Inert gas damper EKO–JBGI

Decompression
damper
Inert gas damper EKO–JBGI
Description
Design
The EKO–JBGI inert gas damper is intended for use
The EKO–JBGI inert gas damper is available with
as protection against fire in adjoining premises or for
guide or flange connection and is fitted with two in-
decompression in data rooms or other sensitive
spection hatches on the drive side. The damper
areas containing valuable technical equipment. The
blade axle must always be mounted in a horizontal
damper frame is from our type approved EKO–JBG
position. The damper drive unit is a pneumatic motor
combustion gas damper. The damper is designed in
with spring return and adjustable pressure reducing
accordance with the requirements of the Swedish
valve with manometer on the secondary side and,
standard VVS AMA 98, section QJD.
wherever necessary, two contacts for indicating the
The damper is for installation in fire isolation building
cells in accordance with fire technical classification up
position of the damper blade.
The EKO-JBGI inert gas damper is manufactured of
to EI120. The inert gas damper is normally closed.
hot-dip galvanised sheet steel to environmental classifi-
When emissions of inert gas occur, the damper opens
cation M2. The damper blades are made of solid fire-
and the wall constructions in the premises are decom-
resistant material. The inert gas damper may also be
pressed. More information on the damper is available
supplied in alternative materials such as stainless steel
under EKO-JBG.
2333 or acid resistant 2343 for increased environmental
The EKO–JBGI inert gas damper drive unit is con-
requirements.
nected to the inert gas installation via a pipe system.
When emissions of inert gas occur, the damper
Air tightness classification
opens via the drive unit and the spring is tensioned.
The damper is equipped with a sealing gasket on the
When the gas fills the room, the pressure in the inert
air side equivalent of class 4, VVS AMA 98.
gas installation drops and the spring in the drive unit
There is also a sealing strip around the damper
closes the damper.
frame, that expands and seals if the damper is exposed
The damper must always be installed with the
to heat.
drive unit in the protected room.
Because the EKO–JBGI is not connected to the
Working pressure
ducting, it must be fitted with a wire mesh grille.
The working pressure of the damper is max. 2500 Pa,
Manual movement of the inert gas damper is con-
pressure class B, differential pressure with
ducted once a year in connection with testing of the
closed blades.
inert gas installation.
EKO VENTILATIONSDETALJER AB, Mejselgatan 7, SE-235 32 Vellinge, Sweden, TEL: +46 (0)40-42 16 15, FAX: +46 (0)40-42 25 18, E-MAIL: [email protected], INTERNET: www.ekovent.se
Decompression
damper
Sizes
Accessories
The EKO-JBGI inert gas damper is manufactured in a
EKO-ANS
Connection adapter for spiral ducting.
large number of standard dimensions, from 200x200
EKO-FLS
Extension adapter for walls or beams
to 1200x1000 mm.
thicker than 360 mm and in combination
with connection adapter EKO-ANS or
Maintenance
wire mesh grille EKO-N.
We recommend preventive maintenance of the dampers
EKO-GIS
as required by the plant in which they are installed. The
Erection collar for damper mounting in
plasterboard walls material for making
damper blades and interior surfaces are cleaned with a
good not included.
brush, vacuum cleaner or by wiping down. NOTE! Water
EKO-KER
Material for making good walls.
or other liquids must not be used.
EKO-MFL
Counter flange.
EKO-INR
Wall frame.
EKO-N
Wire mesh grille.
Mounting instructions
See EKO-JBG.
How to order EKO-JBGI
Designation: Inert gas damper EKO-JBGI-A-B-C-D
A
B
C
D
SIZE
MATERIAL
CONNECTIONDAMPER
MOTOR
(Width x Height)
1 = Galvanized
5 = Flange
2 = Aluzinc (M3)
6 = Guide
7 = Pneumatic damper motor
3 = Stainless steel SS 2333
4 = Stainless steel SS 2343
Example: 1 Decompression damper EKO-JA-400x200-1-6-7
EKO VENTILATIONSDETALJER AB, Mejselgatan 7, SE-235 32 Vellinge, Sweden, TEL: +46 (0)40-42 16 15, FAX: +46 (0)40-42 25 18, E-MAIL: [email protected], INTERNET: www.ekovent.se
Decompression
damper
Technical data EKO-JBGI
Dimensions
Inert cas pressure
60-80 bars
Max 200
spacing n = 200
C
20
600
D
D
50
Operating pressure
Inert gas connection
Inspection
hatches
1/4" NPT internal thread
C
B
spacing n = 200
C
4-6 bars
Guide connection
Ø 12
19
40
A
185
230
185
Standard sizes
Free area for open damper
A or B
C
Number
spacing n
D
200
250
300
350
120
145
170
195
0
0
0
0
0
0
0
0
400
500
600
650
120
170
120
145
1
1
2
2
0
0
0
50
700
800
900
1000
170
120
170
120
2
3
3
4
50
100
150
200
1100
1200
170
120
4
5
-
Width
Height
Area
200
300
400
500
200
300
400
500
2.6
6.9
13.2
21.5
600
700
800
900
600
700
800
900
31.8
44.1
58.4
74.7
1000
1100
1200
1000
1000
1000
93.0
102.3
111.6
Weight for standard sizes*
A
B
200
250
300
350
400
450
500
600
700
800
1000
1100
1200
200
250
300
350
20
21
21
23
21
23
24
25
21
24
25
27
23
25
27
29
25
27
29
31
26
28
31
33
28
30
33
35
32
33
37
39
35
37
40
43
38
42
44
46
45
48
51
54
48
52
55
58
52
55
59
62
400
450
500
600
25
26
28
33
27
28
30
34
29
31
33
38
31
33
35
40
34
35
37
42
35
37
39
45
37
39
45
47
42
44
48
50
45
48
51
57
49
52
55
65
58
61
64
75
62
65
69
79
66
69
73
83
700
800
900
1000
36
39
42
45
38
42
45
49
41
45
48
51
44
47
51
56
46
50
55
60
49
53
57
62
52
56
60
65
57
62
66
70
62
67
82
77
70
73
78
84
82
95
98
100
85
97
100
105
90
99
105
110
* Weight in kg, including damper motor.
EKO VENTILATIONSDETALJER AB, Mejselgatan 7, SE-235 32 Vellinge, Sweden, TEL: +46 (0)40-42 16 15, FAX: +46 (0)40-42 25 18, E-MAIL: [email protected], INTERNET: www.ekovent.se