Schematic diagram (sample)
Bleed and drain of main riser (on site)
Module main riser TTV (thermostatic temperature lead module)
Ball valves (on site)
KaMo – TW-Mini
Installation type 1 without modules
Shower, wash basin, etc.
Compact radiator
Heat meter and water
meter unit (on site)
Standard radiator
Differential pressure valve (0,1 bar) or dynamic volume
flow limiter (on site) (to be adjusted according to water
quantity for heating circuit).
KaMo WK-Mini
Complete equipment
Installation type 2
Shower, wash basin, etc.
Compact radiator
Standard radiator
Heat meter and water
meter unit (on site)
KaMo WK-Mini
Complete equipment
Installation type 3
Floorheating
Compact radiator
heating flow
Cold water
heating return
Shower, wash basin, etc.
control mixing unit
Heat meter and water
meter unit (on site)
Shut-off of main riser with
bleed and drain (on site)
Distribution pipe
Seite 2
Note:
Hydraulic diagram is a basic scheme.
All indications do not claim to be complete
and are without liability.
WK-Mini-Budget
Indirect Hydraulic Interface Units
Price valid for orders of 100 units or more.
Type
WK-M-B
Article No.
Indirect heat interface unit to produce DHW with
separate heat circuit (2 pipe system) –
non modular
Euro
608,00
WK-M-B unit 15l/min. 22 plate heat exchanger
Including the following components:
NP 22-22
43000305
193,00
surplus stainless steel heat exchanger, nickel soldered,
22 plates
DRG – Differential pressure valve for secondary
heating circuit
TWR – Thermostatic hot water temperature
control
Hard-foam cover – highly thermo-insulated
Additional components
Type
WK-KAS/D6
Article No.
41000075
Euro
56,00
set of 6 ball valves (2 x blue, 2 x red, 2 x green)
Note: For electronic control components please see page 6.
1 Heat exchanger WP22-22
4 distance piece for heat meter optinally 110 x ¾” or 130 x 1”
8 distance piece for cold water meter 110 x ¾”
9 Differential pressure valve
11 Thermostatic hot water temperature control
14 sensor for heat meter
60 Strainer
61 Sensor for TWR
14
B
60
61
C
D
4
8
A DHW for apartment
B Cold water from riser
C Heating flow primary
D Heating return primary
E Heating flow secondary
F Heating return secondary
G Cold water for apartment
11
1
9
G
Primary flow
70 °C
75 °C
80 °C
85 °C
Primary return
30 °C
27 °C
26 °C
26 °C
Heating volume flow
900 l/h
750 l/h
926 l/h
814 l/h
Capacity
ca. 42 kW
ca. 42 kW
ca. 56 kW
ca. 56 kW
DHW-capacity
15 l/min
15 l/min
20 l/min
20 l/h
DHW-temperature
50 °C
50 °C
50 °C
50 °C
DCW-temperature
10 °C
10 °C
10 °C
10 °C
dp Heating
ca. 220 bar
ca. 0,190 bar
ca. 0,220 bar
ca. 0,200 bar
dp Water
ca.1 bar
ca. 1 bar
ca. 1,3 bar
ca. 1,3 bar
F
A
E
Seite 3
WK-Mini
Indirect Hydraulic Interface Units
Type
WK-M-1
Article No.
41001302
Euro
569,50
Basic unit 12l/min. 16 plate heat exchanger
NP 22-16
43000373
157,00
surplus stainless steel heat exchanger, nickel soldered,
16 plates
Type
WK-M-2
Article No.
41001303
Indirect heat interface unit
to produce DHW with
seperate heat circuit
(2 pipe system)
Euro
657,00
Basic unit 15l/min. 22 plate heat exchanger
NP 22-22
43000305
193,00
surplus stainless steel heat exchanger, nickel soldered,
22 plates
Illustration shows unit with basic equipment
Additional components
Type
WK-KAS/D6
Article No.
41000075
Euro
56,00
set of 6 ball valves (2 x blue, 2 x red, 2 x green)
Type
WS-TWR
Article No.
41001042
Euro
104,00
thermostatic hot water control "TWR" 20-50 °C for
underfloor heating
Type
WS-TWR
Article No.
41001025
Euro
104,00
thermostatic hot water control "TWR" 40-70 °C
Type
WK-M-DRG
Article No.
41001311
Euro
149,50
differential pressure valve (setting range 50-300 mbar)
Type
WK-M-RTB
Article No.
