: Selectivity 20 / 50 Cascade “--“ Indicates no Selectivity or Cascade. Selectivity: The Upstream MCCB power contacts do not latch open a fault is cleared by the downstream MCCB. Cascading: An upstream MCCB assists a downstream MCCB to clear a higher fault than the MCCB’s breaking capacity. 35 M MODcurve software MODcurve is a selectivity analysis software package developed by NHP specifically for the Australian and New Zealand markets. Designed around the MOD series of ACBs and MCBs as well as NHP’s extensive range of MCBs and fuses, MODcurve presents a user-friendly interface for conducting selectivity studies. (MODcurve V6, July 2013) Features: Simple and easy to use Can be used for coordination with upstream HV fuses Includes both MOD6 and Din T ranges of MCBs User defined devices can be added Ability to print report with single line diagram and circuit breaker settings included 36 M MODbreak Motor starting table Motor circuit application table for DOL starting General purpose circuit breaker selection for 3 Phase, 4 Pole, 415 V AC motors requiring short circuit protection. Breaker type and current rating (A) Motor kW Approximate FLC (Amps) 0.37 0.55 0.75 1.1 1.5 2.2 3.0 4 4.5 5.5 7.5 10 11 15 18.5 22 25 30 37 45 55 75 90 110 132 160 185 200 220 250 280 300 375 450 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 9 11 14 19 21 28 34 40 46 55 66 80 100 135 160 200 230 270 320 361 380 430 480 510 650 750 Notes: 1) 2) 3) 4) 5) 6) 7) 8) 9) MOD6 or DINT MCB 4 4 6 10 10 16 20 25 32 32 40 50 50 63 100 3) 125 3) 125 3) MB2 Thermal Magnetic MCCB MB2 Electronic MCCB 63 63 100 100 100 125 125 125 200 250 250 250 40 40 40 100 100 100 100 100 250 250 250 250 250 250 250 250 MB3 Thermal Magnetic MCCB MB3 Electronic MCCB 320 320 320 400 400 400 400 630 630 630 630 400 400 400 400 400 400 400 400 630 630 630 630 MB4 Electronic MCCB 800 800 800 800 800 1000 1000 The DOL table is based on holding 125 % FLC continuously and 600 % FLC for 10 seconds. The primary task of the above circuit breakers is to provide short circuit and cable protection. The motor starter would normally be supplied with an overload relay that will detect lower level current overloads or phase loss. 80, 100 and 125 amp refers to Din-T10H type. MOD6 MCBs are C curve MCBs. Din-T MCBs are C or D curve types, and either can be used for motor starting. Thermal magnetic MCCB current adjustment range 0.8 to 1.0 x In. Set magnetic trip to maximum or equivalent to 15 x motor FLC. Electronic MCCB base current adjustment ranges 0.4 to 1.0 x In. Set Short Time setting to maximum or equivalent to 15 x Motor FLC. Lower ampere rated MCCBs are possible for many applications. The above MCCB sizes generally provide additional ampere capacity. MODbreak MCCBs have a maximum instantaneous trip setting of 10 x In. Consideration should be given to the use of high efficiency motors with a short time current inrush of between 15 to 20 x In. Refer NHP for tables for reduced voltage, and Type 2 coordination motor starting. 