DIGICONTROL- Gerätedatenblatt
R-RAK
www.gfr.de
[ 82130 ]
Category: Field Units - Monitor
Universal thermostat
DIGICONTROL
R-RAK
Application
For controlling and monitoring the temperature of liquids in baths, containers,
pipes and ducts. Because of its modular design and universal housing, the
thermostat is very versatile. It can be used as: a stem-type thermostat with
protective tube (pocket); a clamp-on thermostat on pipes; a thermostat with a
remote sensor; or a double thermostat.
Universal housing made of plastic; can be fitted in various ways; snap-on lid
with window, sealable; internal setpoint adjuster; thermostat module with
single-pole change-over contacts (TB has normally-closed contacts);
capillary tube (which can be uncoiled according to needs, depending on the
fitting method) and sensor cartridge; screw terminals for wire of max. 1,5
2
mm ; cable screw fitting for cable of up to Ø 9 mm.
Setting range
Switching
difference
K
Artikeltyp
°C
Capillary tube
mm
Sensor cartridge
mm
Max. temp. of
sensor
°C
As a temperature controller-monitor (TR, TM); with LW 7 pocket, brass, 100 mm; as per DIN 3440
RAK 82.4/3773M
5...30
4
800
68
200
RAK 82.4/3770M
–10...50
4
1600
68
180
RAK 82.4/3728M
15...95
4
800
68
200
RAK 82.4/3754M
40...120
4
1600
68
200
RAK 82.4/3726M
50...130
4
800
68
200
3)
80...160
4
1600
68
200
RAK 82.4/3753M 3)
150...230
4
1000
68
280
RAK 82.4/3729M
As a safety temperature limiter (STB), classified in PED 97/23/EC as per Cat. IV; with LW 7 pocket, brass, 100 mm; as
per DIN 3440; intrinsically safe; with mechanical lock.
RAK 13.4040S
120/110/100/95 1)
20
800
68
200
130/120/110/100/95
RAK 13.4050S
1)
20
800
68
220
Technical Data
Max. contact rating 2)
Degree of protection
IP 40 (EN 60529)
I (IEC 60730)
Terminal 1-2 TW, TB
10 (2.6) A 250 V~
Protection class
Terminal 11-12 STB
10 (6) A 250 V~
DIN register number
Terminal 1-4 TW
4 (0.6) A 250 V~
Thermostat module
TR 706 01
500 mA 40 V
Thermostat module
STB 1060 2000
Not classified in the PED
RAK 84.4 and 82.4
Min. contact rating
Time constant in water
without pocket
< 15 s
with LW 7 pocket
Calibrated at
< 45 s
TW, TB
23 ± 2 °C (Tu 23)
STB
37 ± 2 °C (Tu 37)
Influence of head
temperature
Copyright © GFR mbH 2008 / Änderungen vorbehalten
Classified in the PED 97/23/EG
as per Cat. IV:
Test marking 4)
Wiring diagram
RAK 13.40
ID: 0000006982
TW
A10391
Seite 1 von 4
DIGICONTROL- Gerätedatenblatt
 depends on type
R-RAK

 Weight
0,20 – 0,60 K/K
 Transport and storage
temperature
• Permissible
ambient
temp. (head)
•
as clamp-on sensor
(water temp.)
www.gfr.de
STB
A10396
TB
A10394
0,22 kg
 –25...55 °C
Dimension drawing
M05633
 0...50 °C (T50)
Fitting instructions
MV 505803
Wiring Diagramm
Controller, monitor, limiter TR, TW
Safety temperature limiter STB
1 2 4
1 2
11 12 14
E
L1
N
PE
Temperature limiter TB
E
E
L1
N
PE
L1
N
PE
A10391
A10396
A10394
l
110
L
41
Dimension drawing
Ø6,5
25
68
Pg11
20,8
66,8
Ergänzungsdaten 1 .. n (= Texte, Bilder weiterer
M05633a
Produkteigenschaften)
Operation
The single-pole change-over contacts (or the normally-closed contacts on the TB) function according to temperature. The
adjustable setpoint Xs equals the upper switching point. The switching difference Xsd is fixed. By dovetailing their housings
together, two units can be linked to each other side by side, thereby easily allowing a double thermostat (controller-monitor
or monitor-limiter) to be employed.
