UCC2-1250(2V1250AH. AGM POWER 1750s)

UCC2-1250(2V1250AH. AGM POWER 1750s)
Features
Maintenance-free operation
Stable quality and high reliability
Compact design
12 years design time (at 25℃)
AGM Electrolyte Technology
Application
Telecommunication system
UPS
Electronic apparatus and equipment
Alarm and security system
Emergency lighting
Communication power supply
Backup power for testing and
Fire alarm and security systems
DC power supply
measuring instruments
Auto control system
Specifications
Nominal Voltage
Nominal Capacity
2V (1 cells)
Discharge: -15 - 50°C (5 - 122°F)
1250AH
(10hr, 1.80V/cell, 25°C (77°C)
1020AH
(5hr, 1.80V/cell, 25°C (77°C)
720AH
(1hr, 1.60V/cell, 25°C (77°C)
Length
Dimension
Approx Weight
Terminal
Container Material
Max. Discharge Current
Internal Resistance
Operating Temp.Range
Nominal Operating Temp.Range
Width
175 ± 2mm
338 ± 2mm
Total Height(with Terminal)
365 ± 2mm
Approx 73.5Kg
T6
0 - 40°C (32 - 104°F)
Storage :
-15 - 40°C (5 - 104°F)
25 ± 3°C ( 77 ± 5°F)
Cycle Use
2.30~2.40V (25°C/77°F) Temp.Coe.cient -5mV/°C
Initial Charging Current Less than 300A
Standby Use
2.23~2.28V (25°C/77°F) Temp.Coe.cient -3mV/°C
No limit on Initial Charging Current
475 ± 2mm
Container Height
Charge :
Capacity a.ected by
Temperature
ABS
40°C (104°F)
103%
25°C (77°F)
100%
0°C (32°F)
86%
UCC2 series batteries may be stored for up to 6 months
Self Discharge
4800A (5S)
at 25°C (77°F) and then a freshening charge is required.
For higher temperatures the time interval will be shorter.
Approx 0.3mΩ
Constant Current Discharge (Amperes at 25 ℃/77℉ )
F.V/Time
5min
10min
15min
30min
45min
1h
2h
3h
5h
10h
1.80V/cell
1.75V/cell
1.70V/cell
1.65V/cell
1.60V/cell
2407.00
2625.00
2844.00
3043.00
3257.00
1817.00
1952.00
2100.00
2236.00
2384.00
1423.00
1515.00
1647.00
1770.00
1888.00
956.00
1010.00
1067.00
1110.00
1156.00
765.00
807.00
855.00
889.00
925.00
625.00
646.00
668.00
688.00
708.00
373.00
389.00
406.00
422.00
441.00
283.00
289.00
297.00
303.00
309.00
203.00
207.00
212.00
217.00
222.80
122.00
124.00
126.00
127.00
128.50
100h
17.08
17.36
17.64
17.78
17.99
Constant Power Discharge (Watts per cell at 25 ℃/77℉ )
F.V/Time
5min
10min
15min
30min
45min
1h
2h
3h
5h
10h
20h
1.80V/cell
1.75V/cell
1.70V/cell
1.65V/cell
1.60V/cell
4578.00
4806.00
5062.00
5315.00
5546.00
3363.00
3582.00
3800.00
4009.00
4224.00
2584.00
2790.00
3016.00
3166.00
3318.00
1843.00
1935.00
1971.00
2040.00
2119.00
1475.00
1526.00
1576.00
1639.00
1696.00
1185.00
1226.00
1270.00
1300.00
1338.00
722.00
750.00
781.00
808.00
838.00
559.00
567.00
576.00
590.00
605.00
396.50
405.00
412.00
431.00
433.00
242.90
245.00
247.00
249.00
251.00
125.80
128.00
129.60
131.00
132.80
Note: The above characteristics data are average values obtained within three charge/discharge cycles, not the minimum values.
Dimensions unitimm[inches]
UCC2-1250
(2V1250AH.
AGM POWER 1750s)
UC2-500(2V500AH
)
Temperature Effects in Relation to Battery Capacity
Effect of temperature on long term float life
10
8
120
Capacity ( %)
100
80
Life Expectancy(years)
0.1CA
0.17CA
0.25CA
60
40
6
5
4
Charging Voltage
2.25V/cell
3
2
1
20
0.5
20
10
0
-20 -10
30
40
50
60
20
68
O
Temperature( C)
30
86
40
104
50
122
(℃)
(℉)
BatteryTemperature
Float charging characteristic
Cycle Life in Relation to Depth of Discharge
Testing condition
Discharging: current 0.17C(FV 1.7V/cell);
Charging: current 0.25C max, voltage 2.45V/cell;
Charging volume:125% of discharged capacity.
Charge
Volume
Charging
Current
%
(XCA)
Charging
Voltage
0.10CA-2.25V/cell
(V)
120
temperature25℃
100
0.25
120
2.50
100
0.20
2.33
90
80
Charge Voltage
(Constant 2.2v/cell)
0.15
2.17
70
60
50
0.10
After 50% Discharge
80
60
100%
DOD
50%
DOD
After 100% Discharge
0.05
20
20
1.83
Charging Current
10
0
0
0
0
4
8
12
16
20
28
24
22
36
40
0
400
200
600
800
1000
1200
Number of Cycles
ChargeTime(h)
Discharge characteristic Curve
Self Discharge Characteristics
120
2V
Battery
(V)
O
O
Temperature:25 C(77 F)
Capacity ( %)
2.00
1.84
0.1C
0.205C
0.01C
A
10℃
80
2.16
Term inal Vo lta ge(V)
30%
DOD
AmbientTemperature:
25 OC(77 O F)
40
2.00
40
30
Capacity ( %)
Charged Volume
110
25℃
B
60
30℃
40℃
40
C
20
0.4C
1.68
1C
1.52
0
0.6C
2
4
6
8
10
12
StorageTime(months)
1.36
A
No supplementary charge required
(Carry out supplementary charge before use if 100% capacity is required.)
B
Supplementary charge required before use. Optional charging way as below:
1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.
2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V\cell.
3.Charged for 8~10hours at limted current 0.05CA.
C
Supplementary charge may often fail to recover the capacity.
The battery should never be left standing till this is reached.
2C
1
2
4
6 8 10
20
40 60
Min
DischargeTime
2
4
6 8 10
H
100