SEQUENCE OF OPERATIONS – SPLIT SYSTEMS
SEQUENCE OF OPERATIONS – SPLIT SYSTEMS
FRN-1 AND FRN-2 SHALL BE PROVIDED WITH A 7 DAY / 24 HOUR COMMERCIAL THERMOSTAT WITH OCCUPIED/ UNOCCUPIED SETBACK
MODE. FAN SHALL RUN CONTINUOUSLY IN THE OCCUPIED MODE. OUTSIDE AIR DAMPERS SHALL CLOSE IN UNOCCUPIED MODE AND
FAN SHALL CYCLE ON HEATING / COOLING DEMAND ONLY. OUTSIDE AIR DAMPERS SHALL MODULATE IN THE OCCUPIED MODE BASED
ON CO2 SPACE SENSORS. THE SYSTEM SHALL BE PROVIDED WITH ALL DAMPERS AND CONTROLS NECESSARY TO ENABLE CO2
MONITORING AND CONTROL. THE BASIS OF THERMOSTAT DESIGN SHALL BE THE HONEYWELL PRESTIGE 2.0 IAQ. THE SYSTEMS
SHALL BE PROVIDED WITH REMOTE SPACE TEMPERATURE SENSORS WITH THE THERMOSTATS LOCATED IN SECURE LOCATIONS.
FRN-1 AND FRN-2 SHALL BE PROVIDED WITH A 7 DAY / 24 HOUR COMMERCIAL THERMOSTAT WITH OCCUPIED/ UNOCCUPIED SETBACK
MODE. FAN SHALL RUN CONTINUOUSLY IN THE OCCUPIED MODE. OUTSIDE AIR DAMPERS SHALL CLOSE IN UNOCCUPIED MODE AND
FAN SHALL CYCLE ON HEATING / COOLING DEMAND ONLY. OUTSIDE AIR DAMPERS SHALL MODULATE IN THE OCCUPIED MODE BASED
ON CO2 SPACE SENSORS. THE SYSTEM SHALL BE PROVIDED WITH ALL DAMPERS AND CONTROLS NECESSARY TO ENABLE CO2
MONITORING AND CONTROL. THE BASIS OF THERMOSTAT DESIGN SHALL BE THE HONEYWELL PRESTIGE 2.0 IAQ. THE SYSTEMS
SHALL BE PROVIDED WITH REMOTE SPACE TEMPERATURE SENSORS WITH THE THERMOSTATS LOCATED IN SECURE LOCATIONS.
LM1
C7189R1004 WIRELESS REMOTE
SENSOR – LOCATE PER DRAWINGS
T4
OUTSIDE
AIR
RETURN
AIR
EIM1
S1
ACT 24V
T1
DA1
ACT 2-10
S2
LM2
50062329-001 DA TEMP
10K NTC @ 77°F
SUPPLY
AIR
RETURN
AIR
S1
EIM2
S1
1
2
3
ACT COM
T5
50062329-001 DA TEMP
10K NTC @ 77°F
DA2
ACT 2-10
T2
S2
T6
S2
FRN1
MAT
FRN2
50062329-001 RA TEMP
10K NTC @ 77°F
T3
MAT
LM1
T7
LM2
MAT
MAT
72°F
C7250A1001 OA TEMP
20K NTC @ 77°F
W/ 50053060-001 DUCT
MOUNT KIT
72°F
C7250A1001 OA TEMP
20K NTC @ 77°F
W/ 50053060-001 DUCT
MOUNT KIT
PT1
THX9421R5021WW HIGH DEFINITION
COLOR TOUCHSCREEN THERMOSTAT
FRN1 CONTROL SCHEMATIC AND WIRING DETAIL
MAT
SD-O/B
OAT
OCC
OAT
E-GND
S-BUS
EXH1
R
C
CONV
W1
W2
W3
Y1
Y2
G
A
POWER
HEAT
COOL
FAN
U1
U2
U3
OR
OR
OR
PT1
R
C
C7250A1001
T4
IAQ 2-10
Y2-I
Y2-O
IAQ 24+
Y1-I
ACT 2-10
Y1-O
ACT COM
C
ACT 24+
R
2
DA1
W7220A1000 EXPANDABLE
ECONOMIZER LOGIC MODULE
WITH DISPLAY
U3
U3
U2
U2
U1
U1
LM1
EIM2
TO THERMOSTAT
R
C
CONV
W1
W2
W3
Y1
Y2
G
A
POWER
HEAT
COOL
FAN
U1
U2
U3
OR
OR
T2
50062329-001 RA TEMP
10K NTC @ 77°F
S2
S2
S1
S1
FRN1
CONTROL
SECTION
T1
Y1,Y2 CONTACTS MAY
BE LOCATED AT
OUTSIDE CONDENSING
UNIT. FIELD VERIFY
50062329-001 DA TEMP
10K NTC @ 77°F
PT2
R
C
OCC
E-GND
C7250A1001
T8
EXH1
AUX
Honeywell
Economizer W7220
IAQ 2-10
Y2-I
IAQ COM
Y2-O
IAQ 24+
Y1-I
ACT 2-10
Y1-O
ACT COM
C
ACT 24+
R
1
2
DA2
3
W7220A1000 EXPANDABLE
ECONOMIZER LOGIC MODULE
WITH DISPLAY
LM2
Rev.
