ASHBurN 2 (dC2) IBX® CENTEr

IBX TECHNICAL SPECIFICATIONS
ashburn 2 (dC2) IBX® Center
about
location
power
Equinix operates International Business
Exchange™ (IBX®) data centers across 18
markets in North America, Europe, and
Asia-Pacific. These IBX centers serve
as a reliable and secure destination for
the world’s most powerful networks
and companies. It’s what we do every
day•without compromise.
21715 Filigree Ct.
Ashburn, VA 20147
Electrical Capacity – 1.75 kW per cabinet
UPS Configuration –N+1 Distributed
Redundant System
# of Utility Feeders – 1
# of Power Transformers – 7
Utility Voltage – 480 volts, 3-phase
Standby Power – Six 2,000 kW diesel
engine-generator power
Standby Power Config. – N+1
Equinix operates five IBX centers
in a campus environment and offers
a full range of premium colocation,
interconnection and support services
to a wide range of networks, enterprise,
content companies and financial
institutions.
Because of the area’s strategic importance
as the Eastern hub of traffic exchange to
the United States, Equinix’s DC metro
IBX centers are one of the largest Internet
exchange points in the world.
From Airports – 6 miles to Dulles Intl
Airport (IAD); 33 miles to Washington
National Airport (DCA); 61 miles to
Baltimore-Washington Intl Airport (BWI)
Location Orientation – 33 miles to the
White House
Parking – Adjacent building parking
available (no charge)
Profile
Phone – 1.888.892.0607 (USA or Canada)
or 1.650.513.7600 (outside USA or Canada)
Email – [email protected]
Cooling Capacity – 1.75 kW per cabinet
(5973 BTUH )
Cooling Plant – Water-cooled centrifugal
chillers & air handlers
security
Square Footage Breakdown (Sq. Ft.)
Leased
147,600
Colocation Area
118,447
0
Flex Space
1,867
Satellite Platform
Telco Information
© 2008 Equinix, Inc. | www.equinix.com
Cooling
NPA/NXX
703-723
CLLI code
ASBNVAAS
LEC
VERIZON
LATA
246
Physical – “Man trap” entry
Human – 24x7 security gaurds
Electronic – CCTV and Recorders,
Motion Detection, Hand Geometry
Readers, Fiber Vault
IBX TECHNICAL SPECIFICATIONS
ashburn 2 (dc2) IBX® Center
building
Construction Type – Single story, tilt-up
concrete, steel, concrete slab on grade
Building Type – 2-C Fully Sprinklered
Floor Load Capacity – 250 PSF
building code compliance
Building – 1996 BOCA National Building
Code with Virginia State Supplement
Mechanical – 1996 International
Mechanical Code
Plumbing – 1995 International
Plumbing Code
Electrical – 1996 National Electric Code
Life Safety – 1996 NFPA 13 - Installation of
Sprinkler Systems; 1996 NFPA 72 - National
Fire Alarm Code
Other – N/A
Significant building Dates
„„
„„
„„
Year Base Building Constructed –
2000
Year Base Building RETROFITTED –
N/A
Year EQIX IBX Constructed –
2000
Lateral Load Design
Seismic EPV(Av) – Av = 0.05
Seismic EPA(Aa) – Aa = 0.05
Seismic Hazard Exposure – SHEG = 1
Seismic Importance Factor Ie – N/A
Seismic Zone – 1
Fire protection
Fire Suppression – Double-interlocked,
pre-action (dry pipe)
Fire Rating – Not required by code
interconnection options
System – Overhead proprietary cable tray
system with multi-tier ladder rack
Cross Connects Available – SingleMode fiber, Multi-Mode fiber (62.5 and
50 micron), CAT5, CAT6, CAT5 (T1), and
CAT3 (POTS)
Intra-Building Innerduct (IBID)
Available – a dedicated private path via a
conduit between buildings or customers
„„
„„
Chicago
CH1 Chicago
CH2 Chicago
CH3 Elk Grove
Dallas
DA1 Dallas
Los Angeles
LA1 Los Angeles
LA2 Los Angeles
LA3 El Segundo
New York
NY1 Newark
NY2 Secaucus
NY3 New York City1 NY4 Secaucus
Silicon Valley
SV1 San Jose (North)
SV2 Santa Clara
SV3 San Jose (South)
SV4 Sunnyvale
Washington
DC1 Ashburn
DC2 Ashburn
DC3 Ashburn
DC4 Ashburn
DC5 Ashburn2
1.
2.
Equinix Exchange
Services only
All DC5 IBXs are
same campus
IBX centers in the North America region
EQUINIX CONFIDENTIAL—Subject to change without notice. For distribution to existing Equinix customers,
or to persons who have signed an Equinix Non-Disclosure Agreement.
© 2008 Equinix, Inc. | www.equinix.com
Each private path innerduct is 1.25” in
width.
Customer runs their own Single-mode
fiber within the innerduct which
can potentially fit 432 standard cross
connects.
Equinix Exchange™ Available – Central
switch for public and private peering
Equinix Direct™ Available – Automated
network provisioning, multi-homing and
billing