PLA33 leaflet

PLA33 power line analyser
s i m p l y
s m a r t
s o l u t i o n
Power line analyser PLA33 is a modern device for
multifunction monitoring of main electrical parameters in
three­phase network. Device measures parameters
according to norm IEC 61000­4­30 and it is ideal for very
precise power management.
Internal memory and communication interface define the
PLA33 being used as power monitoring recorder or part of
SCADA systems.
• 4 quadrant continual measurement
• monitoring of U in every phase and phase­phase
• monitoring of I in every phase
• calculated current in neutral wire
• system frequency
• THD U and THD I
• odd harmonics of U and I till 19th (L1, L2, L3)
• power factor (L1) and cosφ (L1, L2, L3)
• P+/­, Q+/­, S (L1, L2, L3, ∑)
• Eactive+/­, Ereactive+/­ (L1, L2, L3, ∑)
• internal current transformers ICT
• measurement according the standard IEC 61000­4­30
• measuring phase­phase voltage from 0 ... 520 VAC
• auxiliary power supply
• memory for recording of maximums / minimums
• memory for recording of 20 power cut events
• internal real­time clock
• communication interface RS485 with Modbus RTU protocol
• internal memory 512MB for measured parameters recording
• minimum internal memory sampling period 60s (AVG value)
• two independent digital input / output
BMR trading, Horní lán 17, 779 00 Olomouc, Czech Republic, tel.: +420 778 066 566, export@bmr­trading.com, www.bmr­trading.com
PLA33 power line analyser
s i m p l y
s m a r t
s o l u t i o n
Measured parameters
Parameter
L1
L2
L3
Phase voltage, L ­ N
●
●
●
N
Line voltage, L ­ L
Frequency
●
Current
●
●
L2­3
●
●
L3­1 ∑L1­3 Max
●
●
Power factor
Measuring range
Displayed range
Accuracy
±0,5 %
●
●
10 ... 300 V
0 V ... 180 kV
●
●
●
10 ... 520 V
0 V ... 312 kV
±0,5 %
●
●
40 ... 70 Hz
40 ... 70 Hz
±50 mHz
●
●
0,01 ... 6 A
0 ... 7,5 kA
±0,5 %
●
●
­
0 ... 7,5 kA
±0,5 %
●
●
●
0,01 L ... 0,01 C
0,01 L ... 0,01 C
±1 %
●
●
●
0,01 L ... 0,01 C
0,01 L ... 0,01 C
±1 %
●
●
Min AVG
●
●
●
Current in neutral ­ calculated
Cosφ
L1­2
THDU, L ­ N
●
●
●
●
●
0 ... 99,9 %
0 ... 99,9 %
±5 %
THDI
●
●
●
●
●
0 ... 99,9 %
0 ... 99,9 %
±5 %
Harmonics U, odd up to 19th
●
●
●
●
●
0 ... 99,9 %
0 ... 99,9 %
±5 %
Harmonics I, odd up to 19th
●
●
●
●
●
0 ... 99,9 %
0 ... 99,9 %
±5 %
Apparent power, S
●
●
●
●
●
●
0 ... 5,4 kVA
0 ... 999 MVA
±0,8 %
Active power +/­
●
●
●
●
●
●
0 ... 5,4 kW
0 ... 999 MW
±0,8 %
Reactive power +/­
●
●
●
●
●
●
0 ... 5,4 kVAr
0 ... 999 kVAr
±1 %
Active energy +/­
●
●
0 ... 9 999 999 kWh
0 ... 9 999 999 kWh
class 1
Reactive inductive energy +/­
●
●
0 ... 9 999 999 kVArh
0 ... 9 999 999 kVArh
class 2
Reactive capacitive energy +/­
●
●
0 ... 9 999 999 kVArh
0 ... 9 999 999 kVArh
class 2
<1s
<1s
Supply voltage interuptions
Device variants
Type
RS485 interface
Inputs/outputs
Flash memory
Energy memory
panel
PLA33 L
PLA33
PLA33 C
PLA33 CM
●
●
●
●
●
●
●
●
●
PLA33DL
PLA33DL CM
panel
panel
panel
DIN rail
PLA33DL L
PLA33DL C
Mounting
●
●
●
●
●
●
●
●
●
DIN rail
DIN rail
DIN rail
BMR trading, Horní lán 17, 779 00 Olomouc, Czech Republic, tel.: +420 778 066 566, export@bmr­trading.com, www.bmr­trading.com
PLA33 power line analyser
s i m p l y
s m a r t
s o l u t i o n
Technical features
Parameter
Value
Power supply voltage
230 VAC (+10%, ­15%), 50Hz or 24 V AC/DC
System frequency
45 Hz ... 65 Hz
Current range (without current transformer)
10 mA ... 6 A
Measuring voltage L­N (without voltage transformer)
10 ... 300 VAC
Measuring voltage L­L (without voltage transformer)
10 ... 520 VAC
Grid type
TN, TT, IT (with virtual resistor N bridge)
Power consumption
1,5 VA
Sampling frequency
6,4 kHz
Number of outputs / inputs
2
Output type
Open collector, free potential optical insulated (S0)
Data memory
512 MB Flash memory (PLA33CMB variant)
Minimum flash recording interval
60s
Powercut event memory
20 events
Voltage and current transformer ratio
1 ... 1500
Communication interface
RS485
Communication protocol
Modbus RTU
Communication speed
9,6 / 19,2 / 38,4 / 57,6 / 115 kBd
Over­voltage class
300 V CAT III
Pollution degree
2
Ambient working temperature
­25°C ... +60°C
Dimensions PLA33
96 x 96 x 55 mm
Dimensions PLA33DL
5 standard DIN modules
Weight
620 g
Protection degree
IP54 front panel, IP20 rear cover
Related standards
EN 61010­1, EN 60947­1, EN61000­6­2, 2­4, 6­3
BMR trading, Horní lán 17, 779 00 Olomouc, Czech Republic, tel.: +420 778 066 566, export@bmr­trading.com, www.bmr­trading.com