OptiCool Energy ROI 6-11-13

Estimated Return-on-Investment (ROI)
Energy Company
New Data Center
May 11, 2013
OptiCool® Solution Summary
Number of Equipment Racks with Cooling
52 Racks
Number of Active Heat Extractor (AHX) Units
104 AHX Cooling Units
Number of 210 kW Refrigerant Pumps
2 Chilled Water Pump
Average Cooling per Rack
8.1 kW
Competitive ROI Summary
CRAC Solution
Number of Systems Required for N+1
Sensibile Cooling Capacity / kW
Sensibile Cooling Capacity / BTU
CAPEX Investment (Installed Cost)
Incremental Cooling Footprint Construction Cost
Energy Incentive Subsidy Offset
Total Net CAPEX
7 CRACs
423.5 kW
1,445,042 BTU
$518,000
$26,180
$0
$544,180
OptiCool®
2
RPW
420
kW
1,433,100 BTU
696,000
$0
($61,758)
$634,242
Savings / Delta
($178,000)
$26,180
$61,758
($90,062)
Annual Operating Costs
Energy Usage
Annual Energy Cost
Annual Maintenance
Total Net OPEX
73.5 kW
$64,386
$40,000
$104,386
3 kW
$2,628
$40,000
$42,628
70.5 kW
$61,758
$0
$61,758
1.46
ROI Payback Period (in years)
Total Cost of Ownership (15 year period)
$2,109,970
$1,273,662
Years
$836,308
Additional Benefits of the OptiCool® Solution
OptiCool® Space Savings Based on "Cooling Footprint" Floor Space Reduction in the Data Center
OptiCool®Annual Impact on Carbon Footprint
119
(7,050)
Square Feet
Kilograms