NeeserShortCircuit CurrentRating

4/1/2014
Equipment Short-Circuit Current
Rating and Available Fault Current
Dan Neeser – Field Application Engineer
Eaton’s Bussmann Business
[email protected]
© 2013 Eaton. All rights reserved.
Agenda
• Interrupting rating (IR)
• Series Ratings (SR)
• Short-Circuit Current Ratings (SCCR)
• Equipment Marking and Installation Requirements
• Fault Current Calculations
• Industrial Control Panels
• UL 508A Supplement SB
© 2013 Eaton. All rights reserved.
2
Interrupting Rating
• NEC® Article 100 Definition
• Highest current an OVERCURRENT DEVICE
(fuse or circuit breaker) is rated to safely interrupt.
• Self protection rating only
• NEC® 110.9 Interrupting Rating.
• Requires the overcurrent device to have an
interrupting rating not less than the maximum
available fault current.
• The maximum fault current must be calculated and
varies based on system size/location.
• Similar Requirements in OSHA 1910.303(b)(4)
© 2013 Eaton. All rights reserved.
3
1
4/1/2014
Interrupting Rating - Proper Application
Overcurrent device must have interrupting rating adequate for point of
application. Circuit breakers IR varies by voltage and circuit breaker type.
Fuses typically have high IR at rated voltage.
© 2013 Eaton. All rights reserved.
4
Interrupting Rating
• NEC 110.9: Device interrupting rating MUST
be equal to or greater than the maximum
available fault current.
• Chapter 1 Video Clips - Interrupting Rating
© 2013 Eaton. All rights reserved.
5
Series Rated Systems
A combination of:
- Circuit breakers / circuit breakers
OR
- Fuses / circuit breakers …
that can be applied at available fault levels
above the interrupting rating of the load side
circuit breaker, but not above that of the main
or line side device.
Downstream device will ALWAYS be a circuit breaker
© 2013 Eaton. All rights reserved.
6
2
4/1/2014
Series Rated Systems
• CB/CB
• Fuse/CB
© 2013 Eaton. All rights reserved.
7
Series Rated Systems
• NEC® 240.86(A) Selected Under Engineering
Supervision in Existing Installations
• The series rated combination devices must be selected
by licensed, professional engineer.
• Requires Documentation and Stamp.
• Series combination rating and upstream device must be
field marked on end use equipment.
• Downstream circuit breaker must remain passive.
• NEC® 240.86(B) Tested Combinations
• The combination of line side and load side devices must
be tested and marked on the end-use equipment
(panelboards & switchboards).
© 2013 Eaton. All rights reserved.
8
Series Rated Systems
• Additional Limitations and Requirements
• Labeling Requirements
• Manufacturer – NEC® 240.86(B)
• Field Marking – NEC® 110.22(B)&(C)
• Motor Contribution Limitations
• NEC 240.86(C)
• Motor FLA cannot exceed 1% of IR of protected CB.
• Lack of Selective Coordination
© 2013 Eaton. All rights reserved.
9
3
4/1/2014
Current Limitation
• A current limiting
fuse will clear a
fault within one
half of a cycle.
• Thermal energy is
proportionate to the
square of “RMS”
current multiplied by
the time (Irms2t)
• Mechanical stresses
are proportionate to
the square of “peak”
current multiplied by
the time (Ip2t)
© 2013 Eaton. All rights reserved.
10
Current Limitation
• Conductor protection for fault of 45kA/480V (26kA with
conductor) with non-current-limiting device (1 cycle) vs.
current-limiting device (>1/2 cycle)
© 2013 Eaton. All rights reserved.
11
Short-Circuit Current Ratings
• NEC® Article 100 Definition
• The highest current EQUIPMENT can withstand without extensive
damage (fire or shock hazard).
• Also known as component protection
• May be based on a specific type of overcurrent device
• NEC® 110.10 Circuit Impedance, Short-Circuit Current Ratings,
and Other Characteristics.
