D-THERMO DIN rail programmable thermostat - A

D-THERMO
DIN rail programmable thermostat
Ref. 880-0012
L
N
B
Vh Vc 1 2 3 C
Description
DIN rail programmable thermostat for automated
temperature control. It may be used for
radiators, radiating floor, airflow units with 2 or 4
tubes and some models of air conditioning.
Functionalities
Independent programs for winter and summer
3 operation periods for each week day with
Minimum and maximum temperature
Possibility to associate a second unit as slave
Integration with automation
Scenarios
Application
Homes
Hotels
Office buildings
Factories
Accessories
T-THERMO-x
or
T-THGL-x
touch
connected to other wall commands
Certifications
CE
EN 60669-2-1
Low voltage directive 2006/95/CE
EMC directive 2004/108/CE
Mounting
Mounting on DIN rail, 2 modules
Connections
L – Live x 1 for 1.5 mm Ø
N – Neutral x 4 for 1.5 mm Ø
B – Bus x 2 for 1.5 mm Ø
L – Common in x 1 for 1.5 mm Ø
Vh – Heating valve out x 1 for 1.5 mm Ø
Vc – Cooling valve out x 1 for 1.5 mm Ø
1 – Speed 1 out x 1 for 1.5 mm Ø
2 – Speed 2 out x 1 for 1.5 mm Ø
3 – Speed 3 out x 1 for 1.5 mm Ø
Electrical characteristics
Supply voltage:
230 V 50 Hz
Power consumption:
0.5 W
Max. load current:
5 A total (cosØ=1)
3 A total (cosØ=0.4)
Contact rating:
max 230 VAC 5 A
max 30 VDC 5 A
Contact material:
Ag alloy (Cd free)
panels
Remarks
This unit must be associated as slave of another
thermostat or associated with a thermostat touch
panel mounted on any other wall mounted unit.
subject to change without notice
d-domotics.com
• www.advanced-domotics.com
A-TOUCH inter
Lda. • [email protected]
• www.atouch.com.pt
D-THERMO
DIN rail programmable thermostat
Ref. 880-0012
Protections:
The unit must be protected by a 6 ampere circuit breaker. This circuit breaker may also protect the
supply to other DIN rail A-TOUCH units on the same RCD segment.
The potential free contacts must have a current limitation (protection) of 5 ampere maximum.
Dimensions
A = 35 mm (2 modules)
B = 90 mm
C = 62 mm
D = 46 mm
E = 58 mm
D C B
E
Connection diagram: RADIATOR
B
N
L
E
L
N
B
Vh Vc 1 2 3 C
RADIATOR
subject to change without notice
d-domotics.com
• www.advanced-domotics.com
A-TOUCH inter
Lda. • [email protected]
• www.atouch.com.pt
A
D-THERMO
DIN rail programmable thermostat
Ref. 880-0012
Connection diagram: RADIATING FLOOR
B
N
L
E
L
N
B
Vh Vc 1 2 3 C
RADIATING FLOOR VALVES
Connection diagram: AIRFLOW UNIT 2 TUBES
B
N
L
E
L
M
N
B
Vh Vc 1 2 3 C
AIRFLOW UNIT 2 TUBES
subject to change without notice
d-domotics.com
• www.advanced-domotics.com
A-TOUCH inter
Lda. • [email protected]
• www.atouch.com.pt
D-THERMO
DIN rail programmable thermostat
Ref. 880-0012
Connection diagram: AIRFLOW UNIT 4 TUBES
B
N
L
E
L
N
B
Vh Vc 1 2 3 C
M
AIRFLOW UNIT 4 TUBES
Connection diagram: DAIKIN KRP413A
B
N
L
E
L
N
B
S4
S1
Vh Vc 1 2 3 C
SW1
S2
1
2
OFF ON
S3
KRP413A
subject to change without notice
d-domotics.com
• www.advanced-domotics.com
A-TOUCH inter
Lda. • [email protected]
• www.atouch.com.pt