ECS429 - Sylvania

www.sylvania.com
QUICKTRONIC® PROStart® T5HO
UNV High Ambient Temp. Systems
Type CC
Programmed Rapid Start Systems
Normal Ballast Factor HT
Professional Series
Q T P T 5H O
PSN H T
Lamp / Ballast Guide
54W T5HO - PENTRON lamps
1 or 2 lamp
QTP2x54T5HO/UNV PSN HT
4 lamp Switchable:
QTP4x54T5HO/UNV PSN HT W
Also operates:
FP54/SS, FT50DL, FT55DL, FPC55, L58T8
1 or 2 lamps on 2L ballast
1, 2, 3, or 4 lamps on 4L ballast
®
Key System Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
9 0°C maximum case temp.
Universal voltage (120-277V)
Low-profile (1.00” High)
100% ballast factor (see table)
QUICKSENSE ballast technology
(end-of-lamp-life sensing)
PROStart programmed rapid start
UL type CC rated
-20°F (-29C) Min. Starting Temp.
Operates at >42 kHz to reduce
potential interference with infrared
control systems
High power factor
Low harmonic distortion
Lightweight
UL, CSA, FCC
RoHS compliant
Lead-free solder, printed circuit board
and manufacturing process
Application Information
SYLVANIA QUICKTRONIC
T5HO HT ballasts
are ideally suited for:
• Industrial high-bay
• Commercial
• Retail
• Hospitality
• Institutional
• New construction
• Direct lighting
• Indirect lighting
• Surface mount
• Cove lighting
ECS429 - 6-13
SYLVANIA QUICKTRONIC PROStart
T5HO High Ambient Temperature (HT)
electronic ballasts operate PENTRON HO,
PENTRON HO Circline, and DULUX® L T5
lamps with full lumen output and optimal
system performance. The ballasts are
available in two and four lamp models to
cover a wide range of applications.
These QUICKTRONIC PROStart T5HO
ballasts are specifically designed for
applications where the ballast is subjected
to higher ambient temperatures, as in
high bay industrial installations. The four
lamp UNV (120-277V) ballast system
provides 18,600 mean lumens, which,
when factoring in lumen maintenance
and typical T5HO fixture efficiency, can
be considered as a direct replacement for
standard 400W MH. As such, the family
is ideally suited to replace 250W to 400W
metal halide installations.
Unique to the family is the 120-277V
4-lamp “switching” ballast, designed to
switch from 4- to 2-, 3- to 2-, 3- to 1- or
System Information
QUICKTRONIC PROStart T5HO HT
ballasts operate on 120V through 277V,
50/60 Hz current, eliminating “wrong
voltage” wiring errors and reducing the
number of ballast models in inventory
by half.
PROStart programmed rapid starting
provides optimum starting conditions to
yield up to 100,000 switching cycles for
use on occupancy sensors and building
control systems.
Customers should always consider
upgrading to our High Efficiency Systems
to maximize energy savings.
QUICKSENSE ballast technology helps
to protect against overheated bases
and sockets, as well as cracking of
the lamp glass wall, and uses dynamic
end-of-lamp-life sensing to avoid false
shutdowns caused by some static sensing
methods. QUICKSENSE ballast technology
will auto reset when spent lamps are
replaced with new ones.
2- to 1-lamps. The switching feature can
be accessed through a second input power
terminal. This feature allows for a range of
control interfaces, including an occupancy
sensor, mounted inside a fixture.
circuit boards and manufacturing process.
Setting the standard for quality,
QUICKTRONIC PROStart T5HO HT systems
are covered by the QUICK 60+® warranty,
the first and most comprehensive system
warranty in the industry.
