vertical riser power cable, 5000 volt, tr-xlp teck 90 (-40ºc) hl

VERTICAL RISER POWER CABLE, 5000 VOLT, TR-XLP
TECK 90 (-40ºC) HL
SPEC 8-29-1.3VR
Ver. 8.0
Revised: 03/26/14
STRANDED BARE
COPPER CONDUCTOR
EXTRUDED
SEMI-CONDUCTING
CONDUCTOR SHIELD
STRANDED BARE COPPER GROUND WIRE
TR-XLP INSULATION
ENCAPSULATED RIBBED INNER PVC JACKET
GALVANIZED INTERLOCKED ARMOR
-40°C PVC OR LSOH JACKET
90°C CONDUCTOR TEMPERATURE, WET OR DRY
Conductor
Size
AWG
or KCMIL
No. of
Strands
Nominal
O.D
in Inches
Insulation
in Mils
Inner/
Outer
Jacket
in Mils
Size
AWG
Copper
Ground
Wire
Approximate O.D. in Inches
Over
Inner
Jacket
Over
Armor
Over
Overall
Jacket
Ampacity**
30°C
Ambient
Approximate
Net
Weight
Lbs/Kft
THREE CONDUCTOR 5000 VOLT, 100% OR 133% INSULATION LEVEL, NON-SHIELDED
8*
7
0.14
80
80/50
10
1.04
1.24
1.42
45
1455
6*
7
0.18
80
80/50
8
1.12
1.34
1.52
65
1655
4*
7
0.23
80
80/50
8
1.22
1.44
1.62
85
1950
2
7
0.27
80
80/60
6
1.31
1.54
1.72
120
2345
1
19
0.30
95
80/60
6
1.44
1.64
1.82
140
2725
1/0
19
0.34
95
80/60
6
1.52
1.81
1.99
155
3075
2/0
19
0.38
95
80/60
6
1.61
1.94
2.12
185
3485
3/0
19
0.42
95
80/60
4
1.71
2.00
2.18
210
4010
4/0
19
0.48
95
110/60
4
1.86
2.19
2.37
235
4720
250
37
0.52
110
110/75
4
2.02
2.31
2.53
265
5495
350
37
0.62
110
110/75
3
2.23
2.50
2.72
325
6855
500
37
0.74
110
110/75
3
2.49
2.81
3.03
395
8790
750
61
0.91
125
140/85
2
2.99
3.31
3.53
500
12365
1000*
61
1.12
125
140/85
1
3.44
3.75
3.97
585
15790
Note:**Based on cables in free air run, per CEC Part 1, Table 2. For
other installations refer to the CEC.
*Compressed conductors.
The above data is approximate and subject to normal manufacturing tolerances.
STANDARDS AND RATINGS:
1. Listed as Teck90 by CSA per CSA Standard C22.2 No. 131 Teck90 Cable.
2. Listed as FT4 & HL by CSA per CSA Standard C22.2 No. 174 Cables for Use in Hazardous Locations
(HL for sizes 6AWG & larger).