Date
01
02/20/2014
02
02/20/2014
Description
GH
CHANGE TITLE BLOCK
GH
URBAN PROMISE SPIRIT
BUILDING
U3
U3
U2
U2
U1
U1
25-27 NORTH 36TH STREET
CAMDEN, NEW JERSEY 08105
R
C
G
W1
W2
W3
Y1
Y2
T6
50062329-001 RA TEMP
10K NTC @ 77°F
S2
S2
S1
S1
FRN2
CONTROL
SECTION
DRAWING TITLE
SANCTUARY FURNACE CONTROL
SCHEMATIC AND WIRING DETAIL
HUTCHINSON MECHANICAL
621 CHAPEL AVENUE
CHERRY HILL, NEW JERSEY 08034
(800)360-5807
T5
Y1,Y2 CONTACTS MAY
BE LOCATED AT
OUTSIDE CONDENSING
UNIT. FIELD VERIFY
50062329-001 DA TEMP
10K NTC @ 77°F
DRAWING NUMBER
14JTC1002-2
SHEET
DATE
CONTROL COMPONENTS WIRING DETAILS
Project Manager: SC
Sales Engineer:
Installation Tech:
CONTROL COMPONENTS WIRING DETAILS
Systems Engineer: gh
By
ADD WRITTEN SEQUENCE
SITE NAME AND LOCATION
RH
RC
R
C
SENSORS
SD-O/B
OAT
OAT
S-BUS
S-BUS
OR
R
C
G
W1
W2
W3
Y1
Y2
MAT
T7
72°F
IAQ COM
3
MAT
C7250A1001
AUX
Honeywell
Economizer W7220
1
RH
RC
R
C
SENSORS
Golden Valley, MN 55422
Assembled in Mexico
72°F
TO THERMOSTAT
THM5421R1021 EQUIPMENT
INTERFACE MODULE
MOUNT NEAR OR IN
ROOFTOP UNIT CONTROL SECTION
Golden Valley, MN 55422
Assembled in Mexico
T3
S-BUS
EIM1
FRN2 CONTROL SCHEMATIC AND WIRING DETAIL
MAT
C7250A1001
THX9421R5021WW HIGH DEFINITION
COLOR TOUCHSCREEN THERMOSTAT
Golden Valley, MN 55422
Assembled in Mexico
Golden Valley, MN 55422
Assembled in Mexico
THM5421R1021 EQUIPMENT
INTERFACE MODULE
MOUNT NEAR OR IN
ROOFTOP UNIT CONTROL SECTION
PT2
MS7503A2030
THM5421R1021
W7220A1000
THX9421R5021WW
C7189R1004
50062329-001
50062329-001
C7250A1001
C7250A1001
YTHX9421R5085WW
YL7220A7503
S2
50062329-001 RA TEMP
10K NTC @ 77°F
44 IN/LB D.C.S.R. ACTUATOR 24VAC
EQUIPMENT INTERFACE MODULE
EXPANDABLE ECONOMIZER LOGIC MODULE
PRESTIGE HIGH DEFINITION COLOR TOUCHSCREEN THERMOSTAT
WIRELESS REMOTE SENSOR
DISCHARGE AIR SENSOR 10K NTC @ 77°F
RETURN AIR SENSOR 10K NTC @ 77°F
MIXED AIR SENSOR 20K NTC @ 77°F
OUTSIDE AIR SENSOR 20K NTC @ 77°F
PRESTIGE KIT - INCLUDES EIM1-3, PT1-PT3, T1-T6
JADE KIT - INCLUDES LM1-2, T3,T7,T4,T8,DM1
EIM2
2
3
2
3
3
2
2
2
2
2
2
EIM1
HONEYWELL
HONEYWELL
HONEYWELL
HONEYWELL
HONEYWELL
HONEYWELL
HONEYWELL
HONEYWELL
HONEYWELL
HONEYWELL
HONEYWELL
ACT COM
T8
OUTSIDE
AIR
S1
1
2
3
C7189R1004 WIRELESS REMOTE
SENSOR – LOCATE PER DRAWINGS
DM1,DM2
EIM1-EIM3
LM1-LM2
PT1-PT3
RS1-RS3
T1,T5
T2,T6
T3,T7
T4,T8
ACT 24V
LM1
C7250A1001 OA TEMP
20K NTC @ 77°F
W/ 50053060-001 DUCT
MOUNT KIT
SUPPLY
AIR
RS2
OAT OAT
SANCTUARY FURNACE UNITS - FIELD BILL OF MATERIALS
IDENT. MANUFACTURER QTY.
PART NO.
DESCRIPTION
C7250A1001 OA TEMP
20K NTC @ 77°F
W/ 50053060-001 DUCT
MOUNT KIT
LM2
RS1
OAT OAT
Installation Supervisor:
Drawn By: gh
2/1/2014
Approved By:
2