37 M MODbreak Motor starting table Motor circuit application table for DOL FIRE PUMP starting duty Circuit breaker selection for 3 Phase, 4 Pole, 415 V AC motors requiring short circuit protection Breaker type and current rating (A) Motor kW Approximate FLC (Amps) 0.37 0.55 0.75 1.1 1.5 2.2 3.0 4 4.5 5.5 7.5 10 11 15 18.5 22 25 30 37 45 55 75 90 110 132 160 185 200 220 250 280 300 375 450 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 9 11 14 19 21 28 34 40 46 55 66 80 100 135 160 200 230 270 320 361 380 430 480 510 650 750 Notes: 1) 2) 3) 4) 5) 6) 7) 8) MOD6 or DINT MCB 4 6 6 10 10 20 25 32 32 32 50 63 63 100 125 3) 125 3) 125 3) MB2 Thermal Magnetic MCCB MB2 Electronic MCCB 40 40 40 100 100 100 100 100 250 250 250 250 250 250 63 100 100 125 125 160 160 250 250 MB3 Thermal Magnetic MCCB MB3 Electronic MCCB 320 320 400 400 400 400 400 630 630 630 400 400 400 400 400 630 630 630 MB4 Electronic MCCB 800 800 1000 1000 The DOL table is based on holding 125 % FLC continuously and 600 % FLC for 20 seconds. The primary task of the above circuit breakers is to provide short circuit and cable protection. The motor starter would normally be supplied with an overload relay that will detect lower level current overloads or phase loss. 80, 100 and 125 amp refers to Din-T10H type. MOD6 MCBs are C curve MCBs. Din-T MCBs are C or D curve types, and either can be used for motor starting. Thermal magnetic MCCB current adjustment range 0.8 to 1.0 x In. Set magnetic trip to maximum or equivalent to 15 x motor FLC. Electronic MCCB base current adjustment ranges 0.4 to 1.0 x In. Set Short Time setting to maximum or equivalent to 15 x Motor FLC. MODbreak MCCBs have a maximum instantaneous trip setting of 10 x In. Consideration should be given to the use of high efficiency motors with a short time current inrush of between 15 to 20 x In. Refer NHP for tables for reduced voltage, and Type 2 coordination motor starting. 38 M MODbreak technical data Watts Loss for Thermal Magnetic and Electronic MCCBs MCCB MB2 250 D/N_TM/SE MB3 400 D/N_TM/SE MB3 630 D/N_TM/SE MB4 800 D/N_TM/SE MB4 1000 D/N_TM/SE MB4 1250 D/N_TM/SE Watts loss per pole (W) 18 22 47 32 50 78 250A 400A 630A 800A 1000A 1250A Let-through and Cut-off values at 415V AC - Thermal Magnetic and Electronic MCCBs Cut-off (kA) MCCB MB2 250 D/N_TM/SE MB3 400 D/N_TM/SE MB3 630 D/N_TM/SE MB4 800 D/N_TM/SE MB4 1000 D/N_TM/SE MB4 1250 D/N_TM/SE 250A 400A 630A 800A 1000A 1250A 36 kA MCCB 19 25 30 - 50 kA MCCB 22 26 32 65 65 65 Let-through (x106 A2seconds) 36 kA MCCB 50 kA MCCB 1.4 1.6 2 2.4 3 3.6 26 30 30 Temperature Ratings for Thermal Magnetic MCCBs MCCB type MB2 125 D/N_TM MB2 160 D/N_TM MB2 200 D/N_TM MB2 250 D/N_TM MB3 400 D/N_TM MB3 630 D/N_TM 125A 160A 200A 250A 400A 630A 40 125 160 200 250 400 630 45 123 156 192 241 391 621 Ambient Temperature (oC) 50 55 60 121 119 118 152 148 144 184 176 168 232 224 215 382 373 364 612 603 594 65 116 140 160 206 355 585 70 114 136 152 198 346 576 Ambient Temperature (oC) 50 55 60 40 40 40 63 63 63 100 100 100 125 125 125 160 160 160 250 243 236 400 393 386 630 605 585 800 790 780 1000 1000 1000 1250 1235 1220 65 40 63 100 125 160 229 379 565 770 990 1205 70 40 63 100 125 160 222 372 545 760 980 1190 Temperature Ratings for Electronic MCCBs MCCB type MB2 250 D/N_SE MB2 250 D/N_SE MB2 250 D/N_SE MB2 250 D/N_SE MB2 250 D/N_SE MB2 250 D/N_SE MB3 400 D/N_SE MB3 630 D/N_SE MB4 1250 N_SE MB4 1250 N_SE MB4 1250 N_SE 40A 63A 100A 125A 160A 250A 400A 630A 800A 1000A 1250A 40 40 63 100 125 160 250 400 630 800 1000 1250 45 40 63 100 125 160 250 400 630 800 1000 1250 39 M MODbreak Characteristic curves Thermal Magnetic MCCBs MB2: 63A, 100A, 125A, 160A, 200A, 250A MB3: 400A / 630A 40 M MODbreak Characteristic curves Electronic MCCBs: 40A to 1250A MTX1: MB2 / MB3 / MB4 MTX1: MB2 / MB3 / MB4 MTX1 short Time setting: