ELECTRIC DUCT HEATERS

Circular electric duct heaters
EKA
EKA (-NV,-NI,-NIS,-PTC) 100-0.3-1f
EKA Circular electric duct heater
NV With integrated temperature control, internal setpoint
With integrated temperature control, external remote setpoint must
be connected
NIS With integrated temperature control The external control signal (0-10V)
is needed.
NI
PTC With air flow sensor
100 Heater diameter [mm]
0.3 Heating power [kW]
1f
Number of phases
Type
IP class
Heating power
[kW]
Voltage
V/50Hz
Suitable controller
EKR
Accessories
EKR
EKR
EKR
EKR
EKR
EKR
EKR
EKR
Duct temperature sensor TJK 10K
Controller for electric heaters
EKR:
EKR
EKR
EKR
EKR
EKR
EKR
EKR30, EKR30P
EKR
EKR
ELECTRIC DUCT HEATERS
EKR
EKR
EKR
EKR
EKR
EKR
EKR15.1, EKR15.1P
EKR
EKR
EKR
EKR
Heaters conform with IEC 60335-2-30 : 1996, EN 600335-2-30 : 1999, EN 61010-1+ A2 : 2000, EN 50081-2 : 1995,
EN 55011 : 1999+ A1 : 2001 standards and are CE marked.
EKR 6.1
Circular electric duct heaters
EKA
All EKA duct heaters has two-stage overheat protection:
1)the first stage switches on when the temperature reaches 50°C
(Resets automatically).
2)the second stage switches on when the temperature reaches 100°C
Heating power
[kW]
Voltage
V/50Hz
Suitable controller
EKR
EKA 250-1,5-1f
1,5
1 ~ 230
EKR
EKA 250-2,0-1f
2
1 ~ 230
EKR
EKA 250-3,0-1f
3
1 ~ 230
EKR
EKA 250-3,0-2f
3
2 ~ 400
EKR
EKA 250-5,0-2f
5
2 ~ 400
EKR
EKA 250-6,0-2f
6
2 ~ 400
EKR
EKA 250-3,0-3f
3
3 ~ 400
EKR
EKA 250-6,0-3f
6
3 ~ 400
EKA 250-9,0-3f
9
3 ~ 400
EKA 315-1,2-1f
1,2
1 ~ 230
EKA 315-1,5-1f
1,5
1 ~ 230
EKA 315-2,0-1f
2
1 ~ 230
EKA 315-3,0-2f
3
2 ~ 400
EKA 315-5,0-2f
5
2 ~ 400
EKA 315-6,0-2f
6
2 ~ 400
EKA 315-6,0-3f
6
3 ~ 400
EKR
EKA 315-9,0-3f
9
3 ~ 400
EKR
EKA 315-12-3f
12
3 ~ 400
EKR
EKA 400-3,0-2f
3
2 ~ 400
EKR
EKA 400-5,0-2f
5
2 ~ 400
EKR
EKA 400-6,0-2f
6
2 ~ 400
EKR
EKA 400-6,0-3f
6
3 ~ 400
EKR
EKA 400-9,0-3f
9
3 ~ 400
EKR
EKA 400-12-3f
12
3 ~ 400
EKR
EKA 400-15-3f
15
3 ~ 400
EKR
Type
IP class
Accessories
EKR
EKR
EKR
EKR
EKR
EKR
EKR
Duct temperature sensor TJK 10K
Controller for electric heaters
EKR:
EKR
EKR
EKR30, EKR30P
EKR15.1, EKR15.1P
EKR 6.1
ELECTRIC DUCT HEATERS
Heaters conform with IEC 60335-2-30 : 1996, EN 600335-2-30 : 1999, EN 61010-1+ A2 : 2000, EN 50081-2 : 1995,
EN 55011 : 1999+ A1 : 2001 standards and are CE marked.
Temperature sensors
Temperature sensors TJ
TJK10K
Duct temperature sensors TJK10K, TJK PT1000 are used for
measuring air temperature in ventilation system ducts. Duct temperature sensors are
delivered with installation flange. Insertion length can be adjusted with flange.
Type
IP class
Thermistor
(10KΩ @
25°C), range
-30..105°C
Measurement
accuracy
Sensor
tube
Length
Diameter
Cable
length
Plastic
TEMPERATURE SENSORS
Controllers for electric heating
EKR
PRODUCT HIGHLIGHTS
FOR THREE PHASE DUCT HEATERS
CONTROLLED POWER TILL 255 kW
MODERN CASING DESIGN
Type
Controlled load [kW]
Relay output
Voltage [V]
15
1x5A/230V
3x230/3x400
15
4x5A/230V
3x230/3x400
30
1x5A/230V
3x230/3x400
30
4x5A/230V
3x230/3x400
Controllers conforms to requirements of standards EN 61010-1+A2:2000, EN 50081-1:1995, EN 55022:2000 and carries CE mark.
CONTROLLERS FOR ELECTRIC HEATING
EKR15.1, EKR30 is a proportional controllers for electric
heaters with automatic voltage adaptation.
EKR15.1P, EKR30P is a proportional controllers for multistep
(up to 5 steps) electric heaters with automatic voltage adaptation.
Controllers EKR are designed only for electric heating control.
The control principle makes it unsuitable for motor or lighting control. EKR controls
the whole load On-Off. The ratio between On-time and Off-time is varied 0-100% to
suit the prevailing heat demand.
EKR15.1 can control 15kW heater and has relay output for
extra load control with contactor, on which can be connected load up to 12kW. Full load
can be 27kW.
EKR15.1P can control with triac output 15kW heater and has
four relay outputs for 4 extra load steps control with contactors, on which can be
connected load up to 450kW.
EKR30 can control 30kW heater and has relay output for extra
load control with contactor, on which can be connected load up to 12kW. Full load can
be 42kW.
EKR30P can control with triac output 30kW heater and has four
relay outputs for 4 extra load steps control with contactors, on which can be connected
load up to 450kW. Full load can be 470kW.
Controllers for electric heating
EKR
PRODUCT HIGHLIGHTS
FOR ONE AND TWO PHASE DUCT
HEATERS
EKR 6.1 is a proportional controller for electric heating, with
automatic adaptation of voltage. An internal or an external sensor is used with the
device. EKR 6.1 controls the heating intensity by switching electrical power on or off.
The ratio between the on-time and off-time depends on the need for heating and can
vary in the range between 0% and 100%. EKR6.1 is suitable for the control of
electrical heating only. EKR6.1 is not suitable for the control of three-phase electrical
current, it is used to control monophasic and diphase heaters only.
Night function (NIGHT) setpoint reducing 0..10°C, then
timer is connected and its contacts close. Supply air temperatures can be limited (MIN,
MAX), then 2 sensors wiring diagram is used.
CONTROLLERS FOR ELECTRIC HEATING
Type
Controlled load
[kW]
Max. controlled
current [A]
Voltage [V]
1x230/2x400
Controllers conforms to requirements of standards: LST EN 61010-1:2002, LST EN55022:2000, LST EN 60730-1+A11:
2002/A16 2007, marked with conventional sign CE.