SEQUENCE OF OPERATIONS – SPLIT SYSTEMS SEQUENCE OF OPERATIONS – SPLIT SYSTEMS FRN-1 AND FRN-2 SHALL BE PROVIDED WITH A 7 DAY / 24 HOUR COMMERCIAL THERMOSTAT WITH OCCUPIED/ UNOCCUPIED SETBACK MODE. FAN SHALL RUN CONTINUOUSLY IN THE OCCUPIED MODE. OUTSIDE AIR DAMPERS SHALL CLOSE IN UNOCCUPIED MODE AND FAN SHALL CYCLE ON HEATING / COOLING DEMAND ONLY. OUTSIDE AIR DAMPERS SHALL MODULATE IN THE OCCUPIED MODE BASED ON CO2 SPACE SENSORS. THE SYSTEM SHALL BE PROVIDED WITH ALL DAMPERS AND CONTROLS NECESSARY TO ENABLE CO2 MONITORING AND CONTROL. THE BASIS OF THERMOSTAT DESIGN SHALL BE THE HONEYWELL PRESTIGE 2.0 IAQ. THE SYSTEMS SHALL BE PROVIDED WITH REMOTE SPACE TEMPERATURE SENSORS WITH THE THERMOSTATS LOCATED IN SECURE LOCATIONS. FRN-1 AND FRN-2 SHALL BE PROVIDED WITH A 7 DAY / 24 HOUR COMMERCIAL THERMOSTAT WITH OCCUPIED/ UNOCCUPIED SETBACK MODE. FAN SHALL RUN CONTINUOUSLY IN THE OCCUPIED MODE. OUTSIDE AIR DAMPERS SHALL CLOSE IN UNOCCUPIED MODE AND FAN SHALL CYCLE ON HEATING / COOLING DEMAND ONLY. OUTSIDE AIR DAMPERS SHALL MODULATE IN THE OCCUPIED MODE BASED ON CO2 SPACE SENSORS. THE SYSTEM SHALL BE PROVIDED WITH ALL DAMPERS AND CONTROLS NECESSARY TO ENABLE CO2 MONITORING AND CONTROL. THE BASIS OF THERMOSTAT DESIGN SHALL BE THE HONEYWELL PRESTIGE 2.0 IAQ. THE SYSTEMS SHALL BE PROVIDED WITH REMOTE SPACE TEMPERATURE SENSORS WITH THE THERMOSTATS LOCATED IN SECURE LOCATIONS. LM1 C7189R1004 WIRELESS REMOTE SENSOR – LOCATE PER DRAWINGS T4 OUTSIDE AIR RETURN AIR EIM1 S1 ACT 24V T1 DA1 ACT 2-10 S2 LM2 50062329-001 DA TEMP 10K NTC @ 77°F SUPPLY AIR RETURN AIR S1 EIM2 S1 1 2 3 ACT COM T5 50062329-001 DA TEMP 10K NTC @ 77°F DA2 ACT 2-10 T2 S2 T6 S2 FRN1 MAT FRN2 50062329-001 RA TEMP 10K NTC @ 77°F T3 MAT LM1 T7 LM2 MAT MAT 72°F C7250A1001 OA TEMP 20K NTC @ 77°F W/ 50053060-001 DUCT MOUNT KIT 72°F C7250A1001 OA TEMP 20K NTC @ 77°F W/ 50053060-001 DUCT MOUNT KIT PT1 THX9421R5021WW HIGH DEFINITION COLOR TOUCHSCREEN THERMOSTAT FRN1 CONTROL SCHEMATIC AND WIRING DETAIL MAT SD-O/B OAT OCC OAT E-GND S-BUS EXH1 R C CONV W1 W2 W3 Y1 Y2 G A POWER HEAT COOL FAN U1 U2 U3 OR OR OR PT1 R C C7250A1001 T4 IAQ 2-10 Y2-I Y2-O IAQ 24+ Y1-I ACT 2-10 Y1-O ACT COM C ACT 24+ R 2 DA1 W7220A1000 EXPANDABLE ECONOMIZER LOGIC MODULE WITH DISPLAY U3 U3 U2 U2 U1 U1 LM1 EIM2 TO THERMOSTAT R C CONV W1 W2 W3 Y1 Y2 G A POWER HEAT COOL FAN U1 U2 U3 OR OR T2 50062329-001 RA TEMP 10K NTC @ 77°F S2 S2 S1 S1 FRN1 CONTROL SECTION T1 Y1,Y2 CONTACTS MAY BE LOCATED AT OUTSIDE CONDENSING UNIT. FIELD VERIFY 50062329-001 DA TEMP 10K NTC @ 77°F PT2 R C OCC E-GND C7250A1001 T8 EXH1 AUX Honeywell Economizer W7220 IAQ 2-10 Y2-I IAQ COM Y2-O IAQ 24+ Y1-I ACT 2-10 Y1-O ACT COM C ACT 24+ R 1 2 DA2 3 W7220A1000 EXPANDABLE