MB2 / MB3 / MB4 41 M MODbreak Electronic MCCB DIP Switch Setting Refer below for DIP switch positions and settings. Long Time Delay (LTD) Overload Protection (It = x IN) Thermal Memory The thermal memory feature is enabled or disabled by switching the DIP switch above the symbol θ on the OCR facia. Up = BYPASS (OFF) / Down = ON. The thermal memory feature is similar to the effects of hot and cold starting on an overload relay or thermal magnetic MCCB. Thermal memory can protect the system from thermal stresses generated by cumulative heating caused by cyclic overload conditions, thereby allowing the MCCB & system to return to a safe operating temperature. This function also allows for an optimisation of cables or busbar protection in the case of low amplitude repetitive faults. The “Advance tripping” of the MCCB also increases overall life and eliminates installation downtime. 42 M MODbreak Electronic MCCB DIP Switch setting Refer below for DIP switch positions and the resulting setting Inverse Overload Curve Type Selection Allows a degree of curve adjustment to allow for grading with upstream or downstream devices. Adjust the tripping characteristics of the MCCB for motor starting to take into account motor start up times. Refer MODbreak characteristic curves on previous pages for each setting characteristic. Short Time Delay (STD) Short Circuit Setting (IS = x IN) Time Delay for Short Circuit Protection Allows for the selection of a short delay just prior to the MCCB tripping if a short circuit occurs. 43 M About MODbreak Electronic MCCB OCRs Electronic OCR Layout: • • • • • • • Overload protection LT with selectable inverse time delay Adjustable Short Time ST characteristic Short circuit (ST) characteristic with selectable time delay LT and ST characteristic can be switched OFF Fixed instantaneous trip at 10 x In Thermal memory enable / disable True RMS sensing Overload Pick-Up Indication LED Improves uptime and productivity, via a visual indicator LED which can be used to monitor an unbalanced load so that proactive measures can be taken to avoid overload conditions. Overload pick-up LED Indicator % of IR 30% 85% 115% Overload pick-up LED indication Green LED Fast blinking of LED LED operates sequential ON/OFF operations LED Indicator • When the current flowing through the MCCB is less than 30% of the preset OCR current setting, the LED is OFF. • When the current reaches ≥ 30% of IN, the green LED is ON. • At 85% of Ir the OCR enters alarm mode and starts to blink OFF and ON. • At 115% of Ir the OCR enters into pick up mode and is indicated by sequential ON OFF operations of the LED. • Above the 115% level the OCR will trip the MCCB. 44 M About MODbreak Electronic MCCB OCRs Example of setting the LTD – Long Time Delay setting, which is used to reset the amp rating of the MCCB. EXAMPLE 250A Trip Unit The DIP switches allow LTD setting changes - refer examples below. The photo below shows the FACTORY DEFAULT settings. The raised white indicator indicates the up or down position of the DIP switch (switch in photo is shown down) EXAMPLE 250A Trip Unit To calculate the current setting, simply add up the DIP switch multiples. For example: when the DIP switches are switched DOWN the amp ratings are selected. • • • • 0.4 + 0.05 + 0.1 + 0.2 + 0.25 = 1, in other words, set at 100% of the trip unit rating = 250A. 0.4 + 0.05 + 0.2 = 0.65 x 250A = 162.5A 0.4 = 0.4 x 250A = 