• Requires the equipment to have a short circuit current rating
not less than the maximum available fault current.
• The maximum fault current must be calculated and varies
based on system size/location.
• Similar Requirements in OSHA 1910.303(b)(5)
© 2013 Eaton. All rights reserved.
12
4
4/1/2014
SCCR Marking Requirements
• 430.8 – Marked on motor controllers
• 440.4(B) – Marked on HVAC equipment
• 409.110(3) – Marked on industrial control panels
• 409.22 – Fault current cannot exceed marked SCCR
• 670.3(A)(4) – Marked on industrial machinery control
panel
• 670.5 – Fault current cannot exceed marked SCCR
• UL 508A, Supplement SB is an approved method to
determine SCCR for industrial control panels and
industrial machinery control panels
• Typically Equipment is rated only 5kA unless higher
ratings are requested!
© 2013 Eaton. All rights reserved.
13
Fault Current Marking Requirement
• 110.24 Available Fault Current.
• (A) Service equipment must be marked with
the maximum available fault current and
date of calculation
• (B) If fault current increases due to system
modification, the marking must be updated.
© 2013 Eaton. All rights reserved.
14
How to Comply?
Engineer – Calculate
All equipment must comply with:
NEC 110.9 (IR) &110.10 (SCCR)
Isc = 60,142 A
Contractor – Label
Max Avail. Fault Current = 58,524 A
Service Equipment
Date Determined/Calculated: 9/2010
Required per NEC 110.24
Isc = 38,525 A
HVAC
SCCR = 40kA
Isc = 42,153 A
Isc = 27,532 A
Industrial Machinery Panel
Industrial Control Panel
SCCR = 65kA
SCCR = 30kA
© 2013 Eaton. All rights reserved.
Isc = 18,752 A
Motor Controller
SCCR = 25kA
15
5
4/1/2014
Fault Current Calculations
• To determine the fault current:
• Draw the one-line diagram
• Identify sources of short-circuit current (utility,
generation, motors)
• Include system component information
(tranformers, conductors, busway, overcurrent
devices are not considered)
• Use calculation method (ohmic, per unit, point-topoint, software)
• Use “typical” fault current values as a reference
only.
© 2013 Eaton. All rights reserved.
16
Typical Short-Circuit Current Values
• Short-Circuit Current at service entrance equipment
varies by type/size of system:
• Small residential systems (100A to 200A) – 10,000A to
15,000A or less
• Small commercial building systems (400A to 800A) –
20,000A to 30,000A
• Larger commercial and manufacturing building systems
(2,000A to 3,000A) - 50,000A to 65,000A
• Higher short-circuit currents are possible where low
impedance (energy-efficient) transformers are used (or
where larger transformers (kVA) feed multiple services.
• Commercial buildings directly connected to utility “grid
system” – 200,000A or greater
© 2013 Eaton. All rights reserved.
17
Short-Circuit Current Factors
• Typically
highest at
service point
• Decreases in
downstream
equipment
(due to
impedance of
transformers
and
conductors)
© 2013 Eaton. All rights reserved.
18
6
4/1/2014
Calculation Example
• 480V/3000A Service supplied from 2500 kVA
Transformer
• Find Isc at Transformer Secondary & Service
Equipment
480V, 3000A Service Equipment
Service Transformer
Isc = 58,524A
2500 kVA
13.2kV – 480V
5% Impedance
Isc = 60,142 A
7 – 600 Cu kcmil/phase
25 Feet in PVC
© 2013 Eaton. All rights reserved.
19
Calculation Example
• Step One: Calculate Secondary FLA of
Transformer (3 phase)
IFLA =
KVA X 1000
EL-L X 1.732
KVA = KVA of Transformer
EL-L = Secondary Phase to Phase voltage
© 2013 Eaton. All rights reserved.
