METASYS
GB
Central suction system
METASYS ZPA
Installation, operation and maintenance
Table of contents
Explanation of the pictograms
The groups of people for whom certain types of activities
are relevant can be found in the footer.
1. Table of contents:
Page
1. Table of contents
2
2. Explanation of the pictograms
2
3. General instructions
3
4. Application
4
5. Overview of types
4
6. Number of treatment units per suction system
5
7. Construction
6
8. Functional description
6
9. Technical data
7
10.Installation guidelines
7
11.Modifying the suction systems to ZPA
8
12.Pipes
9
13.Explanation of the control unit
10
14.Electrical connections
11
15.Calibrating the system
12
16.Commissioning
13
17. Maintenance
14
18.Disposal of the equipment
14
2. Explanation of the pictograms:
means that if the instructions are disregarded
danger for people, operational problems or
damage to the equipment or its immediate surroundings can occur.
means that the attention of operating or maintenance personnel particularly needs to be drawn to
important items in this section.
Page
GB
Practice personnel / technician
General instructions
3. General instructions:
The safety, reliability and performance of the
equipment is only guaranteed by METASYS if the
following instructions are followed:
Before the ZPA central suction system can be correctly
q
installed and calibrated, please carefully read the complete Installation, Operating and Maintenance manual.
Installation, alterations or repairs must only be carried
q
out by authorised specialists who guarantee compliance
with standard EN 60601-1 (International Standard for
Medical Electrical Equipment, particularly Part 1: General Safety Requirements).
The electrical installation must correspond with IEC (Interq
national Electrotechnical Commission) requirements.
The equipment must only be used in accordance with the
q
installation, operation and maintenance instructions.
q Only genuine METASYS spare parts must be used for
repairs or replacement.
q You must also observe all information and instructions
issued by the manufacturers of the treatment units to
which the ZPA suction system is to be connected.
After commissioning, the Installation Proof found
into the Equipment Logbook must be completed
and returned to METASYS in order to determine
the guarantee period.
q Every service and inspection must be recorded in the
Equipment Logbook.
q If requested by a qualified technician, METASYS declares
to provide all prepared documentation likely to be of
use to the technically qualified person for service and
repairs of the the equipment's components.
qMETASYS takes no responsibility for damages arising
from outside influences (inaccurate installation), incorrect information, use of the equipment for purposes
other than the one intended, or for improper repairs.
The equipment is not suitable for use in explosive
or combustible environment.
q Users must study equipment and assure themselves of
its good condition before every use.
Practice personnel / technician
GB
Page
Application
Overview of types
4. Application:
1.4
1.3
1.5
ZPA stands for (in German) "Central Unit in Parallel Arrangement". The METASYS ZPA system is a central suction system used to produce centralised vacuum at dental medical
practices.
1.6
1.2
Depending on the equipment, it can be designed to be:
1.7
Ø 70 mm
Ø 50 mm
1
1.1
and amalgam separation
2.4
5. Overview of types:
2.3
2.5
q A dry suction system
q A semi-wet suction system with air/water separation
q A semi-wet suction system with air/water separation
The ZPA central suction system is available in 2 basic versions:
2.6
ZPA 2: The ZPA 2 is a central suction system which combines two METASYS EXCOM Z2/Z5, EXCOM hybrid
2/5 or VAC II/III into a single parallel unit.
2.2
2.7
Ø 100 mm
Ø 70 mm
2
2.1
2x
1x
or
+
ZPA 3: The ZPA 3 is a central suction system which combines three METASYS EXCOM Z2/Z5, EXCOM hybrid
2/5 or VAC II/III into a single parallel unit.
1
Scope of supply ZPA 2 /
1.1
2 pcs. Suction power distributor
2.1
2 pcs.
1.2
1 pc.
Extension pipe
2.2
1 pc.
1.3
1 pc.
Vacuum relief
2.3
1 pc.
1.4
2 pcs.
Non-return valve
2.4
3 pcs.
1.5
1 pc.
Control unit
2.5
1 pc.
1.6
1 pc.
Vacuum relief hose
2.6
1 pc.
1.7
2 pcs.
Tube plugs
2.7
3 pcs.