100A. If 0.4 and the other LT settings are switched to the upper position, the Long Time characteristic is switched OFF. The MCCB is now short time and instantaneous only. 45 M MODbreak MCCB Dimensions MB2: 16A to 250A M4 threaded mounting hole 28mm 26.5mm MB2: Thermal Magnetic MCCBs Electronic MCCBs 16A to 250A with optional spreader busbar tags 46 Rating Type 63A – 100A 125A – 250A 40A – 250A Thermal magnetic Thermal magnetic Electronic Dimension mm (A) 25.5 28 28 M MODbreak MCCB Dimensions MB3: 320A to 630A M5 threaded mounting hole Terminal width 30.5mm MB3: 320A to 630A with optional spreader busbar tags MCCB without spreader bars (top drawing) Dim A 400A Thermal Magnetic: 39mm 400A Electronic: 39mm 630A Thermal Magnetic: 43.3mm 630A Electronic: 43mm Dim B 400A Thermal Magnetic: 36.6mm 400A Electronic: 38mm 630A Thermal Magnetic: 39mm 630A Electronic: 39.3mm 47 MCCB with spreader bars (bottom drawing) MB3 MB4 A 39 41 B 37 38 C 45 55 D 324 344 E 370 390 F 13 11 M MODbreak MCCB Dimensions MB4: 800A, 1000A and 1250A Connection tag height from rear of MCCB is 46.3 mm Door Mounting cut-out dimensions MB4: 800A, 1000A and 1250A with optional extension busbar tags. 10.5 24 10.5 Bar size: 116 x 45 x 15 mm Material: Tinned copper 14 11mm θ 116 8 113mm θ slotted 15 13mm θ 22.5 22.5 45 48 M MODbreak MCCB Dimensions Direct mount handle mounting L1 L2 / L3 L4 / L5 MCCB Type MB2 MB3 MB4 = Mounting depth MCCB + handle = Door or escutcheon cut-out = Breaker position relative to cut-out 49 L1 122 146 156 L2 96 121 121 L3 63 87 87 L4 53 78 78 L5 66 82 82 M MODbreak MCCB Dimensions Extension handle mounting MCCB Type MB2 MB3 MB4 MB4 - example 50 L1 202 233 302 L L1 = 152 L1 = 183 L1 = 252 L2 27 39 69 L3 84 122 170 M MODbreak MCCB Dimensions MB2 MCCB with motor operator fitted MB3 MCCB with motor operator fitted 51 M MODbreak MCCB Dimensions Mechanical interlock and mounting plate MB2 MB3 52 M MODbreak MCCB Dimensions MB2 Terminal covers – 250AF MCCBs Typical internal construction for MODbreak terminal covers 53 M MODbreak MCCB Dimensions MB3 Terminal covers - 630AF MCCBs MB4 Terminal covers - 1250AF MCCBs 54 M MODbreak MCCB Dimensions Manual Transfer Switch 250AF – 3 Pole Manual Transfer Switch 250AF – 4 Pole 55 M MODbreak MCCB Dimensions Manual Transfer Switch 630AF – 3 Pole Manual Transfer Switch 630AF – 4 Pole 56 M MODbreak MCCB Dimensions Basic Transfer Switch 250AF – Motorised 3 Pole MB2MOTOR240VAC Motor operators mounted on MCCBs (240VAC) x 2 Basic Transfer Switch 250AF – Motorised 4 Pole MB2MOTOR240VAC Motor operators mounted on MCCBs (240VAC) x 2 Note1: 57 Escutcheon height is to the underside of the escutcheon. M MODbreak MCCB Dimensions Basic Transfer Switch 630AF – Motorised 3 Pole MB3MOTOR240VAC Motor operators mounted on MCCBs (240VAC) x 2 Basic Transfer Switch 630AF – Motorised 4 Pole MB3MOTOR240VAC Motor operators mounted on MCCBs (240VAC) x 2 Note1: 58 Escutcheon height is to the underside of the escutcheon. M MODBreak Over-Current Relay (OCR) Tester General information MBOCRTESTER facia shown above NHP Catalogue Number: MBOCRTESTER (code: ST374980000 / DNT20) NHP MODBreak MCCBs use OCR types “MTX1” which are indicated below The MBOCRTESTER is suitable for MODbreak MCCBs (not ACBs) The MBOCRTESTER tester kit consists of: 1 tester. (The tester will need a 240V GPO plug adaptor or a local GPO plug to replace the plug the tester comes with) 2 x D shell 9 pin serial