Data Sheet (English)

BL compact multiprotocol station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
■ Compact fieldbus I/O module in IP69K
■ EtherNet/IP™, Modbus® TCP, or
PROFINET® slave
■ Integrated Ethernet switch
■ 10 Mbps / 100 Mbps supported
■ Two males M12, 4-pin, D-coded, for
fieldbus connection
■ 2 rotary switches for node address
■ IP69K
■ M12 I/O Steckplätze
■ LEDs zur Anzeige von Status und Diagnose
■ Elektronik über Optokoppler galvanisch
von der Feldebene getrennt
Type code
Ident no.
BLCEN-6M12LT-4AI-VI-2AO-I
6811482
Nominal system voltage
System power supply
Voltage supply connection
Admissible range Vi
Nominal current Vi
Max. current Vi
Admissible range Vo
Nominal current Vo
Max. current Vo
24 VDC
via auxiliary power
2 x M12, 5-pin
18…30VDC
137 mA
2A
18…30VDC
50 mA
4A
Fieldbus transmission rate
Adjustment transmission rate
Fieldbus address range
Protocol detection
Web server
Service Interface
Vendor ID
Product type
Product code
10/100 Mbps
automatic detection
1…92
0 (192.168.1.254)
93 (BootP)
94 (DHCP)
95 (PGM)
96 (PGM-DHCP) *Recommended for PROFINET
97…99 (manufacturer specific)
2 dez. Drehkodierschalter
2 x M12
4-polig, D-kodiert
automatic
integriert
Ethernet
48
12
11482
Modbus TCP
Addressing
Supported function codes
Number of TCP connections
Input Data Size
Input register start address
Output Data Size
Output register start address
Static IP, BOOTP, DHCP
FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23
6
max. 6 register
0 (0x0000 hex)
max. 2 register
2048 (0x0800 hex)
■ 0/4…20 mA or -10/0…+10 VDC (kanalweise umschaltbar)
■ 2 analoge Stromausgänge
■ 0/4…20 mA
Edition • 2016-03-24T22:19:56+01:00
Fieldbus addressing
Fieldbus connection technology
■ 4 analoge Eingänge für Strom oder
Spannung
1/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
BL compact multiprotocol station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
EtherNet/IP™
Addressing
Device Level Ring (DLR)
Number of CIP connections
Input Assembly Instance
Input Data Size
Output Assembly Instance
Output Data Size
Configuration Assembly Instance
Configuration Size
Comm Format
acc. to EtherNet/IP™ specification
supported
6
103
7 INT
104
2 INT
106
0
Data - INT
PROFINET
Addressing
Conformance class
MinCycleTime
Diagnostics
Topology detection
Automatic addressing
Media Redundancy Protocol (MRP)
Input Data Size
Output Data Size
DCP
B (RT)
1 ms
acc. to PROFINET alarm handling
supported
supported
supported
max. 8 BYTE
max. 4 BYTE
from 4AI-VI
0/4 … 20 mA or -10/0 … 10 VDC
channel diagnostics
24 VDC
Strom: < 0,125 Kò, Spannung: < 98,5 Kò
< 20 Hz
< 0.3 %
< 0.05 %
< 300 ppm/ºC of full scale
16 bit
Sigma Delta
16 bit signed integer
12 bit full range left-justified
Analog outputs
Output type
Type of output diagnostics
Sensor supply
Load resistance, resistive
Load resistance, inductive
Transmission frequency
Basic fault limit at 23 °C
Repeatability
Temperature coefficient
Resolution
Measured-value display
from 2AO-I
0/4 … 20 mA
Channel diagnostics
24 VDC
< 0,45
< 1 mH
< 200 Hz
< 0.2 %
< 0.05 %
< 150 ppm / ºC v.E.
16 bit
16 Bit Signed Integer
12 bit full range left justified
Edition • 2016-03-24T22:19:56+01:00
Analog inputs
Operating modes
Type of input diagnostics
Sensor supply
Input resistance
Maximum limiting frequency analog
Basic fault limit at 23 °C
Repeatability
Temperature coefficient
Resolution
Measuring principle
Measurement display
2/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
BL compact multiprotocol station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
Dimensions
Operating temperature
Storage temperature
Relative humidity
Vibration test
Extended vibration resistance
- up to 20 g (at 10 to 150 Hz)
Shock test
Electro-magnetic compatibility
Protection class
Bei Festmontage auf Trägerplatte oder
Maschinenkörper.
nach IEC 61131-2
nach IEC 61131-2
IP67
IP69K
Nylon glasfaserverstärkt, Stecker nickelbeschichtet
black
Lexan
nickel-plated brass
Polyester with Polycarbonate overlay
nickelbeschichtetes Messing
600 ± 20 g
CE, cULus
Edition • 2016-03-24T22:19:56+01:00
Housing material
Housing color
Window material
Screw material
Label material
Ground tab material
Weight
Approvals and certificates
168 x 71 x 32.5 mm
-40…+70 ºC
-40…+85 ºC
15 to 95% (nicht kondensierend)
nach IEC 61131-2
3/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
BL compact multiprotocol station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
Ethernet
Fieldbus cable (example): RSSD RSSD 441-2M ident-no. U-02482
or RSSD-RSSD-441-2M/S2174 ident-no. 6914218
Slot 1: Analog Inputs
Pin Assignment
Extension cable (example): RK 4.5T-2-RS 4.5T/S653 ident-no.