2
Scope of supply ZPA 3
The METASYS ZPA can be fitted in the following combinations:
3
or
See picture
ZPA 2 as the central suction system, with or without air/
water separation:
1 pc. ZPA 2
q
2 pcs. VAC II/III, EXCOM Z2/Z5 or EXCOM hybrid 2/5
q
3
Page
GB
Practice personnel / technician
Overview of types, number of treatment units per suction system
4
See picture
1 pc. ZPA 2
q
2 pcs. EXCOM Z2/Z5 or EXCOM hybrid 2/5
q
2 pcs. COMPACT A8/A16 or ECO II
q
5
2x
2x
1x
ZPA 2 as semi-wet suction system with air/water separation and amalgam separation
+
or
+
See picture
ZPA 3 as the central suction system, with or without air/
water separation:
4
1 pc. ZPA 3
q
3 pcs. VAC II/III, EXCOM Z2/Z5 or EXCOM hybrid 2/5
q
6
or
3x
See picture
ZPA 3 as semi-wet suction system with air/water separation and amalgam separation:
1x
1 pc. ZPA 3
q
3 pcs. EXCOM Z2/Z5 or EXCOM hybrid 2/5
q
3 pcs. COMPACT A8/A16 or ECO II
q
or
+
6. Number of treatment units per suction system:
Number of
treatment
units
1
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Suction systems
at 60%
at 70%
at 100%
load
load
load
EXCOM Z-ECO EXCOM Z-ECO EXCOM Z-ECO
EXCOM ZE
EXCOM ZE
EXCOM ZE
EXCOM ZA1 EXCOM ZA1 EXCOM ZA1
EXCOM Z2
EXCOM Z2
EXCOM Z2
EXCOM Z5
EXCOM Z5
EXCOM Z5
EXCOM Z5
EXCOM Z5
ZPA 2
EXCOM Z5
ZPA 2
ZPA 2
ZPA 2
ZPA 2
ZPA 3
ZPA 2
ZPA 2
ZPA 3
ZPA 2
ZPA 3
ZPA 3
ZPA 2
ZPA 3
ZPA 3
ZPA 3
ZPA 3
ZPA 3
ZPA 3
ZPA 3
ZPA 3
ZPA 3
ZPA 3
ZPA 3
ZPA 3
or
5
3x
3x
1x
+
or
+
or
The table above illustrates the principles of measurement.
Variances can occur because the suction power is greatly influenced by the condition of the pipe system, and by its size.
6
Practice personnel / technician
GB
Page
Construction
Functional description
7. Construction:
1
See picture, in the ZPA3 example
1.1 EXCOM Z5
Suction system with air/water separation
1.2
1.6
1.2 Control unit
Controls the suction flow volume
As soon as the vacuum drops below or exceeds the set value
one suction system is switched on or off. This increases or
reduces the volume of suction flow.
1.3
1.7
1.5
1.3 Control line
Transfers the "on-off" signal to the suction system
1.4 Air inlet valve
Optimises the vacuum so that any losses can be compensated through the pipe system. It also protects the suction
systems from overheating.
1.4
1.8
1.5 Vacuum relief
Conducts the vacuum to the control unit
1.6 Exhaust air line
Conducts the exhaust air to the outside
1.1
1.7 Waste water line
Conducts the waste water to the drain system
1.4
1.8 Suction flow distributor
The suction flow distributor distributes the suction flow
evenly to the suction systems required.
8. Functional description:
After a suction hose on the hose system has been lifted or
when waste water emerges from the rinsing basins, a start
signal is sent to the control system via the suction contact
cable which starts all the suction systems at the same
time.
As soon as the nominal vacuum is reached, the system
automatically switches back to the operation of one or two
suction systems (depending on need).
The control unit constantly controls the vacuum in the pipe
system by switching the suction systems on or off, depending
on the amount of suction flow required.
1
Page
GB
Practice personnel / technician
Technical data
Installation guidelines
9. Technical data:
ZPA 2 / ZPA 3
Mains voltage:
230 V AC
Frequency:
50/60 Hz
Max. current consumption:
400 mA
Equipment fuse:
1A
Vacuum range:
180 mbar regulated
Max. ambient temperature:
40 °C
Operating time:
100 % ED
+ 40 °C
RH < 70 %
+ 10 °C
10. Installation guidelines:
See picture
2
T
he METASYS ZPA suction system is designed to be
q
installed only in dry, adequately ventilated rooms.
T
heir use in areas subject to explosive and fire hazards
q
is not permitted.
T
he permitted room temperature ranges from between
q
+10° C and +40° C. The relative humidity must not
exceed 70%.
I
n case of room temperatures above +35° C, additional
q
air ventilation must be catered for. A ventilator must be
installed at the installation space.
2
Installation can be on the same level as the treatment units,
in a side room or one floor lower.
I n order to avoid vibrations, the suction system
must be installed on a firm base.