On reaching the setpoint, the contacts change over and lock mechanically. Not until the temperature has fallen can the
thermostat be reset by pressing the internal ‘Reset’ knob.
Copyright © GFR mbH 2008 / Änderungen vorbehalten
Seite 2 von 4
DIGICONTROL- Gerätedatenblatt
Additional technical details
Setting accuracy
as a limiter
as a clamp-on sensor
Serviceable life
when used as a limiter
Degree of radio
interference
Material:Housing base
Housing lid
Window
± 6 K at 50 °C
+0/–9 K at 50 °C
+4 K (systematic error)
> 100 000 switchings
> 15 000 switchings
click rate < 5 (EN 55014)
R-RAK
www.gfr.de
Sensor medium:up to 160 °C
up to 230 °C
Setting accuracy
as a limiter
as a clamp-on sensor
Serviceable life
On the basis of the information currently available, no risks
to health or to the environment (as per 67/548/EEC) can be
expected if used in accordance with regulations.
PA reinforced to 120 °C
ABS, resistant to 80 °C
PC, resistant to 80 °C
Conforms to low-voltage directive 73/23/EC (EN 60730-1;2-9)
Conforms to EMC directive 89/336/EC as per EN 55014: 4.2
RAK 82.4 + 84.4 should not be used to guarantee the safety of installations which are subject to regulation 97/23/EEC
concerning pressure equipment.
Influence of temperature of instrument head
Type
Calibration
Correction factor
RAK . . . .M tolerance
*)
K
K/K
3773
±6
0,14
3770
±6
0,29
3728
±6
0,18
3754
±6
0,31
3726
±7
0,19
3729
±7
0,34
3753
±8
0,25
4040, 4050 +0 /-9
0,31
3782
±6
0,32
3783
±7
0,38
*) with respect to the ambient temperature
Technical notes
RC circuit under inductive load
For the optimum RC circuit, see specifications supplied by the manufacturer of the contactors, relays etc. If,
however, these are not available, the following rule of thumb (not binding) can be used to reduce the inductive load:• Capacitance of the RC circuit (µF) ≥ operating current (A)
• Resistance of the RC circuit (Ω) ≈ coil resistance (Ω)
B03772
Accessories
Artikelnummer
Beschreibung
0364433 001*
Indicator lamp: 250 V~ for showing the switching status on the monitor
0364435 001
Assembly kit for clamp-on and double thermostat with 2 plugs for maintaining degree of
protection IP 40, plus retaining strap for fitting to pipes of ½ “…3“ (for RAK as a clamp-on
thermostat: T < 120 °C)
As stem-type thermostat: (see chapter 29 for further details on pockets)
0364439 . . .
LW 7 pockets; of brass; R½; for one sensor cartridge
0364244 . . .
LW 15 pockets; of brass; R½, for 2-3 sensor cartridges
As thermostat with remote sensor:
0296724 000*
Sensor holder for wall mounting
0303212 000*
Rubber grommet for capillary-tube guide in air ducts; T < 50 °C
0364140 000*
Tension-relief piece for fitting in protective tubes.
0364432 001*
Fixing bracket for wall or duct mounting
0364434 001*
Supporting coil for sensor, for direct fitting in air ducts
0036787 000*
Grommet for capillary tube, with packing box; R½, brass, 12 bar, 180 °C
Copyright © GFR mbH 2008 / Änderungen vorbehalten
Seite 3 von 4
DIGICONTROL- Gerätedatenblatt
R-RAK
www.gfr.de
1)
Settings (via catches) are irreversible
2)
If under inductive load, take RC circuit into account.
3)
No pocket included; stainless-steel pockets should be used above 130 °C; see chapter 29
4)
Certificates can be downloaded from www.tuv.com
1 2
E
GFR - Gesellschaft für Regelungstechnik
und Energieeinsparung mbH
Kapellenweg 42
D-33415 Verl
phone: +49 (0) 5246 962-0
www.gfr.de / [email protected]
Löbstedter Str. 101
D-07749 Jena
phone: +49 (0) 3641 4697-0
[email protected]
07.2008 / Rev1
Copyright © GFR mbH 2008 / Änderungen vorbehalten
Seite 4 von 4