20
Calculation Example
ISC
2500 KVA Transformer
13.2kV - 480V, 3 Phase
Z = 5%
IFLA =
2500 X 1000
480 X 1.732
IFLA = 3007 A
© 2013 Eaton. All rights reserved.
21
7
4/1/2014
Calculation Example
• Step Two: Calculate Multiplier
• Z = Impedance of Transformer, refer to transformer
nameplate or manufacturer data
Mult =
Mult =
100
%Z
100
5
Mult = 20
© 2013 Eaton. All rights reserved.
22
Calculation Example
• Step Three: Calculate Secondary Short
Circuit Current
ISC = IFLA X Mult
ISC = 3007 X 20
ISC = 60,140 A
© 2013 Eaton. All rights reserved.
23
Calculation Example
• Calculate Short Circuit Current at 480V
Switchgear
480V
Switchgear
7 – 600 Cu kcmil/phase
25 Feet in PVC
ISC = 60,140A
© 2013 Eaton. All rights reserved.
24
8
4/1/2014
Calculation Example
• Isc known from previous calculation
• Calculate multiplier for Cable
• Step One: Calculate f value
ISC 480V SWGR = ISC X Mult
© 2013 Eaton. All rights reserved.
25
Calculation Example
• Step One: Calculate f value
f =
1.732 X L X ISC
C X EL-L
L = Length of conductor
ISC = Short-circuit current at beginning of circuit
C = “C” Value Constant for Cable
From Table. Multiply by # of runs
EL-L = Phase to Phase Voltage
© 2013 Eaton. All rights reserved.
26
Calculation Example
• C Value – 600 kcmil, CU, PVC = 28,033
© 2013 Eaton. All rights reserved.
27
27
9
4/1/2014
Calculation Example
• Step One: Calculate f Value
• L = 25 Feet
• ISC = 60,140 A
• C = 7 X 28,033 - See “C” Value Table
• EL-L = 480V
f =
1.732 X 25 X 60,140
7 X 28,033 X 480
= 0.0276
© 2013 Eaton. All rights reserved.
28
Calculation Example
• Step Two: Use Calculated f Value
• Calculate Multiplier
Mult =
Mult =
1
1+f
1
1 + 0.0276
= 0.9731
© 2013 Eaton. All rights reserved.
29
Calculation Example
• Calculate Short Circuit Current at 480V
Switchgear
ISC 480V SWGR = ISC X Mult
ISC 480V SWGR = 60,140 X .9731
ISC 480V SWGR = 58,522 A*
* Add motor contribution if present
© 2013 Eaton. All rights reserved.
30
10
4/1/2014
What if the System Changes?
480V, 4000A Service Equipment
Service Transformer
Isc = 70,587A
3000 kVA
13.2kV – 480V
5% Impedance
Isc = 72,171 A
9 – 600 Cu kcmil/phase
25 Feet in PVC
480V, 3000A Service Equipment
Service Transformer
Isc = 72,667A
2500 kVA
13.2kV – 480V
4% Impedance
Isc = 75,178 A
7 – 600 Cu kcmil/phase
25 Feet in PVC
© 2013 Eaton. All rights reserved.
31
Bussmann Short-Circuit Calculator
• NEW version
• Apple or Android Apps
• Web (run from homepage
after entering contact info)
© 2013 Eaton. All rights reserved.
32
Fault Current Calculation Example
Isc = 50,000 A
Marking Required per NEC 110.24
Isc = 54,688 A
Isc = 42,575 A
Main
Switchboard
SCCR=200kA
Fault current at RTU1 > SCCR of RTU1
CODE VIOLATION!
Isc = 8,562 A
HVAC RTU1
SCCR = 5kA
© 2013 Eaton. All rights reserved.
33
11
4/1/2014
How to Determine SCCR?
