MARINE & SHIPBOARD CABLES MX HX INSULATED FLAME RETARDANT SWITCHBOARD WIRE FLAME RETARDANT / LOW SMOKE EMISSION / WITHOUT POISONED AND CORROSIVE GASES / HX INSULATION 105° C CONSTRUCTION 1 - Conductor 2 - Insulation 3 - Insulation Colour IEC 60228 CLASS 5 TINNED OR PLAIN COPPER IEC 60092-351 CROSS-LINKED HFFR COMPOUND RAL 9005 BLACK; OTHER COLOUR ON REQUEST TECHNICAL CHARACTERISTICS INSULATION RESISTANCE (MIN) TEST VOLTAGE OPERATING VOLTAGE BENDING RADIUS MΩxKm 3,5 kV. AC 0,6/1kV 4x D TEMP. RANGE FLAME RETARDANT TEST SMOKE DENSITY -40ºC~+ 105ºC IEC 60332-1-2 IEC 61034-2 500 APPLICATION IEC 60332-3-22 (CAT A) For fixed wiring in switchboards, control panels and other enclosures DESIGN STANDARDS IEC 60092-350 IEC 60092-351 IEC 60092-359 IEC 60092-353 CODE NR. 353015010 353025010 353040010 353060010 35301 0 01 0 3 5 3 01 6 01 0 3 5 3 02 1 0 1 0 353035010 353005010 353070010 353095010 353012010 353055010 3 5 3 01 8 01 0 353024010 8 CROSS SECTION (mm2) 1 x 1,5 1 x 2,5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 OVERALL DIAMETER (mm) 2 , 90 3 , 60 4 , 10 4 , 70 6 , 00 7 , 50 9 , 00 10 , 00 11 , 80 13 , 60 16 , 60 18 , 00 20 , 10 22 , 00 26 , 00 TEST ON CORROSIVENESS OF COMBUSTION GASES HALOGENFREE TEST IEC 60754-2 IEC 60754-1 COPPER WEIGHT (kg/km) 14 23 37 56 93 138 200 276 393 553 760 968 1210 1520 2005 APPROX. WEIGHT (kg/km) 22 35 51 76 123 173 257 340 477 649 891 1111 1287 1732 2280 CURRENT RATING (A) 22 29 37 51 71 94 125 156 195 240 292 339 388 443 522 MIN. BENDING RADIUS (mm) 12 14 16 19 24 30 34 36 40 48 54 67 62 89 105