41001316
Euro
67,00
return temperature limiter (sec.heat circuit-pre
adjusted 37,5 °C)
Type
WK-M-SF
Article No.
41001314
Type
WS-TTV-S
Article No.
41001317
Euro
131,50
thermostatic temperature lead module, One per riser
Type
WS-TTV-SK
Article No.
41001319
Euro
181,00
thermostatic temperature lead module, TTV, mounted
at end of riser (on site, incl. ball valve, bleed/drain
valve), One per riser
Euro
33,50
strainer secondary-return
Note: For electronic control components please see page 6.
Pumps and accessories
Type
WK-M-PM
Article No.
41001318
Covers
Euro
179,00
injection circuit (without pump and actuator)
Type
WK-M-F
Article No.
43000144
3-point actuator
Seite 4
Article No.
43000348
Euro
158,50
high efficiency pump for underfloor heating ( Laing,
Auto EG)
Euro
81,50
fixed command control
Type
WK-M-E
Type
WK-PL
Type
WK-PA
Article No.
43000379
Euro
on request
high efficiency pump for underfloor heating
(Grundfos ALPHA)
Article No.
43000333
Euro
117,50
Type
Article No.
Euro
on request
WK-M-AP
41001320
cover survace mounted,
Dimensions (mm): width: 375, height: 442, depth: 280
Type
Article No.
Euro
on request
WK-M-AP-S
41001312
cover surface mounted (with viewing hole
100 x 100 mm)
Order example
Art. No.
Type
Euro
43100031 room thermostat analog 230 V, 7 days program
41001302 WK-M-1 basic unit 12l/min. 16 plate heat exchanger
41001317 thermostatic temperature lead module, TTV, connected on unit
569,50
131,50
41001042 thermostatic hot water control "TWR" 20-50° C for underfloor heating 104,00
43100115 actuator 230 V, ( currentles closed )
19,00
41001316 return temperature limiter (sec.heat circuit - pre adjusted 37,5°C)
67,00
41000075 set of 6 ball valves (2 x blue, 2 x red, 2 x green)
56,00
Basic Unit
Full equipment
1 Stainless steel plate heat exchanger
2 PM – valve with priority circuit for DHW
3 Cold water limitation plate
4 Distance piece for heat meter (3/4” x 110 mm, Qn 1,5)
5 Air vent of the unit (only unit, not plant)
6 Zone valve for limitation of heating volume flow
7 Multifunctional block for the allocation of further components,
immersion sleeve in flow line for heat meter sensor M10x1
16 Base plate, Dimensions (mm): width: 298, height: 440, depth: 216
26 Strainer – flow primary
27 Strainer DCW
A DHW for apartment
B DCW from riser
C Heating water – primary flow
9 Differential pressure valve DRG in entrance of the unit
10 Thermostatic lead module TTV
11 Thermostatic hot water control TWR
12 Strainer for apartment heating circuit
20 Ball valves ¾” internal thread
D Heating water – primary return
E Heating – secondary flow
F Heating – secondary return
Capacity production of DHW WK1-Mini:
Primary flow:
70 °C, 65 °C, 65 °C
Primary return:
32 °C, 35 °C, 31 °C
Heating volume flow: 760 l/h, 960 l/h, 925 l/h
Capacity:
34kW, 34 kW, 36,5 kW
DHW-capacity:
12l/min, 12 l/min, 15 l/min
DHW-temperature:
50 °C, 50 °C, 45 °C
DCW-temperature:
10 °C, 10 °C, 10 °C
Capacity production of DHW WK2-Mini:
Primary flow:
65 °C, 70 °C
Primary return:
27 °C, 30 °C
Heating volume flow: 828 l/h, 900 l/h
Capacity:
36,5kW, 42kW
DHW-capacity:
15l/min, 15l/min
DHW-temperature:
45 °C, 50 °C
DCW-temperature:
10 °C, 10 °C
Capacity during heating operation:
Primary flow:
70 °C, 65 °C
Primary return:
50 °C, 45 °C
Heating volume flow: 645 l/h 645 l/h
Capacity:
15 kW 15 kW
Seite 5
WK-Mini Plus
Indirect Hydraulic Interface Units
Type
WK-MP-1
Article No.
41001201
Euro
511,00
Indirect heat interface
unit to produce DHW with
seperate heat circuit
(2 pipe system)
Basic unit 12l/min. 16 plate heat exchanger
Type
WK-MP-2
Article No.
