VERTICAL RISER POWER CABLE, 5000 VOLT, TR-XLP TECK 90 (-40ºC) HL SPEC 8-29-1.3VR Ver. 8.0 Revised: 03/26/14 STRANDED BARE COPPER CONDUCTOR EXTRUDED SEMI-CONDUCTING CONDUCTOR SHIELD STRANDED BARE COPPER GROUND WIRE TR-XLP INSULATION ENCAPSULATED RIBBED INNER PVC JACKET GALVANIZED INTERLOCKED ARMOR -40°C PVC OR LSOH JACKET 90°C CONDUCTOR TEMPERATURE, WET OR DRY Conductor Size AWG or KCMIL No. of Strands Nominal O.D in Inches Insulation in Mils Inner/ Outer Jacket in Mils Size AWG Copper Ground Wire Approximate O.D. in Inches Over Inner Jacket Over Armor Over Overall Jacket Ampacity** 30°C Ambient Approximate Net Weight Lbs/Kft THREE CONDUCTOR 5000 VOLT, 100% OR 133% INSULATION LEVEL, NON-SHIELDED 8* 7 0.14 80 80/50 10 1.04 1.24 1.42 45 1455 6* 7 0.18 80 80/50 8 1.12 1.34 1.52 65 1655 4* 7 0.23 80 80/50 8 1.22 1.44 1.62 85 1950 2 7 0.27 80 80/60 6 1.31 1.54 1.72 120 2345 1 19 0.30 95 80/60 6 1.44 1.64 1.82 140 2725 1/0 19 0.34 95 80/60 6 1.52 1.81 1.99 155 3075 2/0 19 0.38 95 80/60 6 1.61 1.94 2.12 185 3485 3/0 19 0.42 95 80/60 4 1.71 2.00 2.18 210 4010 4/0 19 0.48 95 110/60 4 1.86 2.19 2.37 235 4720 250 37 0.52 110 110/75 4 2.02 2.31 2.53 265 5495 350 37 0.62 110 110/75 3 2.23 2.50 2.72 325 6855 500 37 0.74 110 110/75 3 2.49 2.81 3.03 395 8790 750 61 0.91 125 140/85 2 2.99 3.31 3.53 500 12365 1000* 61 1.12 125 140/85 1 3.44 3.75 3.97 585 15790 Note:**Based on cables in free air run, per CEC Part 1, Table 2. For other installations refer to the CEC. *Compressed conductors. The above data is approximate and subject to normal manufacturing tolerances. STANDARDS AND RATINGS: 1. Listed as Teck90 by CSA per CSA Standard C22.2 No. 131 Teck90 Cable. 2. Listed as FT4 & HL by CSA per CSA Standard C22.2 No. 174 Cables for Use in Hazardous Locations (HL for sizes 6AWG & larger). AETNA INSULATED WIRE, LLC 1537 AIR RAIL AVENUE, VIRGINIA BEACH, VA 23455 TELEPHONE: (800) 423-6505 FAX: (757) 605-2094 WWW.AETNAWIRE.COM
© Copyright 2024 ExpyDoc