U2187-09 or RKC4.5T-2-RSC4.5T/TEL ident-no. 6625212
2-wire connection (current)
4-wire connection technology
Edition • 2016-03-24T22:19:56+01:00
?
4/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
BL compact multiprotocol station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
Slot 2: Analog Outputs
Pin Assignment
Extension cable (example): RK 4.5T-2-RS 4.5T/S653 ident-no.
U2187-09 or RKC4.5T-2-RSC4.5T/TEL ident-no. 6625212
Auxiliary Power
Pin Assignment
Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no.
Edition • 2016-03-24T22:19:56+01:00
U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208
5/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
BL compact multiprotocol station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
Status: Station LED
LED
Color
Status
Description
OFF
Power off
RED
ON
Insufficient power supply
RED
FLASHING (1Hz)
Deviating station configuration
RED
FLASHING (4 Hz)
No module bus communication
GREEN
ON
Station OK
GREEN
FLASHING
Force mode active
OFF
No connection
GREEN
ON
Fieldbus communication active
GREEN
FLASHING (1Hz)
Fieldbus communication disabled, device status OK
RED
ON
Double MAC-ID
RED
FLASHING
Fieldbus communication timeout
GREEN
ON
I/O slots OK
GREEN
FLASHING (1Hz)
At least one I/O slot in idle state
RED
ON
At least one faulty I/O slot
RED
FLASHING
At least one I/O slot in faulty state
Color
Status
Description
OFF
Diagnostic disabled
RED
ON
Station / module bus communication failure
RED
FLASHING (0.5Hz)
Summarized diagnostic
OFF
Channel inactive
GREEN
ON
Channel active
GREEN
FLASHING (0.5 Hz)
Measuring range undershoot
GREEN
FLASHING (4 Hz)
Measuring range overshoot
Status
Description
OFF
Diagnostic disabled
RED
ON
Station / module bus communication failure
RED
FLASHING (0.5Hz)
Summarized diagnostic
IOs
MNS
IO
Status: I/O LED, slot 1
LED
D1 *
AI channels
10…13
* D1 LED also indicates gateway diagnostic
I/O LED Status Slot 2
LED
Colour
D2 *
AO channels
Not connected
0/1
Edition • 2016-03-24T22:19:56+01:00
* The D2 LED also indicates gateway diagnosis
6/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
BL compact multiprotocol station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
Prozessdaten Mapping der einzelnen Protokolle
EtherNet/IP™ I/O und Diagnosedaten Mapping
INPUT
BYTE
Bit 7
AI 10
0
AI 10 LSB
1
AI 10 MSB
2
AI 11 LSB
3
AI 11 MSB
4
AI 12 LSB
5
AI 12 MSB
6
AI 13 LSB
7
AI 13 MSB
8
Modulnummer meldet Diagnose Daten
9
Austauschsta- -
Diagnose ak- -
tion
tiv
AI 11
AI 12
AI 13
Diagnose
Steckplatz 1
10
Bit 6
-
Bit 5
-
Bit 4
-
-
Bit 3
Bit 2
Bit 1
Bit 0
-
-
-
-
-
-
Offener
Bereichsfehler
(ref. Byte 8)
Stromkreis AI AI 10
10
11
-
-
-
-
-
-
Offener
Bereichsfehler
Stromkreis AI AI 11
11
12
-
-
-
-
-
-
Offener
Bereichsfehler
Stromkreis AI AI 12
12
13
-
-
-
-
-
-
Offener
Bereichsfehler
Stromkreis AI AI 13
13
OUTPUT
BYTE
Bit 7
AO 20
0
AO 20 LSB
1
AO 20 MSB
2
AO 21 LSB
3
AO 21 MSB
AO 21
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Modbus TCP Register Mapping
REG
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
0x0000
AI 10
0x0001
AI 11
0x0002
AI 12
0x0003
AI 13
Status (RO)
0x0004
-
FCE
-
-
CFG
COM
VI low -
Diag. (RO)
0x0005
-
-
-
-
-
-
-
-
Outputs (RW)
0x0800
AO 20
0x0801
AO 21
-
-
-
-
-
OCAI
MRAI
11
11
OCAI
MRAI
13
13
Inputs (RO)
I/O Diag. (RO) 0xA000
0xA001
-
-
-
-
-
-
Bit 8
Bit 7
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
VO low -
-
-
-
-
-
DIA
-
-
-
-
-
-
S2 DIA S1 DIA
-
-
-
-
-
-
OCAI
MRAI
10
10
OCAI
MRAI
12
12
-
Bit 6
-
-
-
-
-
PROFINET® Process Data
Edition • 2016-03-24T22:19:56+01:00
Eingänge
Ausgänge
7/7
BYTE
Bit 7
0
AI 10 LSB
1
AI 10 MSB
2
AI 11 LSB
3
AI 11 MSB
4
AI 12 LSB
5
AI 12 MSB
6
AI 13 LSB
7
AI 13 MSB
0
AO 20 LSB
1
AO 20 MSB
2
AO 21 LSB
3
AO 21 MSB
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com