41001202
Euro
529,50
Basic unit 15l/min. 22 plate heat exchanger
Additional components
Type
TW-KAS/D4
Article No.
41000007
Pumps and accessories
Euro
37,50
Article No.
41001042
Euro
104,00
thermostatic hot water control "TWR" 20-50 °C for
underfloor heating
Type
WS-TWR
Article No.
41001025
Euro
104,00
thermostatic hot water control "TWR" 40-70 °C
Type
WS-WMZ
Article No.
49000014
Article No.
41001311
Euro
146,00
differential pressure valve (setting range 50-300 mbar)
set of 4 ball valves (2 x blue, 2 x red)
Type
WS-TWR
Type
WK-M-DRG
Type
WS-TTV-S
Article No.
41001317
Euro
131,50
thermostatic temperature lead module
Type
WS-TTV-SK
Article No.
41001319
Article No.
41001205
Euro
164,00
injection circuit (without pump and actuator)
Type
WK-PL
Article No.
43000348
Euro
158,50
high efficiency pump for underfloor heating ( Laing,
Auto EG)
Euro
181,00
thermostatic temperature lead module, TTV, mounted
at end of riser (on site, incl. ball valve)
Euro
13,50
Type
WK-PA
Article No.
43000379
Euro
on request
high efficiency pump for underfloor heating
(Grundfos ALPHA)
Type
WK-M-F
assembling heat meter
Article No.
43000144
Euro
81,50
Article No.
43000333
Euro
117,50
Article No.
43100188
Euro
20,50
fixed command control
Cover
Type
WK-M-AP
Type
WK-MP-PM
Article No.
41001206
Type
WK-M-E
Euro
3-point actuator
on request
cover survace mounted,
Dimensions (mm): width: 465, height: 342, depth: 300
„230 V“ electric control units
Type
WS-KTS
Article No.
43100115
Euro
19,00
actuator 230 V, ( currentles closed )
Type
WS-KTS-O
Article No.
43100069
Article No.
43100016
Euro
23,00
Article No.
43100017
room thermostat , flush mounted, 230 V
Seite 6
Article No.
43100073
Euro
30,25
Type
WS-RTU-P
Article No.
43100018
Euro
44,00
room thermostat flush mounted (night setback) 230 V
Euro
17,00
room thermostat on-wall, 230 V
Type
WS-RTU
Type
WS-RTA-P
room thermostat with night setback, on wall, 230 V
actuator 230 V, ( currentles open )
Type
WS-RTA
„24 V“
Type
WS-UTW
Article No.
43100031
Euro
92,00
room thermostat analog 230 V, 7 days program
Euro
39,50
Type
WS-ZP-RTA
Article No.
43100074
Euro
2,25
between plate for all room thermostats without
analog clock
Type
WS-KTS-24
actuator 24 V, (currentles closed)
Type
WS-RTU-P-24
Article No.
43100190
Euro
34,00
actuator 24 V, (currentles open)
Type
WS-UTW-24
Article No.
43100189
Euro
145,00
room thermostat analog 24 V, 7 days program
Type
WS-Trafo
transformator 230V/24 V
Article No.
43100191
Euro
87,00
Order example
Art. No.
Type
Price
41001202 WK-MP-2 Basic unit 12l/min. 22 plate heat exchanger
529,50
41001042 thermostatic hot water control "TWR" 20-50 °C for underfloor heating 104,00
41001311 differential pressure valve (setting range 50-300 mbar)
146,00
41001205 injection circuit (without pump and actuator)
164,00
Basic Unit
Full equipment
1 Stainless steel plate heat exchanger
2 PM – valve with priority circuit for DHW
3 Cold water limitation plate
4 Distance piece for heat meter (3/4” x 110 mm, Qn 1,5)
5 Air vent of the unit (only unit, not plant)
16 Base plate, Dimensions (mm): width: 445, height: 225, depth: 294
27 Strainer DCW
A DHW for apartment
B DCW from riser
C Heating water – primary flow
D Heating water – primary return
E Heating – secondary flow
F Heating – secondary return
Capacity production of DHW WK-Mini Plus:
Primary flow:
70 °C, 65 °C
Primary return:
32 °C, 35 °C
Heating volume flow: 780 l/h, 957 l/h
Capacity:
34 kW, 34 kW
DHW-capacity:
12 l/min, 12 l/min
DHW-temperature:
50 °C, 50 °C
DCW-temperature:
10 °C, 10 °C
9 Differential pressure valve DRG in entrance of the unit
11 Thermostatic hot water control TWR
20 Ball valves ¾” internal thread
22 Not return valve in bypass
24 Control valve (Kvs 2,5) with fixed command control and STB: safety temperature limiter
Capacity during heating operation:
Primary flow:
70 °C, 65 °C
Primary return:
50 °C, 45 °C
Heating volume flow: 645 l/h, 645 l/h
Capacity:
15 kW, 15 kW
Technical specification:
Max. working pressure heating:
Max. working pressure sanitary:
Max. operating temperature heating:
Max. differential pressure heating:
Min. primary pressure sanitary:
Dimensions of base plate w/h/d:
Material fittings:
PN 10
PN 10
85 °C
2,5 bar
2,0 bar
445 x 225 x 294 mm
CW 617 N
Seite 7
TW-Mini
Indirect Hydraulic Interface Units
Type
TW-M-1
Article No.
