Fan Filter Unit

AIR FILTER TECHNOLOGY
FAN FILTER UNIT
(FFU)
Specifications
• Easy installation into cleanroom grids
• Snap-in, washable prefilter for easy
replacement and maintenance
• Silent operation (65 dBA)
• Guaranteed leak-free
• Self-contained ceiling fan filter unit
• Diffrential pressure gauge available on request
• Replacement Hepa Filter from room side or ceiling side
• Flexible dimensions
• Uniform Air Velocity
• Adjustable airflow with variable
speed controller on request
• Low operating cost, low wattage
• AC or EC fans optionally
Filter Media; High quality glass fibre
Design; Compact, Seperated and Gel type
Fan Motor; AC or EC fans
Filter Separators; Hotmelt
Max. Operating Temperature; 75°C
Recommended Final Pressure Drop; 400 Pa
Recommended Prefilters; G4, F7 (EN779-2012)
Unit Frame type; Aluminium, Galvanized or Stainless Steel
Applications:
Medical technology / Pharmaceutics / Microelectronics / Nanotechnology / Micromechanics / Bio-engineering and Genetic engineering / Laborities /
Pharmaceutical Industry / Automotive Industry / Food and Beverage Industry and also suitable for all sterile applications.
Dimensions
WxHxD
Prefilter
Nominal
Airflow
Filter Initial
Pressure Drop
(mm)
(EN779)
(m³/h)
H14 (Pa)
610x610x390
G4
600
125
FFU-H14-ASM-610x915/4
610x915x390
G4
900
125
FFU-H14-ASM-610x1220/4
610x1220x390
G4
1200
125
Filter Model
FFU-H14-ASM-610x610/4
FFU-H14-ASM-610x1220/4S
Unit Type
Unit Frame
FFU :Fan Filter Unit
No Mark: Standard Aluminium
Filter Class
H13
S
H14
:Stainless Steel
G : Galvanised Steel
(powder coated)
H15
Design
Prefilter
ASM
:Seperated
G
:Gel Type
No Mark
:Compact
4 :G4 (EN779)
Widht x Height
(mm x mm)
7 : F7 (EN779)
WxH
Unit Model
Seperated
Gel Type
Compact
HEPA / ULPA
HEPA / ULPA
HEPA / ULPA
0,45
0,45
0,45
Filter Type
ASM
ANJ, AJ,AMJ,ALJ
Special
Unit Model
Fan Filter
FFU
Motor Type
AC / EC
AC / EC
AC / EC
Filter Class
H14 (EN1822)
H14
Differantial Pressure Gauge
Optional
Optional
Optional
Design
Seperated
ASM
Variable Speed Controller
Optional
Optional
Optional
Filter Dimensions
WxH (mm)
610x610
Recommended Prefilters
G4 / F7
G4 / F7
G4 / F7
Prefilter
G4
Filter Replacement Side
Ceiling
Room
Ceiling
Unit Frame
Aluminium
Filter
Nominal Air Velocity
FFU-H14-ASM-610x610/4
ADVANCED FILTRATION FOR A BETTER FUTURE!
www.ulpatek.com
4
No Mark