Please see the relevant installation, operating and maintenance instructions and the installation guidelines for the
individual components (EXCOM Z2/Z5, EXCOM hybrid 2/5,
VAC I-III, COMPACT A8/A16 and ECO II).
3
See picture
3.1
Suction flow distributor
T o ensure that all the suction systems reach the
same suction volume, the connections on the suction flow distributor must be fitted at an angle of
45° to the vertical.
3.1
3
Practice personnel / technician
GB
Page
Installation guidelines
Modifying the suction systems to ZPA
1
Vacuum relief, see picture
2 m
The vacuum relief hose is supplied to the maximum
permitted length of 2 m. Do not extend this hoses!
11. Modifying the suction systems to ZPA:
2
odification actions for EXCOM Z2/Z5
M
and EXCOM hybrid 2/5
2.1
Pull the air inlet valve out of the Y-distributor (the
air inlet valve just removed will be fastened to the
vacuum relief later in the installation procedure).
2.2
Insert the tube plugs (supplied) into the Y-distributor.
2.3
Undo the hose clamp and pull the suction hose off
the separation.
2.4
Push the non-return valve onto the separation (with
the O-ring side pointing downwards) and fasten the
suction hose to the non-return valve.
3
Modification action for the VAC II/III:
3.1
Pull the the Y-distributor and air inlet valve out of
the condensate separator (the air inlet valve just
removed will be fastened to the vacuum relief later
in the installation procedure).
3.2
Insert the extension pipe into the condensate separator.
3.3
Push the non-return valve into the extension pipe
(the side with the O-rings to the outside, the nonreturn valve must open in the direction of suction!)
3.4
Insert the connector dia. 50 - dia. 40 (supplied with with the VAC II/III) into the non-return valve.
1
2.1
2.2
2.3
2.4
2
3.1
3.2
3.4
3.3
3
Page
GB
Practice personnel / technician
Pipes
12. Pipes:
The existing pipework must comply with the guidelines
specified by METASYS. These guidelines can be found in
the basic planning information for central suction systems.
1.4
Please maintain a minimum and maximum diameter for the
central suction line:
ZPA2: Minimum Ø 50 mm, Maximum Ø 70 mm
ZPA3: Minimum Ø 70 mm, Maximum Ø 110 mm
1.3
Connection to the existing pipework:
1.6
4
See picture
1.1
Central suction line
1.2
Extension pipe
This is fitted between the central suction line and the
vacuum relief, so that no humidity can get into the
vacuum relief.
1.3
Vacuum relief
Conducts the vacuum to the control unit via a hose.
1.4
1.2
Air inlet valves
T he air inlet valves removed from the suction
systems (see section 11), are fastened to the
vacuum relief (1 on the ZPA2, 2 on the ZPA3). They
will be required later to calibrate the vacuum.
1.5
Suction flow distributor
Keep the hose paths to the suction systems as short
as possible.
1.6
Connectors
These are set to the connectors concerned on the
suction flow distributor for the suction hose connection to EXCOM / VAC (included in the scope of supply
for EXCOM Z2/Z5, EXCOM hybrid 2/5 and VAC II/III).
1.1
1.5
4
2.2
5
See picture
Waste water line:
Please see the Installation, Operating and Maintenance
Manual entitled "METASYS EXCOM Z2/Z5 Central Suction
system", section 11 Installation Guidelines, for how to lay
the waste water line. 2.1
2.3
Exhaust air line:
The exhaust air line from the suction system to the exhaust
pipe must comply with the guidelines set out in the
Installation, Operating and Maintenance Instructions for
the METASYS EXCOM or METASYS VAC, respectively. The
diameter of the central exhaust line 2.2 must be at least
equal to (or larger than) that of the central suction line
2.3 . Use a pipe material made from PP-H.
2.1
5
Practice personnel / technician
GB
Page
Explanation of the control unit
1.7
13. Explanation of the control unit
1.6
1.5
1
1.4
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12
1.8
1.1
1.2
1.9
1.10
1.11
1.12
1
2.1
2.2
2.3
1.3
See picture, in the ZPA3 example
Relay Vacuum 1
Relay Vacuum 2
Relay Vacuum 3
Warning panel
Vacuum switch suction system 2
Vacuum switch suction system 3
T1A fuse
Terminal block
230 V AC, 50/60 Hz mains connection
Vacuum measurement connection
Sealing plugs
Vacuum relief
The control unit receives the start signal via the suction contact cable which is connected to the terminals 1.8 This
start signal is transferred via the control lines, which are
likewise connected to the terminals 1.8 , to all the suction systems.