These ballasts are also RoHS compliant
and feature lead-free solder, printed
System Type
Input System Initial MeanRelative Energy
Power Fixture*Fixture*Fixture* Savings
(W)
LPW
Lumens
Output
(%)
M400/U (1-lamp)
Magnetic Ballast
452
61
FP54T5HO (4-lamps)
QTP4x54T5HO/UNV PSN-HTW
236
76 16,74094% 48%
FP54/50W/SS (4-lamps)
QTP4x54T5HO/UNV PSN-HTW
215
85 17,07596% 52%
FP54/47W/SS (4-lamps)
QTP4x54T5HO/UNV PSN-HTW
200
84 15,62588% 56%
17,784Baseline Baseline
*Based on Fixture Efficiency: 76% for M400 and 90% for FP54T5HO
*277V input voltage
*Lumen Output for T5HO @ 35°C/95°F
120%
100%
Relative Fixture* Output
100% 100%
88%
48%
Energy
Savings
80%
60%
System Power (%)
96%
94%
52%
52%
Energy
Savings
48%
40%
56%
Energy
Savings
44%
20%
0%
M400/U (1-lamp)
Magnetic Ballast
FP54T5HO (4-lamp)
QTP 4x54T5HO/UNV PSN-HTW
FP54/50W/SS (4-lamp)
QTP 4x54T5HO/UNV PSN-HTW
FP54/47W/SS (4-lamp)
QTP 4x54T5HO/UNV PSN-HTW
SPECIFICATION DATA
Catalog #
Date
Project
Prepared by
2 LAMP T5HO UNV HT
Type
Fixed Output Ballast
Professional Series
Comments
Lamp / Ballast Guide
2 Lamp, Type CC, High Ambient, Universal Voltage (120-277V)
Q T P T 5HO
PSN HT
High ambient model (90°C case temp.)
49136 QTP 2x54T5HO/UNV PSN HT
Wiring diagram for 2-Lamp model
Installation Notes
• Install in accordance with National
& Local Electric Code
• Ground ballast case
• Switching: Simultaneously
disconnect all ungrounded line
conductors
• Insulate unused leads for 600V
2-Lamp model can be wired for one lamp operation.
Item Number
49136 QTP 2 x 54 T5HO / UNV PSN HT
High Ambient Temperature (Case)
QUICKTRONIC PROFESSIONAL
Starting/Ballast Factor
Number of Lamps (1, 2)
Line Voltage (120-277V)
Primary Lamp Wattage
Specifications subject to change without notice.
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
SPECIFICATION DATA
Catalog #
Date
Project
Prepared by
4 LAMP T5HO UNV HT
Type
Switchable Ballast
Comments
Professional Series
4 Lamp, Type CC, High Ambient, Universal Voltage (120-277V)
Switching Schematics
4-Lamp Switching Wiring Diagram (4L to 2L)
S2 (Output B)
Closed (ON)
Open (OFF)
Closed (ON)
Open (OFF)
Lamp Control
All 4 Lamps ON (Output A&B ON)
2 Lamps ON (Output A ON)
2 Lamps ON (Output B ON)
All Lamps OFF
Q T P T 5HO
PSN HT
S1 (Output A)
Closed (ON)
Closed (ON)
Open (OFF)
Open (OFF)
Output A
S1
S2
(Red Switching Line)
Output B
High ambient switchable model (90°C case temp.)