ECONOMIZER LOGIC MODULE WITH DISPLAY LM2 Rev. Date 01 02/20/2014 02 02/20/2014 Description GH CHANGE TITLE BLOCK GH URBAN PROMISE SPIRIT BUILDING U3 U3 U2 U2 U1 U1 25-27 NORTH 36TH STREET CAMDEN, NEW JERSEY 08105 R C G W1 W2 W3 Y1 Y2 T6 50062329-001 RA TEMP 10K NTC @ 77°F S2 S2 S1 S1 FRN2 CONTROL SECTION DRAWING TITLE SANCTUARY FURNACE CONTROL SCHEMATIC AND WIRING DETAIL HUTCHINSON MECHANICAL 621 CHAPEL AVENUE CHERRY HILL, NEW JERSEY 08034 (800)360-5807 T5 Y1,Y2 CONTACTS MAY BE LOCATED AT OUTSIDE CONDENSING UNIT. FIELD VERIFY 50062329-001 DA TEMP 10K NTC @ 77°F DRAWING NUMBER 14JTC1002-2 SHEET DATE CONTROL COMPONENTS WIRING DETAILS Project Manager: SC Sales Engineer: Installation Tech: CONTROL COMPONENTS WIRING DETAILS Systems Engineer: gh By ADD WRITTEN SEQUENCE SITE NAME AND LOCATION RH RC R C SENSORS SD-O/B OAT OAT S-BUS S-BUS OR R C G W1 W2 W3 Y1 Y2 MAT T7 72°F IAQ COM 3 MAT C7250A1001 AUX Honeywell Economizer W7220 1 RH RC R C SENSORS Golden Valley, MN 55422 Assembled in Mexico 72°F TO THERMOSTAT THM5421R1021 EQUIPMENT INTERFACE MODULE MOUNT NEAR OR IN ROOFTOP UNIT CONTROL SECTION Golden Valley, MN 55422 Assembled in Mexico T3 S-BUS EIM1 FRN2 CONTROL SCHEMATIC AND WIRING DETAIL MAT C7250A1001 THX9421R5021WW HIGH DEFINITION COLOR TOUCHSCREEN THERMOSTAT Golden Valley, MN 55422 Assembled in Mexico Golden Valley, MN 55422 Assembled in Mexico THM5421R1021 EQUIPMENT INTERFACE MODULE MOUNT NEAR OR IN ROOFTOP UNIT CONTROL SECTION PT2 MS7503A2030 THM5421R1021 W7220A1000 THX9421R5021WW C7189R1004 50062329-001 50062329-001 C7250A1001 C7250A1001 YTHX9421R5085WW YL7220A7503 S2 50062329-001 RA TEMP 10K NTC @ 77°F 44 IN/LB D.C.S.R. ACTUATOR 24VAC EQUIPMENT INTERFACE MODULE EXPANDABLE ECONOMIZER LOGIC MODULE PRESTIGE HIGH DEFINITION COLOR TOUCHSCREEN THERMOSTAT WIRELESS REMOTE SENSOR DISCHARGE AIR SENSOR 10K NTC @ 77°F RETURN AIR SENSOR 10K NTC @ 77°F MIXED AIR SENSOR 20K NTC @ 77°F OUTSIDE AIR SENSOR 20K NTC @ 77°F PRESTIGE KIT - INCLUDES EIM1-3, PT1-PT3, T1-T6 JADE KIT - INCLUDES LM1-2, T3,T7,T4,T8,DM1 EIM2 2 3 2 3 3 2 2 2 2 2 2 EIM1 HONEYWELL HONEYWELL HONEYWELL HONEYWELL HONEYWELL HONEYWELL HONEYWELL HONEYWELL HONEYWELL HONEYWELL HONEYWELL ACT COM T8 OUTSIDE AIR S1 1 2 3 C7189R1004 WIRELESS REMOTE SENSOR – LOCATE PER DRAWINGS DM1,DM2 EIM1-EIM3 LM1-LM2 PT1-PT3 RS1-RS3 T1,T5 T2,T6 T3,T7 T4,T8 ACT 24V LM1 C7250A1001 OA TEMP 20K NTC @ 77°F W/ 50053060-001 DUCT MOUNT KIT SUPPLY AIR RS2 OAT OAT SANCTUARY FURNACE UNITS - FIELD BILL OF MATERIALS IDENT. MANUFACTURER QTY. PART NO. DESCRIPTION C7250A1001 OA TEMP 20K NTC @ 77°F W/ 50053060-001 DUCT MOUNT KIT LM2 RS1 OAT OAT Installation Supervisor: Drawn By: gh 2/1/2014 Approved By: 2
© Copyright 2024 ExpyDoc