The nominal vacuum required has been preset at the vacuum
switches for suction system 2 1.5 and suction system 3
1.6 . As soon as this nominal vacuum has been reached, a
stop signal is sent via the vacuum switch to suction system 2
and suction system 3. In this situation, only suction system 1
is still in operation.
If, later on, a greater volume of suction flow is required (for
example when other vacuum consumers join the network),
the vacuum in the suction line network is reduced.
The vacuum switches detect this via the vacuum relief 1.12 .
So if the vacuum at the vacuum switch on suction system 2
1.5 falls below the minimum set point, suction system 2
automatically switches back on.
If this situation still does not produce the required suction
flow volume, the vacuum drops again. As soon as it falls
below the nominal minimum vacuum at the vacuum switch
for suction system 3 1.6 , suction system 3 switches on.
The system is then running at maximum power.
If the vacuum exceeds the maximum vacuum set for the
vacuum switch on suction system 3 1.6 , suction system
3 is switched off again. In this way the suction systems are
switched on and off in the sequence described.
In the event that no further start signals are sent via the
suction contact cable, all the suction systems switch off
automatically.
2
2.1
2.2
2.3
Warning panel
LED suction system 1
LED suction system 2
LED suction system 3
The LEDs on the warning panel show which suction systems
are in operation.
2
10
Page
GB
Practice personnel / technician
Explanation of the control unit
Electrical connections
Vacuum switch suction system 1 + 2
3
3.1
3.2
3.3
3.2
Vacuum connection
Adjusting screw suction system 2
Adjusting screw suction system 3
There is an adjusting screw on each of the two vacuum
switches, which can be used to adjust the vacuum level to
suit the condition of the suction line network. The various
suction line networks vary so greatly that it is not possible
to make a factory pre-setting for the vacuum switch.
If you turn a screw to the right, the nominal vacuum (at
which the suction system with switch on or off) on the
suction system concerned will increase. The switching
hysteresis is preset and cannot be altered.
3.3
3.1
3
14. Electrical connections:
Only qualified electricians are authorised to
carry out the electrical connection. Always carry
out electrical installations in accordance with
applicable national regulations.
Before making the electrical connection, compare
the nominal voltage stated on the type plate of the
device with the mains voltage.
Circuit diagram ZPA 2 /
4
5
Circuit diagram ZPA 3
Key:
A1
F1
K1
K2
K3
S1.1
S1.2
T1
warning panel
control fuse
EXCOM 1 relay
EXCOM 2 relay
EXCOM 3 relay (on ZPA 3 only)
Pressure switch
Pressure switch (on ZPA 3 only)
Transformer
4
Connection to the control unit:
ll cables must be connected only to the terminal
A
block specific to them. Cable connections should
be made only with the plug removed from the
mains socket.
T
he suction contact cables installed at the treatment units
q
must be collected together into a wiring loom. The wiring
loom must be connected to fuse F1 (T1A) and terminal 4.
T
he control line for suction system 1 must be connected
q
to terminals 7 and 8. The control line for suction system 2
must be connected to terminals 9 and 10.
For ZPA 3 only: The control line for suction system 3
must be connected to terminals 11 and 12.
T
he line cross sections must be minimum 0,75 mm2.
q
The polarity of the cable has no role in the case of the connections described above.
The control line connection to the suction systems must be
made in accordance with the guidelines set out in the Installation, Operation and Maintenance Manual for the device in
question.
Technician
Practice personnel
/ technician
GB
5
Page
11
Calibrating the system
15. Calibrating the system:
Calibrating the system is the last step before putting the
ZPA suction systems into operation. Make sure that all the
devices have been properly installed.
1
You will need the METASYS digital manometer (article no.
40400005) to carry out the calibration!
2
Calibrating the ZPA 2 and ZPA 3:
Switch off all the vacuum consumers!
q
2
1
1
P
ull the sealing plugs out of the measurement connector and attach the digital manometer.
2
T urn the air inlet valve(s) to the right until they reach
the stop (close).
1

Switch off suction system 2 and suction system 3!
q
2
180 mbar
3
A
ctuate the tray contact, (lift the suction hose from
the treatment unit) without sucking in air (plug the
hose so as to be air-tight).
4
O
pen the air inlet valve(s) (turning to the left) until
the digital manometer shows a vacuum of 180 mbar.
The setting should be almost identical in the case of
two air flow valves. If it is not possible to reach this
value, examine the pipe system for leaks.
