Installation - StarTek Lighting America

INSTALLATION AND MAINTENANCE MANUAL
Lestra LED Luminaire
Document No: 0071 Rev C
May 2014
IMPORTANT: Read carefully before installation and retain for future reference.
NOTE: Installation must be conducted by licensed electrician.
Lestra LED Luminaire
MODEL #’s
LST18
LST18D
LST36
LST36D
LST-18V1
LST-36V1
Document No: 0071 Rev C
1: Introduction
light output.
Models LST18, LST18D, LST36, LST36D, LST-18-V1, LST-36-V1 are all suitable for damp location
per UL 1598.
2: Warnings
READ AND FOLLOW
INSTRUCTIONS PR
READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS
PRIORALL
TO INSTALLATION
HANDLING PRODUCT.
SUITABLE FOR DAMP LOCATIONS.
CONVIENT AUX EMPLACEMENTS HUMIDES.
THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY
A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS
INVOLVED.
CE PRODUIT DOIT ÊTRE INSTALLÉ SELON LE CODE D’INSTALLATION PERTINENT, PAR UNE PERSONNE QUI
CONNAÎT BIEN LE PRODUIT ET SON FONCTIONNEMENT AINSI QUE LES RISQUES INHÉRENTS.
REMOVE PRODUCT FROM PACKAGING AND CONFIRM IT IS FREE OF DAMAGE PRIOR TO INSTALLATION.
ENLEVEZ LE PRODUIT DE L’EMBALLAGE ET VERIFIEZ QU’IL N’EST PAS ENDOMMAGE AVANT L’INSTALLATION.
DISCONNECT POWER PRIOR TO ANY INSTALLATION.
DÉBRANCHEZ LE COURANT AVANT TOUTE INSTALLATION.
CAP ALL WIRING CONNECTIONS WITH UL APPROVED WIRE CONNECTORS.
COUVRIR TOUTES LES CABLES AVEC DES CONNECTIONS APPROUVES (UL).
VERIFY SUPPLY VOLTAGE MEETS LUMINAIRE LABEL SPECIFICATIONS.
VÉRIFIEZ QUE LA TENSION SOIT COMPATIBLE AVEC LES CARACTÉRISTIQUES DU LUMINAIRE MARQUE SUR
L’ETIQUETTE.
ALLOW FIXTURE TO COOL BEFORE TOUCHING HEATSINK OR LIGHT SOURCE.
LAISSEZ LE PROJECTEUR REFROIDIR AVANT DE TOUCHER LE RADIATEUR OU LA SOURCE DE LUMIÈRE.
DO NOT ATTEMPT TO OPEN OR MAKE REPAIRS INSIDE LUMINAIRE.
NE PAS TENTER D’OUVRIR OU DE FAIRE DES REPARATIONS A L’INTERIEUR DU LUMINAIRE.
CLEAN LENS, WHENEVER NECESSARY, WITH CLEAN WARM WATER OR A NON-ABRASIVE EPA APPROVED
SOLUTION WHICH WILL NOT SCRATCH SURFACE.
NETOYEZ L’OBJECTIF CHAQUE FOIS QUE NECESSAIRE, A L’EAU TIEDE PROPRE OU AVEC UNE SOLUTION NON
ABRASIVE EPA APPROUVEE, ET QUI NE RAYERA PAS LA SURFACE.
AVOID DIRECT VIEWING OF LIGHT SOURCE.
EVITEZ DE REGARDER DIRECTMENT LA SOURCE LUMINEUSE.
Page 2 of 4
14045 Petronella Drive Suite 5, Libertyville, IL 60048
Tel: 877-STARTEK
www.starteklightingamerica.com
Document No: 0071 Rev C
3: Installation Instructions:
1. Shut off power.
2. Inspect mounting location for damage. Make sure it can support
the weight of the Lestra luminaire.
3. Remove Lestra luminaire from package and inspect for damage. Locate
Griplock Grippers (Figure A) or Eye Bolts (Figure E) attched to
luminaire.
(Figure A)
Pendant Mount:
4. Remove 1/16” Aircraft Cable with Gated Hook Sleeve (Figure B)
from package and inspect for damage.
(Figure B)
5. Insert Aircraft Cable through Gripper to attain desired mounting
height (Figure C). When feeding Cable into Gripper, always allow
it to pass at least 1” beyond the body of the Gripper.
NOTE: Grippers work best when Cable follows their centerline.
Avoid angled pulls in excess of 5°.
6. To re-adjust, simply depress the plunger (on top of the Gripper)
with your fingertip and move the Cable to a new position. Release the
plunger to lock (Figure D).
(Figure C)
7. Mount Aircraft Cable to structure. Proceed to number 9 for wiring instruction.
Eye Bolt Mount:
8. Mount Eye Bolts (Figure E) to structure. Proceed to number 9
for wiring instruction.
(Figure D)
9. Connect Lestra luminaire wiring to line wire, black to L1,
white to L2, and green to building ground. Use only UL listed
wiring devices.
9a. If product includes 5-wire line cord, connect black to L1,
connect white to L2. Use orange and red for 0-10 dimming
function. Orange-to-negative (-) and red-to-positive (+).
NOTE: Orange and Red leads are used for 0-10 dimming ONLY.
Cap wires if not used.
(Figure E)
10. Restore power and verify operation.
Page 3 of 4
14045 Petronella Drive Suite 5, Libertyville, IL 60048
Tel: 877-STARTEK
www.starteklightingamerica.com
Document No: 0071 Rev C
Nominal AC Supply Voltage
120-277VAC
Power consumption
LST18 All : 87.5W nominal
LST36 All: 175W nominal
Operating temperature range
-20°C to +50°C [-4°F to +122°F]
Power factor
>0.9
Dimensions (Length x Width x Height)
LST18 All : 18.2” x 8.2” x 4” [462 mm x 209.4 mm x 100.8 mm]
LST36 All : 35.2” x 8.2” x 4” [894 mm x 209.4 mm x 100.8 mm]
Weight
LST18 All : 8.1 lbs. [3.7 kg]
LST36 All: 15.5 lbs. [7 kg]
DIMENSIONS ARE FOR REFERENCE ONLY.
Page 4 of 4
14045 Petronella Drive Suite 5, Libertyville, IL 60048
Tel: 877-STARTEK
www.starteklightingamerica.com