connector, to go from the tester to the MCCB (1 spare lead) 1 x D shell 9 pin serial connector (For an older OCR series not sold by NHP) MODbreak electronic MCCB OCR Tester MODBreak connector lead Spare connector For other MCCB types (ignore this) Connector lead plugs into MTX1 OCR test socket connection, and to OCR tester’s rear 9 pin serial port. 59 M MODBreak Over-Current Relay (OCR) Tester Using the MTX1.0 OCR Release Setting Checker Test Kit S1 & S2 are OCR checker dial settings that are dependent on the MCCB OCR DIP switch settings The rocker switch has 3 positions: TEST / OFF / AUX. Power. When the switch is in AUX mode, the GREEN LED will glow indicating AUX supply is provided to the tester. The RED LED & display will not be on. When the switch is in TEST mode, the RED LED and display will be on, indicating that the tester is ready to test. The GREEN LED will not be on, ensuring that only one mode can be activated at any time. Ensure that the MCCB toggle is in ON position when the settings are checked. For setting S1 Over Current Relay (OCR) Setting MTX1 Over Current Relay Long Time Characteristic 50 70 100 OFF Setting on OCR Tester Short Time Characteristic 8 5.5 4 OFF S1 S2 A A A A A A A A OCR Output At 20mS: OCR trips within 0.06s or 0.00s on display At 100mS: OCR trips within 0.13s on display At 200mS: OCR trips within 0.23s on display For setting S2 Over Current Relay (OCR) Setting MTX1 Over Current Relay Setting on OCR Tester Long Time Characteristic 60 80 40 60 40 Short Time Characteristic OFF OFF OFF OFF 2.5 60 100 2.5 1.5 S1 S2 A A A A A B A E H A A A C A 60 OCR Output OCR trips within 20 to 50 seconds OCR trips within 86 to 128 seconds OCR trips within 7 to 12 seconds OCR trips within 7 to 12 seconds At 20mS: OCR trips within 0.06s or 0.00s on display At 100mS: OCR trips within 0.13s on display At 200mS: OCR trips within 0.23s on display M MODBreak Installation Instructions: MB2, MB3, MB4 MCCBs MB2, MB3, MB4 – General installation precautions MB2, MB3, MB4 – MCCB toggle operation and tripping the MCCB 61 M MODbreak Installation Instructions MB2 Interpole barriers Exhaust gas vents from the line side (top) of the MCCB, which is the opposite end to where the current adjustment dials are located. MB3 Interpole barriers Exhaust gas vents from the line side (top) of the MCCB, which is the opposite end to where the current adjustment dials are located. 62 M MODbreak Installation Instructions MB4 Interpole barriers Exhaust gas vents from the line side (top) of the MCCB, which is the opposite end to where the current adjustment dials are located. MB2 Mounting orientation and termination mounting, torque, capacity and weight Mount in any one of these three orientations only 63 M MODbreak Installation Instructions MB3 Mounting orientation and termination mounting, torque, capacity and weight MB4 Mounting orientation and termination mounting, torque, capacity and weight 64 M MODbreak Installation Instructions MB2, MB3 – Adjustment of THERMAL MAGNETIC trip unit MB2, MB3, MB4 – Adjustment of ELECTRONIC Over Current Relay Refer previous pages for more detailed setting diagrams 65 M MODbreak Installation Instructions MB2, MB3, MB4 – Accessory cover removal, internal accessory mounting and wire routing 66 M MODbreak Installation Instructions MB2, MB3, MB4 – Internal accessory cover fitting MB2, MB3, MB4 – Internal accessory removal 67 M 68
© Copyright 2024 ExpyDoc