5
P
ull the air inlet valve(s) out of the vacuum relief
and cover the openings with the polystyrene leaves
supplied.
6
S
lowly push in a polystyrene leaf until a half-moon
shaped opening is made and the manometer shows
a value of 160 mbar.
7
T urn the adjusting screw on the vacuum switch for
suction system 2 to the right until the LED on suction
system 2 lights up, and then slowly turn it back to
exactly the point where the LED on suction system 2
goes out.
å
4
3
1
160 mbar
2
6
5
©
©
7.2
7.1
fi
·
1
·
2
1
7.1
For ZPA 3 only: Slowly push in the polystyrene leaf
until the manometer shows a value of 140 mbar.
7.2
For ZPA 3 only: Turn the adjusting screw on the
vacuum switch for suction system 3 to the right until
the LED on suction system 3 lights up, and then
slowly turn it back to exactly the point where the LED
on suction system 3 goes out.
fi
2
140 mbar
7
12
Page
GB
Practice personnel
Technician
/ technician
Calibrating the system
First time operation
8
Hang the suction back into the hose tray.
9
Fasten the air inletvalve(s) to the vacuum relief.
10
Remove the digital manometer and replace the
sealing plugs into the measurement connection.

16. First time operation:
8
11
See picture
11.1
S witch on all the devices, or the practice main
switch
11.2
Remove the suction hose from the hose tray on one
treatment unit. All the suction systems must start at
the same time. After running for a maximum of 60
seconds, only one suction system should still be
running (check the LEDs on the warning panel).
11.3
H ang the suction hose back into the hose tray.
Suction system 1 will continue to run for the pre-set
run-on time. Check that the vacuum during the runon time is 180 mbar, adjust if necessary.
Remove the suction hoses in sequence from the
treatment units until you have reached the maximum
possible number. Ensure that the suction systems
start up in sequence.
11.5
H ang the suction hoses back into the hose tray.
Ensure that suction systems 2 and 3 switch back off,
take account of the run-on time!
1
2
3
10
60
sec

11.4
9
11.2
11.1
11.6
1 ...
180 mbar
2 ...

If all the above points are met, the system has been
correctly installed.
60 sec

Siphon off 2 litres of water on each treatment unit.
Check all the hose connections and joints on the suction line for leaks, repair if necessary. After a repair
the ZPA must be subjected to another function test.

11.3
... 3

11.5
11.4
... 2
1 x

2 l
11.6
11
Technician
Practice personnel
/ technician
GB
Page
13
Maintenance
Disposal of the equipment:
17. Maintenance:
For maintenance of the individual components on the suction systems please see the relevant Installation, Operation
and Maintenance Manual for the devices concerned.
Once the servicing work has been completed, check that
the non-return valve 1 has been correctly set and is
functioning properly.
18. Disposal of the equipment:
T he devices may be contaminated. Please
inform the disposal company of this so that the
necessary precautions can be taken.
Disposal of amalgam separator components,
such as sieves, filters, hoses etc., must also
comply with local regulations.
Uncontaminated plastic components of the suction system
may be re-cycled.
The built-in control unit, electronic circuit boards and components may be disposed of as electro-technical scrap.
Other metal components may be disposed of as ordinary
metal scrap.
If the devices is returned, for example to the dealer or
METASYS Medizintechnik GmbH, all connections must
be sealed so that they are water-tight.
1
14
Page
GB
Practice personnel / technician
Notes
Practice personnel / technician
GB
Page
15
METASYS
Austria
METASYS
Medizintechnik GmbH
Florianistraße 3
A-6063 Rum bei Innsbruck
1+43/(0)512 /20 54 20-0
5 +43/(0)512/20 54 20-7
Germany
METASYS
Medizintechnik GmbH
Ahornstraße 19
D-85614 Kirchseeon
1 +49/(0)2236/37 42 42
5 +49/(0)2236/37 42 41
France
Ihr METASYS Berater:/Your METASYS agent:
ZK-55.246/01
Dental ECO Service Italia S.r.l.
Florianistraße 3
A-6063 Rum bei Innsbruck
1 +39/045/981 4477
5 +39/045/981 4475
e-mail: [email protected]
GB
Italy
70100328
www.metasys.com
EBW ZPA, 06.07.2011
email: [email protected]
Subject to technical changes, printing and setting errors!
METASYS France S.a.r.l.
9, bd E. Michelet
F-69008 Lyon
1+33/(0)4/37 90 22 15
5 +33/(0)4/37 90 22 47
e-mail: [email protected]
www.metasys.fr