• Short-Circuit Current Rating (SCCR)
• Can be established by testing during the listing
and labeling process
OR
• Can be determined using an approved
(calculation) method
•
UL 508A Supplement SB is an approved method
(industrial control panels and industrial machinery
control panel)
•
AHJ Approved Method
• NRTL field evaluation can also be used.
© 2013 Eaton. All rights reserved.
34
Industrial Control Panel SCCR
• Industrial Control Panel.
An assembly of two or more components consisting of one of the
following:
1) power circuit components only, such as motor controllers,
overload relays, fused disconnect switches, and circuit breakers;
2)control circuit components only, such as push buttons, pilot
lights, selector switches, timers, switches, and control relays;
3) a combination of power and control circuit components. These
components, with associated wiring and terminals, are mounted
on, or contained within, an enclosure or mounted on a subpanel.
The industrial control panel does not include the controlled
equipment.
35
© 2013 Eaton. All rights reserved.
35
UL 508A Supplement SB
• What Needs to be Analyzed per UL 508A,
Supplement SB?
• All power circuit components (SB 4.1)
• Feeder and branch circuit components that supply power to
loads (motors, lighting, heating and appliances)
• Includes disconnect switches, fuses, circuit breakers, load
controllers, overload relays, power distribution/terminal
blocks, bus bars, etc.
• Control circuit components are NOT required to be
analyzed
• Pushbuttons, pilot lights, selector switches, timers, control
relays, etc.
© 2013 Eaton. All rights reserved.
36
12
4/1/2014
UL 508A Supplement SB
• How to Determine Component SCCR (SB4.2.2)?
• The SCCR marked on the component or on instructions.
• The SCCR determined by the voltage rating of the
component and the assumed short circuit current from
Table SB4.1.
• or
• The SCCR for a load controller, motor overload relay, or
combination motor controller that has been investigated
in accordance with the performance requirements,
including short circuit test requirements for standard fault
currents or high fault currents specified in the Standard
for Industrial Control Equipment, UL 508, and described
in the manufacturer’s procedure.
© 2013 Eaton. All rights reserved.
37
UL 508A Supplement SB
• What are the Rules (Sweep 1)?
• Lowest component SCCR limits
assembly SCCR unless:
• Combination ratings can be used to
increase branch circuit component ratings
(SB 4.2.2)
• Component with marked/specified OCPD
• Check with component manufacturer for
combination ratings
© 2013 Eaton. All rights reserved.
38
Combination Ratings - Branch
Component SCCR
OCPD I.R.
Nameplate
Voltage:
480
SCCR:
100kA
• Use combination
ratings with
specified/marked
OCPD to fix low rated
branch components
Combination ratings of overcurrent protective devices and components can be used
© 2013 Eaton. All rights reserved.
39
13
4/1/2014
Combination Ratings - PDBs
PDBFS220 (4 – 14 Load Side
Conductors) – 100kA with 175A
Class J fuse or less
40
© 2013 Eaton. All rights reserved.
40
Combination Ratings – Motor Starter &
Contactor
© 2013 Eaton. All rights reserved.
41
Combination Ratings - MMP
• OL Protection Only
• Fuse or Circuit Breaker Required for
SC Protection
• Suitable for Group Installations
• Straight Ratings (480V)
© 2013 Eaton. All rights reserved.
42
14
4/1/2014
Combination Ratings – Type E/F
• Combination Motor Controller
• SC & OL Protection
• Line Side Adapters Required
• Slash Ratings (480/277V)
© 2013 Eaton. All rights reserved.
43
UL 508A Supplement SB
• What are the Rules (Sweep 1)?
• Lowest component SCCR limits assembly
SCCR unless:
• Feeder components are used that limit the shortcircuit current reducing the need for higher branch
circuit component SCCR (SB 4.3)
• Current limiting overcurrent protective devices
• Transformers rated 10kVA or less
© 2013 Eaton. All rights reserved.