41001301
Euro
512,00
Basic unit 12l/min. 16 plate heat exchanger
NP 22-16
43000373
157,00
surplus stainless steel heat exchanger, nickel soldered,
16 plates
Type
TW-M-2
Article No.
41001304
Indirect heat interface
unit to produce DHW
(2 pipe system)
Euro
551,00
Basic unit 15l/min. 22 plate heat exchanger
NP 22-22
43000305
193,00
surplus stainless steel heat exchanger, nickel soldered,
22 plates
Illustration shows unit with basic equipment
Additional components
Type
TW-KAS/D4
Article No.
41000007
Euro
37,50
set of 4 ball valve ( 1 x blue, 1 x red, 2 x green)
Type
TW-M-DRG
Article No.
41001321
Euro
166,50
differential pressure valve (setting range 50-300 mbar)
Type
TW-M-TWR
Article No.
41001313
Euro
133,50
thermostatic hot water control "TWR" 40-70 °C
Cover
Type
TW-M-AP
Article No.
41001325
Euro
on request
cover surface mounted,
Dimensions (mm): width: 310, height: 500, depth: 190
Seite 8
Type
WS-TTV-S
Article No.
41001317
Euro
131,50
thermostatic temperature lead module, TTV, mounted
at end of riser (on site)
Type
WS-TTV-SK
Article No.
41001319
Euro
181,00
thermostatic temperature lead module, TTV, mounted
at end of riser (on site, incl. ball valve)
Type
TW-M-TTV
Article No.
41001322
Euro
73,00
thermostatic temperature lead module, connected on unit
Type
TW-M-SF
Article No.
41001323
Euro
21,00
Article No.
41001324
Euro
76,00
strainer primary flow
Type
TW-M-WMZ
distance piece mounted in the unit
Type
WS-WMZ
assembling heat meter
Article No.
49000014
Euro
13,50
Order example
Art. No.
Type
Price
41001301 TW-M-1 Basic unit 12l/min. 16 plate heat exchanger
497,00
41001321 differential pressure valve (setting range 50-300 mbar)
166,50
41000007 set of 4 ball valves (1 x blue, 1 x red, 2 x green)
37,50
Basic Unit
Full equipment
1 Stainless steel plate heat exchanger
2 PM – valve with priority circuit for DHW
3 Cold water limitation plate
4 Distance piece for heat meter (3/4” x 110 mm, Qn 1,5)
5 Air vent of the unit (only unit, not plant)
7 Multifunctional block for the allocation of further components
16 Base plate, Dimensions (mm): width: 298, height: 410, depth: 155
26 Strainer – flow primary
27 Strainer DCW
A DHW for apartment
B DCW from riser
9 Differential pressure valve DRG in entrance of unit
10 Thermostatic lead module TTV
11 Thermostatic hot water control TWR
13 Bleed-drain valve
20 Ball valves ¾” internal thread
C Heating water – primary flow
D Heating water – primary return
Capacity production of DHW TW1-Mini:
Primary flow:
70°C, 65°C, 65°C
Primary return:
32°C, 35°C, 31°C
Heating volume flow: 760l/h, 960l/h, 925l/h
Capacity:
34kW, 34kW, 36,5kW
DHW-capacity:
12l/min, 12l/min, 15l/min
DHW-temperature:
50°C, 50°C, 45°C
DCW-temperature:
10°C, 10°C, 10°C
Capacity production of DHW TW2-Mini:
Primary flow:
65°C, 70°C
Primary return:
31°C, 30°C
Heating volume flow: 925 /h, 900l/h
Capacity:
36,5kW, 42kW
DHW-capacity:
15l/min, 15l/min
DHW-temperature:
45°C, 50°C
DCW-temperature:
10°C, 10°C
Technical specification:
Max. working pressure heating:
Max. working pressure sanitary:
Max. operating temperature heating:
Max. differential pressure heating:
Min. primary pressure sanitary:
Dimensions of base plate w/h/d:
Material fittings:
PN 10
PN 10
85 °C
2,5 bar
2,0 bar
298 x 420 x 216 mm
CW 617 N
Seite 9
Heat Exchanger:
Nickel-soldered stainless steel plate heat exchanger ( SVGW approved )
Max. working pressure, heating: PN16
Max. working pressure, DHW: PN16