49161 QTP 4x54T5HO/UNV PSN HT W
Installation Notes
3-Lamp Switching Wiring Diagram (3L to 2L, 3L to 1L)
S1 (Output A)
Closed (ON)
Closed (ON)
Open (OFF)
Open (OFF)
S2 (Output B)
Closed (ON)
Open (OFF)
Closed (ON)
Open (OFF)
Lamp Control
All 3 Lamps ON (Output A&B ON)
2 Lamps ON (Output A ON)
1 Lamp ON (Output B ON)
All Lamps OFF
Output A
S1
S2
(Red Switching Line)
• Install in accordance with National
& Local Electric Code
• Ground ballast case
• Switching: Simultaneously disconnect
all ungrounded line conductors
• The AC line inputs must be connected
to the same phase of
the line voltage
• DO NOT CONNECT two separate
phases of line voltage to the input
of the ballast
Output B
Input wiring for non-switching operation
(Install jumper between black & red
switching line terminals)
2-Lamp Switching Wiring Diagram (2L to 1L)
S1 (Output A)
Closed (ON)
Closed (ON)
Open (OFF)
Open (OFF)
S2 (Output B)
Closed (ON)
Open (OFF)
Closed (ON)
Open (OFF)
Lamp Control
2 Lamps ON (Output A&B ON)
1 Lamp ON (Output A ON)
1 Lamp ON (Output B ON)
All Lamps OFF
S1
S2
(Red Switching Line)
Item Number
49161 QTP 4 x 54 T5HO / UNV PSN HTW
Input wiring for occupancy sensors
(Install occupancy sensor/switch between
black & red line terminals)
Output A
Output B
High Ambient Temperature (Case)
QUICKTRONIC PROFESSIONAL
Starting/Ballast Factor
Number of Lamps
Line Voltage (120-277V)
Primary Lamp Wattage
OSRAM SYLVANIA National Customer Service and Sales Center 1-800-LIGHTBULB (1-800-544-4828) www.sylvania.com
Specifications subject to change without notice.
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
Normal Ballast Factor
SPECIFICATION DATA
Catalog #
Date
Project
Prepared by
T5HO PROStart
Type
®
Professional Series
Comments
Performance Guide
Type CC, High Ambient, Universal Voltage (120-277V)
InputRated1Ballast1 Input1System
CurrentLamp1 Lumens No. of Factor System1Mean1 Power (W) Efficacy
(AMPS)
Type
(lm) Lamps (BF) Lumens Lumens 120V 277V (lm/W)
BEF2
QTP 2x54 T5HO Fixed Output BF 1.0
QTP2x54T5HO/UNV PSN-HT
1.00/0.43 FP54T5HO 5000 0.96/0.41 FP54/50W/SS 5000 0.89/0.38 FP54/47W/SS 4575
2
2
2
1.00
1.02
1.02
10,000 10,200 9335 9300 9485 8680 121
115
106
118
112
103
85
91
91
0.85
0.91
0.99
0.53/0.24 FP54T5HO 5000 0.50/0.21 FP54/50W/SS 5000 0.45/0.21 FP54/47W/SS 4575
1
1
1
1.05
1.05
1.03
5250 5250 4710 4885 4885 4380 62
59
54
61
58
53
86
91
89
1.72
1.81
1.94
49161 QTP4x54T5HO/UNV PSN-HTW
2.05/0.90 FP54T5HO 5000 1.85/0.80 FP54/50W/SS 5000 1.72/0.75 FP54/47W/SS 4575 4
4
4
1.00
1.02
1.02
20,000 18,600 241
20,400 18,970 221
18,665 17,360 205
236
215
200
85
95
93
0.42
0.47
0.51
1.51/0.65 FP54T5HO 5000 1.46/0.62 FP54/50W/SS 5000 1.34/0.58 FP54/47W/SS 4575 3
3
3
1.00
1.04
1.04
15,000 13,950 183
15,600 14,510 175
14,275 13,275 161
181
170
158
83
92
90
0.55
0.61
0.66
1.00/0.45 FP54T5HO 5000 0.95/0.42 FP54/50W/SS 5000 0.88/0.39 FP54/47W/SS 4575 2
2
2
1.00
1.03
1.03
10,000 10,300 9425 9300 9580 8765 121
114
105
118
111
104
85
93
91
0.85
0.93
0.99
0.51/0.25 FP54T5HO 5000 0.50/0.25 FP54/50W/SS 5000 0.47/0.25 FP54/47W/SS 4575 1
1
1
1.00
1.06
1.06
5000 5300 4850 4650 4930 4510 61
60
55
61
58
54
82
91
90
1.64
1.83
1.96
QTP 4x54 T5HO Switchable Model
1 At 35°C lamp ambient temperature.
2 Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value).