44
Feeder vs. Branch Circuits
Feeder Circuit
Branch
Circuit
Branch
Circuit
© 2013 Eaton. All rights reserved.
45
15
4/1/2014
Use of CL Devices - OCPD
• CL Device must be in the feeder circuit
• For CL Fuses or Circuit Breakers
• Use PEAK Let-through, Not RMS Let-Through (more
conservative)
• Fuses - cannot use manufacturer specific fuse data –
only tables based on performance requirements from
UL 248 (more conservative - apply to all
manufacturers)
• Circuit Breakers - must be Listed and marked “currentlimiting” and use published let-thru curves (most circuit
breakers are not CL)
• Can only raise downstream BRANCH circuit
components (not overcurrent protective devices –
fuses/circuit breaker IR or Combination motor
controllers SCCR)
© 2013 Eaton. All rights reserved.
46
Use of CL Devices - OCPD
Component SCCR
OCPD I.R.
Nameplate
Voltage:
480
SCCR:
14kA
F
• Current limiting
feeder OCPD
can be used to
increase branch
component
SCCR.
B
Use of CL OCPD can only fix components
© 2013 Eaton. All rights reserved.
47
Use of CL Devices - Transformers
• CL Device must be in the feeder circuit
• For Transformers
• If 10kVA with secondary devices (components and
overcurrent devices) of 5kA or higher, apply the IR
of the primary overcurrent protective device
• If 5kVA (120V Secondary) with secondary devices
(Components and overcurrent devices) of 2kA or
higher, apply the IR of the primary overcurrent
protective device
© 2013 Eaton. All rights reserved.
48
16
4/1/2014
Use of CL Devices - Transformers
Component SCCR
OCPD I.R.
Nameplate
Voltage:
480
SCCR:
200kA
10 kVA
• Transformers can be used to
limit the short-circuit current
available
• If 10kVA & sec comp = 5kA+
• If 5kVA/120V & sec comp = 2kA+
• Then assign entire circuit I.R. of
primary overcurrent device
Use of Small Transformers (10kVA or less) can increase secondary component/OCPD ratings
© 2013 Eaton. All rights reserved.
49
UL 508A Supplement SB
• What are the Rules (Sweep 2)?
• Lowest overcurrent protective device interrupting
rating (or SCCR for some devices) always limits
assembly SCCR
• All Feeder and branch circuit overcurrent devices
• Tested series combination ratings or series ratings
(fuse-circuit breaker or circuit breaker-circuit breaker)
are NOT allowed.
• Branch circuit overcurrent devices tapped from the feeder
circuit supplying a control circuit.
• Supplemental protective devices protecting the control
circuit transformer in a motor branch circuit.
© 2013 Eaton. All rights reserved.
50
Why High SCCR?
• NEC & Equipment standards only require the
SCCR to be marked
• NEC requires the marked value to be adequate
for the maximum available fault current
• Although not required, high SCCR is often
preferred
• Flexibility of application
• Multiple installations
• Fault current unknown
• Insufficient SCCR can delay installation
© 2013 Eaton. All rights reserved.
51
17
4/1/2014
Fix It - Solutions
• High I.R. Protective
Devices
• Class R
• Class J
• Class J Drive Fuse
• Class T
• Class CC
• CubeFuse
• High Speed
• High IR/CL CBs
© 2013 Eaton. All rights reserved.
52
Fix It - Solutions
• High SCCR Components
© 2013 Eaton. All rights reserved.
53
Terminal Blocks & Power Distribution Blocks
• Power Distribution
Blocks
• High SCCR.
• Feeder (larger)
spacings.
• UL Listed
• Terminal Blocks
• High SCCR
• Branch Circuit
Spacings
• UL Recognized
© 2013 Eaton. All rights reserved.