Max. operating temperature: 90°C
Ball Valves
Ball Valves for Heating and DHW
Technical specification Ball Valves for heating:
¾” female thread
handle (50 mm) red/blue
overall length 68 mm
internal diameter 16 mm
material: CW617N
min. wall thickness 2 mm
min. max. operating temperature -10°C - +120°C
max. working pressure PN40
Differential pressure valve „DRG“ –
primary heating input:
Curing diaphragm in a red brass body
Setting range 50-300 mbar
M30 x 1,5 connection
Pre adjusted on 250 mbar
Diaphragm module fixed on primary heating return
Capillary pipe fixed on primary flow
Seite 10
Technical specification Ball Valves for DHW:
¾” female thread
handle (50 mm) green
overall length 68 mm
internal diameter 16 mm
material: CW602N
DVGW-approved
min. wall thickness 2 mm
min. max. operating temperature -10°C - +120°C
max. working pressure PN40
Technical specification:
Max. working pressure heating PN10
Max. operating temperature heating 90°C
Max. primary differential pressure heating 2,5 bar
Thermostatic hot water control set “TWR”
Valve with pressure relieved insert,.application up to 4
bar primary differential pressure
Control range 20-50°C / 40-70°C, adjustment terminable and lockable
Reaction time: +/- 3K
Technical specification:
Max. working pressure PN10
Max. operating temperature 90°C
Max. primary differential pressure 4 bar
Return flow temperature limiter RTB:
Assures a specific return temperature of the heating
circuit. For example 60/40°C. Valve with adjusting
scale, directly immerged sensor cartridge, for fast reaction time, pre adjustment lockable
Setting range 0-45°C
Hysteresis +/-2-3 K
Assembling secondary heating return
Connection ¾” male, conical
Pipe section stainless steel 1.4401 or 1.4521, 18x1 mm
Technical specification:
Max. working pressure PN10
Max. operating temperature 90°C
Max. primary differential pressure heating 2,3 bar
Pre adjusted 37,5°C
Kvs value 1,55
Strainer secondary return:
Buckler with internal Allen key 5 mm. Pipe section
stainless steel 1.4401 or 1.4521, 18x1 mm.
Strainer insert 0,5 mm.
Technical specification:
Max. working pressure PN10
Max. operating temperature 90°C
Connection 2 x ¾” male, flat sealed
Material: CW617N
Mesh: stainless steel
Shutoff valve in primary return, without
actuator
Multifunctional base part, with pressure relieved
insert, connection for actuatorM30 x 1,5 incl. pipe
section.
Technical specification:
Max. working pressure heating PN10
Max. operating temperature heating 90°C
distance piece made of stainless steel 1.4401
or 1.14521
Max. primary differential pressure 4 bar, Kvs 3,5
Distance piece for shutoff valve , primary
return
Transition piece for ball valve (length 59 mm),
adapter elbow 1” F x 1” M
Transition piece for ball valve (length 76,5 mm),
adapter elbow ¾” F x ¾” F
Technical specification:
Max. working pressure PN10
Max. operating temperature 90°C
distance piece made of stainless stell 1.4401
or 1.14521
Kvs 6
Distance piece made of stainless steel
For replacement of the standard distance piece made of plastic
Injection circuit with outlet for static heat
circuit „PM“, without pump and actuator
Pipe section made of stainless steel 1.4401 or 1.4521, for
direct connection to the heatboard. Transition piece made
of brass, valve with kvs value 0,06-0,9. Pre-adjusted kvs
value 0,5, adapter for actuator M30 x 1,5. Non-return
valve in bypass, distance piece for external pump ¾” x 1”
Thermally decoupled.