3 System Efficacy calculation based on lowest input power value
*(Item Number) = Item Number/NAED in parentheses are models with leads/wires. Ballast with leads/wires contains 10 pieces each. Ballast without leads contain 20 pieces each.
Installation Notes
Switching: Simultaneously disconnect all ungrounded line conductors.
Install in accordance with National & Local Electrical Code. Ground ballast case.
Dimensions:
Model QTP2x54T5HO/UNV PSN-HT enclosure size:
Overall: 16.73"L x 1.18"W x 1.0"H (425mm L x 30mm W x 25.4mm H)
Mounting: 16.34" (415mm)
Height
Wiring:
Push-in connectors
Use 18AWG solid copper wire only
Product Weight:
0.88lbs (0.40kg) each (approx.)
Length
30.0 mm
1.18”
Width
Height
Dimensions:
Model QTP4x54T5HO/UNV PSN-HT-W enclosure size:
Overall: 16.73"L x 2.32"W x 1.0"H (425mm L x 59mm W x 25.4mm H)
Mounting: 16.34" (415mm)
Wiring:
Push-in connectors
Use 18AWG solid copper wire only
Product Weight:
1.68lbs (0.40kg) each (approx.)
Item Number
Length
59.0 mm
2.32”
Width
49161 QTP 4 x 54 T5HO / UNV PSN HTW
UL Listed Class P, Type 1, Outdoor,
UL Type CC Rated
CSA Certified
High Ambient Applications:
90°C Max. Case Temp. (3 yr. warranty)
Standard Ambient Applications:
70°C Max. Case Temp. (5 yr. warranty)
FCC 47CFR Part 18 Non-Consumer
Class A Sound Rating
ANSI C62.41 Cat. A Transient Protection
Dynamic End-of-Lamp-Life Sensing
Remote Mounting (Max. wire length
from ballast case to lampholder):
up to 18 feet
RoHS Compliant 5
5 Complies with European Union Restriction of
Hazardous Substances Directive (Directive
2002/95/EC)
System Life / Warranty
Mounting Length
Quantity:
10 (leaded and non-leaded)
Starting Method: Programmed
Rapid Start
Ballast Factor: 1.00 (see table)
Circuit Type: Series
Lamp Frequency: >42 kHz
Lamp CCF: Less than 1.6
Starting Temp: -20°F (-29°C) min.4
Input Frequency: 50/60 Hz
Low THD: <10%
Power Factor: >98%
Voltage Range: ±10% of 120-277V
rated line (108-305V)
4 Operation below 50°F (10°C) may affect light
output or lamp operation – see “Low Temp.
Starting” definition. Remote red and brown leads
up to 18 feet. Keep blue and yellow (for 4-lamp
model only) leads <10 ft
Mounting Length
Quantity:
49136: 20 (no leads)
49135: 10 (with leads)
Specifications 4
High Ambient Temperature (Case)
QUICKTRONIC PROFESSIONAL
Starting/Ballast Factor
Number of Lamps
Line Voltage (120-277V)
Primary Lamp Wattage
SYLVANIA,
the system solution, PENTRON, DULUX, QUICKSENSE, SUPERSAVER, PROStart, and QUICK 60+ are registered trademarks of OSRAM SYLVANIA Inc.
SEE THE WORLD IN A NEW LIGHT is a trademark of OSRAM SYLVANIA Inc. QUICKTRONIC is a registered trademark of OSRAM GmbH.
Q T P T 5H O
PSN HT
49136
(49135)*
QUICKTRONIC products are covered by the
QUICK 60+® warranty, a comprehensive
lamp and ballast system warranty. For
additional details, refer to the QUICK 60+
warranty bulletin.
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
Specifications subject to change without notice.
©2013 OSRAM SYLVANIA
Item
Number
Description
Data based upon SYLVANIA
PENTRON® HO lamps shown.
QUICKTRONIC® PHO HT ballasts are
also compatible with other lamp
manufacturers equivalent lamp types
that meet ANSI specifications.