54
18
4/1/2014
Class J
• “Junior”
• Class J – Low-Peak®
• LPJ-(AMP)SP
• 600V, 1A – 600A, 300kA
• Characteristics
• Dual Element Time Delay
• Better time delay than CC
• Less time delay than RK1/RK5
• Very current limiting
• Smaller than RK1/RK5
• Open fuse indication Optional
• Applications
• Feeder and branch circuits
• OEM & Building Systems
• Type 2 Protection
© 2013 Eaton. All rights reserved.
55
New Fuseblocks
•
•
•
•
Class R, H, K & J fuse blocks (70A+)
High SCCR
Modular, snap-together design
UL Listed with creepage and clearance
distances for feeder and branch circuits.
200A+ meet requirements for service
entrance, feeder, and branch circuits.
• Optional high-clarity, see-through, fingersafe covers with optional blown fuse
indication
• Built-in lockout-tagout feature
The only modular design on the market with finger-safe covers across the entire line
© 2013 Eaton. All rights reserved.
56
New PDB Fuseholder
• UL Recognized Class J fuseholder with PDB
• Optional IP20 Finger-Safe Covers
• 100A, 200A or 400A, 1Pole – 3Pole
• 50% space savings, 33% labor savings
The only combination PDB/Fuseblock on the market
© 2013 Eaton. All rights reserved.
57
19
4/1/2014
Class CF
• “CUBE FUSE”
• Class CF - TCF(amp), TCF(amp)RN or
FCF(amp)RN
• TCF - 600Vac/300Vdc, 1-100A, 300kA/100kA
• FCF - 600Vac/dc, 1-100A 200kA/50kA
• Characteristics
•
•
•
•
•
•
DE Time Delay or Fast Acting
Class J Performance
Very Current Limiting
Small physical Size
Finger safe IP20
Optional Indicating version time-delay only
• Applications
• General purpose; e.g. motor circuits (Type 2
Protection, transformers, heaters, feeders and
branch circuit protection
© 2013 Eaton. All rights reserved.
58
Class CC
• “Control Circuit” or “Charlie Chaplin” (little hat)
• Class CC - General Features
•
•
•
•
600V, up to 30A
200kA Interrupting rating
Very Current Limiting
Space Saving Design - 13/32” X 1½”
• Grooved ferrule provides rejection feature from
supplementary fuses with same dimensions
(midget fuses) when Class CC fuseholders are
used
• Offer 3 different fuse types
• Time delay (for motor circuit: LP-CC)
• Time delay (for control transformer primary: FNQ-R)
• Non-time delay (Non-inductive loads: KTK-R)
© 2013 Eaton. All rights reserved.
59
Compact Circuit Protector
• Compact Circuit
Protector (CCP)
• 200kA SCCR
• 600V
• 30A with Class CC
Fuses
• 30A, 60A or 100A with
CUBEFuse®
• Smallest fusible
disconnect available
• Finger-safe design
• UL98 branch circuit
disconnect
• PROVIDES
ISOLATION OF
CIRCUITS AND
LOCK-OUT/TAG-OUT
© 2013 Eaton. All rights reserved.
60
20
4/1/2014
Bussmann Surge Protection Devices
•
UL Product Lineup
•
•
•
•
•
UL 1449 3rd Edition
Recognized Di-rail
SPDs
Surge Protector for
Single, Split, Wye
and Delta Phases
120V to 600V
Type 2 SPD
Data/Field Bus Product
Lineup
•
•
•
•
LV/Controls Product
Lineup
•
•
•
•
Surge Protection for
low voltage/Control
Applications
24v to 240v AC and
DC
Type 2 or 3 SPD
Data communication SPD
© 2013 Eaton. All rights reserved.
UL 497B Listed
BNC Coax Cable,
RJ45 / Ethernet Data
Cable and Universal 4Pole versions available
for popular data signal
applications
DIN-Rail mount makes
installation easy
Universal 4-pole SPD
is easy to apply in
most instrumentation
applications up to
180V
61
Questions?
© 2013 Eaton. All rights reserved.
21