Technical specification:
Max. working pressure heating PN10
Max. operating temperature 90°C
Pipes made of stainless steel 1.4401 or 1.14521
Max. primary differential pressure, heating 2 bar
Max. primary volume flow for heating 645 l/h
Max. performance data according below example:
Primary heating flow temp. 65 °C
Secondary flow temp. underfloor heating 45 °C
(outside temp. -15 °C)
Secondary return temp. underfoor heating 35 °C
(outside temp. -15 °C)
Primary heating return temp. 35 °C
Performance date for static heat circuit:
Primary/secondary heating flow temperature 65 °C
Secondary heating return temperature 45°C
Volume flow: 365 l/h
Heat capacity up to 8,5 KW
Zone valve for static heat circuit provided by
customer
Heat capacity up to 10 KW (underfloor heating)
Primary heating volume flow 280 l/h
Secondary heating volume flow 840 l/h
Bypass volume flow 560 l/h
High efficiency pumps on request:
Laing Auto E6 or Wilo Stratos Pico 25/1-6 130
Thermostatic temperature lead module TTV, mounting
on heat board. To maintain the heating flow temperature on the primary flow/return on the heat board,
if there is no heating operation or DHW production.
The temperature adjustment is lockable by sealing wax.
Ball valves have to be installed on site,
Adjustment range 35-60 °C, Hysteresis +/- 2-3 K
Mounting on heat board
Technical specification:
Max. working pressure heating PN10
Max. operating temperature 90 °C
Max primary differential pressure,
heating 2,0 bar
Pre adjusted on 45 °C
Thermostatic temperature lead module „TTV“,
mounting on main riser
To maintain the heating flow temperature on the main
riser, if there is no heating operation or DHW production. The temperature adjustment is lockable by
sealing wax. Ball valves have to be installed on site,
Adjustment range 35-60 °C, Hysteresis +/- 2-3 K
Mounting on the end of main riser
1 x Ball valve with red handle
1 x Ball valve with blue handle
2 x drain/bleed valve
Technical specification:
Max. working pressure PN10
Max. operating temperature 90°C
Max. primary differential pressure, heating 2,0 bar
Pre adjusted 45°C
Thermostatic temperature lead module „TTV“,
mounting on heat board
To maintain the heating flow temperature on the primary flow/return on the heat board,
if there is no heating operation or DHW production. The
temperature adjustment is lockable by sealing wax.
Ball valves have to be installed on site,
Adjustment range 35-60 °C, Hysteresis +/- 2-3 K
Mounting on heat board
Technical specification:
Max. working pressure heating PN10
Max. operating temperature 90 °C
Max primary differential pressure, heating 2,0 bar
Pre adjusted on 45 °C
Seite 11
Cover surface mounted
Hanging on the wall surface, galvanized, zinc-coated
steel, white powder-coated Design to avoid condensation or retained warmth
Technical specification:
Colour: RAL 9016
Material thickness 1,5 mm
Actuator 230 V
for heating zone valve, electroless-closed, protection
class IP54, operating display, first open function, lower
connection size M30 x 1,5 mm click connection
Actuator 24 V
technical specification:
max. operating temp. 90°C
cable connection 1 m with end sleeve
electrical connection 230 V
function: electroless closed NC
technical specification:
electrical connection 24 V
Room temperature control 230 V
analogue clock, 230 V, and switch pin
adjustable week/day program, with function
off/day/night/automatic
mounting on wall
Room temperature control 24 V
analogue clock, 24 V.
Room thermostat without time control / in-wall or on-wall
Control dial with temperature scale 5-30°C
Protection class IP30
Electrical connection 230 V
Breaking capacity 10A
Color white
Room thermostat / in-wall or on-wall
Control dial with temperature scale 5-30°C
Switch heating/night setback, Mode switch day/night/AUTO
Protection class IP30
Electrical connection 230 V
Breaking capacity 10A
Color white
KaMo Frischwarmwassersysteme GmbH
Max-Planck-Straße 11
89584 Ehingen
Telefon:
Fax:
0 73 91 / 70 07-0
0 73 91 / 5 43 15
E-Mail:
Internet:
[email protected]
www.kamo.de
43100102 / 1. Auflage 06/14
Transformator 230 V / 24 V
Protection class IP67
Capacity 0,7 Ampere
Color white
With connection box
For mounting on base plate